    WM 550-141-996/1 105 Page 1 RWB 6104WMNX R1005 Beckett Model NX Burner  Please read and follow all instructions on Page 3 in this manual regarding your responsibilities in caring for you r heating equipment Contact a qualified service agency for installation and start-up. Incorrect Installation, adjustment, or misuse of this burner could resu ...

  • Weil-McLain NX - page 2

    Page 2 WM 550-141-996/1 105 RWB 6104WMNX R1005 T able of Contents Hazard De fi nitions and Owner ’ s Information ........................................................................................ 3 Information T o Be Used Only By Quali fi ed Service T echnicians Weil McLain Burner Speci fi cation ......................................... ...

  • Weil-McLain NX - page 3

    WM 550-141-996/1 105 Page 3 RWB 6104WMNX R1005 T o the Owner: Thank you for purchasing a Beckett NX burner for use with your heating appliance. Please pay atten- tion to the Safety W arnings contained within this in- struction manual. Keep this manual for your records and provide it to your quali fi ed service agency for use in professionally sett ...

  • Weil-McLain NX - page 4

    Page 4 WM 550-141-996/1 105 RWB 6104WMNX R1005 V erify that burner speci fi cation number (on burner carton) and con fi guration agrees with information below . T able 1. Burner Con fi gurations The table below provides burner speci fi cations and starting air settings for NX burners applied to Weil-McLain Model UO boilers. Follow all instructi ...

  • Weil-McLain NX - page 5

    WM 550-141-996/1 105 Page 5 RWB 6104WMNX R1005 General Speci fi cations T able 2 – Burner Speci fi cations Capacity LB & LC Firing rate 0.40 – 1.35 GPH Input 56,000 – 189,000 Btu LD & LF Firing rate 1.10 - 1.75 GPH Input 154,000 – 245,000 Btu/h Fuels U. S No. 1 or No. 2 heating oil only ........... (ASTM D396) Canada No. 1 stove o ...

  • Weil-McLain NX - page 6

    Page 6 WM 550-141-996/1 105 RWB 6104WMNX R1005 Figure 1. Burner label location State and local approvals are shown on burner rat- ing label mounted on the burner housing. For recommended installation practice in Canada, refer to the latest version of CSA Standard B139 & B140. General Speci fi cations Notice Special Requirements Concealed damag ...

  • Weil-McLain NX - page 7

    WM 550-141-996/1 105 Page 7 RWB 6104WMNX R1005 Inspect/Prepare Installation Site Clearances to Burner and Appliance Provide space around burner and appliance for ease of service and maintenance. Check the minimum clearances against those shown by the appliance manufacturer and by ap- plicable building codes. Inspect Chimney or Direct V ent System I ...

  • Weil-McLain NX - page 8

    Page 8 WM 550-141-996/1 105 RWB 6104WMNX R1005 Fuel Line V alves and Filter Install two high quality oil duty rated shutoff valves in accessible locations on the oil supply line. Locate one close to the tank and the other close to the burner , upstream of the fi lter . Also install a generous capacity fi lter , rated for 50 microns or less, insid ...

  • Weil-McLain NX - page 9

    WM 550-141-996/1 105 Page 9 RWB 6104WMNX R1005 Warning – By-pass Plug in 2 Pipe System The burner pump is shipped without the by-pass plug installed. You must install this plug on two-pipe oil systems. If the unit is a one-pipe oil system DO NOT install the plug in the pump. Failure to comply could cause pump seal failure, oil leakage and the pot ...

  • Weil-McLain NX - page 10

    Page 10 WM 550-141-996/1 105 RWB 6104WMNX R1005 Figure 3. – Burner Connections. Bur ner Prepar ation SK9806 ...

  • Weil-McLain NX - page 11

    WM 550-141-996/1 105 Page 1 1 RWB 6104WMNX R1005 G R R BK W O V BL/W BURNER JUNCTION BO X BURNER PRIMAR Y CONTROL 3/T T CAD CELL IGNITOR SOLENOID VA LV E Y Y W W W LIMIT L1 L2 L2 L2 L2 VA LV E IGNITOR MOT OR W BK R7184P Primary ontrol C T 1 2 BE R MOT OR URN R BK W PRESSURE SWITCH (DIRECT VENT ONL Y) Burners with Beckett Clean Cut Pump must be used ...

