    340AAV 4-Way Multipoise Fixed-Capacity Condensing Gas Furnace Sizes 040 thru 140 Product Data The model 340AAV Multipoise Condensing Furnace is specifi- cally designed to meet the needs of the new construction market. This high-efficiency furnace utilizes a unique 4-way multipoise design and compact size to fit where other fur- naces will not. The ...

  • Bryant 340AAV - page 2

    —2— 340AAV A05070 NO TE S : 1. Minim u m ret u rn - a ir opening s a t f u rn a ce, bas ed on met a l d u ct. If flex d u ct i s us ed, s ee flex d u ct m a n u f a ct u rerí s recommend a tion s f or e qu iv a lent di a meter s . 2. Minim u m ret u rn - a ir opening a t f u rn a ce: a .F o r 8 00 CFM–16-in. ro u nd or 14 1 / 2 x 12-in. rect ...

  • Bryant 340AAV - page 3

    —3— 340AAV Thi s for ced ai r fur nac e i s equi pped for use w i th natur al gas at alt i t udes 0 - 10, 000 f t (0 - 3, 050m), except 140 si ze F ur naces a re only approved for alt it udes 0 - 7,000 ft . (0 - 2,135m). An acce ssor y ki t, sup pl i ed by the manuf act ur er , sha ll be used to co nver t t o propan e gas use or ma y be requi r ...

  • Bryant 340AAV - page 4

    —4— 340AAV Controls—Thermostats and Zoning Non-Programmable Thermostat Selection * Model HP and 2S thermostat must be field converted to air conditioner operation. **Thermidistat Control is versatile and can be configured for multiple use and staging, it must be configured for each specific application. Programmable Thermostat Selection * Mod ...

  • Bryant 340AAV - page 5

    —5— 340AAV SPECIFICATIONS See notes on page 7. UNIT SIZE 024040 036040 024060 036060 048060 036080 RATINGS AND PERFORMANCE Input Btuh* 40,000 40,000 60,000 60,000 60,000 80,000 Output Capacity BTUH* (ICS) (Shaded capacities are specified on rat- ing plate) Direct Vent (2-Pipe) Upflow 37,000 37,000 56,000 56,000 56,000 74,000 Downflow 37,000 37, ...

  • Bryant 340AAV - page 6

    —6— 340AAV SPECIFICATIONS See notes on page 7. UNIT SIZE 048080 060080 048100 060100 060120 060140 RATINGS AND PERFORMANCE Input Btuh* 80,000 80,000 100,000 100,000 120,000 140,000 Output Capacity BTUH* (ICS) (Shaded capacities are specified on rat- ing plate) Direct Vent (2-Pipe) Upflow 74,000 74,000 93,000 93,000 112,000 127,000 Downflow 74,0 ...

  • Bryant 340AAV - page 7

    —7— 340AAV * Gas input ratings are certified for elev ations to 2000 ft. F or elevations abo ve 2000 ft, reduce ratings 2% f or each 1000 ft above sea le vel. In Canada, derate the unit 5% from 2000 to 4500 ft abov e sea lev el. † Capacity and AFUE in accordance with U .S. Government DOE test procedures. ‡ Airflow shown is f or bottom onl ...

  • Bryant 340AAV - page 8

    —8— 340AAV COMBUSTION-AIR AND VENT PIPING Direct-Vent/2-Pipe (All Sizes) and Non-Direct Vent/1-Pipe (Sizes 040 Through 120 Only) Applications MAXIMUM ALLOWABLE PIPE LENGTH (FT) ALTITUDE (FT) UNIT SIZE (BTUH) DIRECT VENT (2-PIPE) ONLY NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90° ELBOWS TERMINATION TYPE PIPE DIA (IN.)* PIPE DIA (IN.)* 12 3 4 5 6 ...

  • Bryant 340AAV - page 9

    —9— 340AAV COMBUSTION-AIR AND VENT PIPING Direct-Vent/2-Pipe (All Sizes) and Non-Direct Vent/1-Pipe (Sizes 040 Through 120 Only) Applications MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED) ALTITUDE (FT) UNIT SIZE (BTUH) DIRECT VENT (2-PIPE) ONLY NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90° ELBOWS TERMINATION TYPE PIPE DIA (IN.)* PIPE DIA (IN.)* ...