  • Weil-McLain NX - page 12

    Page 12 WM 550-141-996/1 105 RWB 6104WMNX R1005 Start the Burner and Set Combustion Start-up and Initial Settings Open the shutoff valves in the oil supply line to the burner . Referencing Figure 5 verify and/or set the Head/ Air Adjustment Pointer to the value shown in T able 1. This is an initial air setting for the pump bleeding procedure only . ...

  • Weil-McLain NX - page 13

    WM 550-141-996/1 105 Page 13 RWB 6104WMNX R1005 Chimney V ent Systems: Install the burner cover and repeat Steps 2 and 4 above. If CO 2 increas- es (O 2 decreases), remove the cover and adjust the air setting so the CO 2 (O 2 ) with the cover installed meets the requirements of Step 3. Direct V ent Systems with Outside Air Ducted to Burner: Install ...

  • Weil-McLain NX - page 14

    Page 14 WM 550-141-996/1 105 RWB 6104WMNX R1005 Warning–Professional Service Required This equipment must be installed, adjusted and put into operation only by a qualified individual or service agency that is: x Licensed or certified to install and provide technical service to oil heating systems. x Experienced with all applicable codes, st ...

  • Weil-McLain NX - page 15

    WM 550-141-996/1 105 Page 15 RWB 6104WMNX R1005 Nozzle Installation Obtain a nozzle having the capacity , spray angle, and pattern speci fi ed in the appliance manufac- turer ’s information or Beckett OEM Speci fi cation Guide, Part # 671 1. Make certain the correct nozzle is selected for the actual fuel pump pressure. See T able 1. Perform the ...

  • Weil-McLain NX - page 16

    Page 16 WM 550-141-996/1 105 RWB 6104WMNX R1005 Check/Adjust Electrodes Check the electrode tip settings, as shown in Fig- ure 7. If necessary , adjust by loosening the elec- trode clamp screw (Figure 8) and slide/rotate the electrodes as necessary . When the adjustment is complete, securely tighten the clamp screw . Check Retention Head Alignment ...

  • Weil-McLain NX - page 17

    WM 550-141-996/1 105 Page 17 RWB 6104WMNX R1005 Professional Maintenance Blower Wheel Replacement For installation or replacement of a blower wheel, insure that there is a space between the blower wheel and the motor face of 0.1 15”. Refer to Figure 10. • Figure 10. – Blower wheel assembly SK9670 ...

  • Weil-McLain NX - page 18

    Page 18 WM 550-141-996/1 105 RWB 6104WMNX R1005 For best performance specify genuine Beckett replacement parts Replacement Parts Diagram Professional Maintenance SK967102 SK9803B SK9804B ...

  • Weil-McLain NX - page 19

    WM 550-141-996/1 105 Page 19 RWB 6104WMNX R1005 Item Description Part No. 1 Head/Air adjustment mecha- nism assembly 51794U 2 Air guide 101 101U 3 Gasket, mounting fl ange (not shown) 32389 4 Air tube combination, (Includes Screws, air tube mounting #8 x 3/8) Specify 4396 5 Blower wheel 2999U 6 Connector tube assembly , 1 1” 51 127 7 Coupling 24 ...

  • Weil-McLain NX - page 20

    Page 20 WM 550-141-996/1 105 RWB 6104WMNX R1005 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett for resale or for incorporation into a product for resale (“Customers”) that its equipment is free from defects in mate ...

Fabbricante Weil-McLain Categoria Burner

I documenti che otteniamo dal fabbricante del dispositivoWeil-McLain NX possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Weil-McLain
- manuali per l’uso NX
- schede prodotto Weil-McLain
- opuscoli
- o etichette energetiche Weil-McLain NX
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Weil-McLain NX.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Weil-McLain NX, manuali di manutenzione, brevi manuali o manuali utente Weil-McLain NX. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Weil-McLain NX.

Manuali per l’uso simili

Manuale completo del dispositivo Weil-McLain NX, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Weil-McLain NX dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Weil-McLain NX.

Il manuale per l’uso completo Weil-McLain, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Weil-McLain NX - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Weil-McLain NX, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Weil-McLain NX che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Weil-McLain NX - che ci dovrebbe aiutare nei primi passi durante l'uso Weil-McLain NX
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Weil-McLain NX
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Weil-McLain NX in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Weil-McLain NX?

Utilizza il modulo sottostante

Se non hai risolto il problema con Weil-McLain NX con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Weil-McLain NX è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)