  • Bryant 340AAV - page 10

    —1 0— 340AAV COMBUSTION-AIR AND VENT PIPING Direct-Vent/2-Pipe (All Sizes) and Non-Direct Vent/1-Pipe (Sizes 040 Through 120 Only) Applications MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED) ALTITUDE (FT) UNIT SIZE (BTUH) DIRECT VENT (2-PIPE) ONLY NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90° ELBOWS TERMINATION TYPE PIPE DIA (IN.)* PIPE DIA (IN. ...

  • Bryant 340AAV - page 11

    —1 1— 340AAV MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION IN WINTER DESIGN TEMPERATURE AMBIENT* * Pipe length (ft) specified for maximum vent pipe lengths located in unconditioned spaces. Vent pipes located in unconditioned space cannot exceed the total allowable pipe length as specified in Maximum Allowable Pipe ...

  • Bryant 340AAV - page 12

    —1 2— 340AAV ACCESSORIES SIDE FILTER RACK* DIMENSIONS (In.) * Dimension A will change accordingly as dimension D is lengthened or shortened. † Dimension D may be lengthened to 60 in. maximum. Dimension D may also be shortened by cutting the pipes provided in the kit to 12 in. minimum. * The plenum should be constructed 1/4 in. smaller in widt ...

  • Bryant 340AAV - page 13

    —1 3— 340AAV AIR DELIVERY—CFM (With Filter)* * A filter is required f or each return-air supply . • For horiz ontal and downflow applications , use “1 side or bottom ” or “bottom only ” as airflow ref erence. UNIT SIZE RETURN-AIR SUPPLY SPEED EXTERNAL STATIC PRESSURE (In. wc) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 024040 1 side or botto ...

  • Bryant 340AAV - page 14

    —1 4— 340AAV COMBU S TION AIR PIPE (DIRECT VENT/2-PIPE APPLICATION) A/C COIL OUTDOOR UNIT VENT PIPE HUMIDIFIER GA S -FIRED WATER HEATER ELECTRONIC AIR CLEANER AIRFLOW FRONT OF FURNACE COMBU S TION AIR INLET (NON-DIRECT 1-PIPE APPLICATION) A05064 ELECTRONIC AIR CLEANER HUMIDIFIER A/C COIL VENT COMBU S TION AIR (DIRECT VENT/ 2 PIPE APPLICATION OU ...

  • Bryant 340AAV - page 15

    —1 5— 340AAV COMBU S TION–AIR PIPE ELECTRONIC AIR CLEANER FURNACE CONDEN S ATE DRAIN REFRIGERATION PIPING AIR CONDITIONING COIL AIRFLOW VENT PIPE FRONT OF FURNACE A05066 DIRECT VENT/2-PIPE APPLICATION) COMBU S TION-AIR INLET (NON-DIRECT VENT/1-PIPE APPLICATION) COMBU S TION– AIR PIPE (DIRECT VENT/2-PIPE APPLICATION) VENT PIPE ELECTRONIC AIR ...

  • Bryant 340AAV - page 16

    —1 6— ©Bryant Heating & Cooling systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. edition date: 01/06 Catalog No. PDS 340A.40.2 Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations Replaces: PDS 340A.40.1 GENERAL System Description Furnish a _________________ (4- ...

Fabbricante Bryant Categoria Furnace

I documenti che otteniamo dal fabbricante del dispositivoBryant 340AAV possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 340AAV
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 340AAV
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 340AAV.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 340AAV, manuali di manutenzione, brevi manuali o manuali utente Bryant 340AAV. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 340AAV.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 340AAV, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 340AAV dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 340AAV.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 340AAV - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 340AAV, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 340AAV che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 340AAV - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 340AAV
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 340AAV
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 340AAV in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 340AAV?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 340AAV con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 340AAV è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)