    P RODUCT S PECIFICA TIONS SS-PCB50 www .goodmanmfg.com 6/06 Supersedes 12/05 S ELF -C ONT AINED P ACKAGE A IR C ONDITIONER The PCB Commercial 50 Hz self-contained packaged air conditioner is designed for ground-level or rooftop application. PCB C OMMERCIAL S ERIES 50 Hz C OOLING C AP ACITY : 90,000 TO 180,000 BTU/ H 7½, 10, AND 15 T ON [26.4 kW to ...

  • Franklin SS-PCB50 - page 2

    2 SS-PCB50 P RODUCT S PECIFICA TIONS S PECIFICA TIONS PCB090-5 PCB120-5 PCB180-5 T otal Cooling - BTU/h (kW) 88,400 (25.9) 118,600 (34.8) 172,000 (50.4) Sensible Cooling - BTU/h¹ (kW) 67,100 (19.7) 89,200 (26.1) 131,000 (38.4) EER² 8.9 9.7 8.5 Indoor Blower (Qty .) 2 2 2 T ype Belt Belt Belt Size - D x W (mm) 12 x 12 (305 x 305) 12 x 15 (305 x 38 ...

  • Franklin SS-PCB50 - page 3

    SS-PCB50 3 P RODUCT S PECIFICA TIONS UNIT SIZE A - HEIGHT B - SUPPL Y AIR C - RETURN AIR 090 36” (914 mm) 12½” (318 mm) 179/16” (446 mm) 120,180 52” (1321 mm) 20¼” (514 mm) 2513/16” (656 mm) D IMENSIONS All dimensions in inches and millimeters. Drawings are not to scale. Note: The Horizontal Conversion K it is required to convert a fa ...

  • Franklin SS-PCB50 - page 4

    4 SS-PCB50 P RODUCT S PECIFICA TIONS E LECTRICAL C ONNECTIONS Main power entrance location (with electric heat installed) Control wiring entrance location Main power entrance location (without electric heat installed) Note: Single-point wiring is available at location #1 when heat kit is installed. See installation instructions for heat kits. 1– ...

  • Franklin SS-PCB50 - page 5

    SS-PCB50 5 P RODUCT S PECIFICA TIONS CFM EXTERNAL ST A TIC PRESSURE (INCHES W .C.) SEE NOTE (3) 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 2600 669 0.44 816 0.59 916 0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67 2800 734 0.53 847 0.69 944 0.85 1030 1.03 1109 1.21 1181 1.40 1249 1.60 1312 ...

  • Franklin SS-PCB50 - page 6

    6 SS-PCB50 P RODUCT S PECIFICA TIONS Motor Sheave - Adjustable Factory Setting F an Sheave - Fixed T wo T urns Opens Motor Sheave T urns Open 0 1 2 3 4 5 F an RPM 3.0 HP Motor 1242 1186 1129 1073 1016 960 Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances. Conversion F actor: 1 CFM = 0.472 L/S 1” W .C. = 2.5 M Bar 1 H ...

  • Franklin SS-PCB50 - page 7

    SS-PCB50 7 P RODUCT S PECIFICA TIONS Motor Sheave - Adjustable Factory Setting F an Sheave - Fixed 2 T urns Opens Motor Sheave T urns Open 012345 F an RPM 5.0 HP Motor 1400 1446 1273 1209 1146 1082 Note: Allow ±5% variation in blower RPM due to pulley manufacturing tolerances. Conversion F actor: 1 CFM = 0.472 L/S 1” W .C. = 2.5 M Bar 1 HP = 0.7 ...

  • Franklin SS-PCB50 - page 8

    8 SS-PCB50 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 75°F 85°F 95°F 105°F 115°F SCFM WB To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw 2550 72 111.8 52.8 8.36 104.6 49.6 9.29 97.5 46.3 10.23 90.3 43.0 11.17 83.1 39.7 12.10 67 ...

  • Franklin SS-PCB50 - page 9

    SS-PCB50 9 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 23.9°C 29.4°C 35.0°C 40.6°C 46.1°C L/S WB T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw T otal Cap. Sens Cap. Kw 2246 22.2 64.17 29.53 16.42 60.17 28.00 18.63 56.17 26.48 20.83 52.17 24.95 23.04 48.17 23.43 25.25 19. ...

  • Franklin SS-PCB50 - page 10

    10 SS-PCB50 P RODUCT S PECIFICA TIONS INDOOR AIR CONDENSER AIR TEMPERA TURE 75°F 85°F 95°F 105°F 115°F SCFM WB To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw To t a l Kbtuh Sens Kbtuh Kw 4760 72 219.0 100.8 16.42 205.3 95.6 18.63 191.7 90.4 20.83 178.0 85.1 23.04 164.4 79.9 2 ...

  • Franklin SS-PCB50 - page 11

    SS-PCB50 11 P RODUCT S PECIFICA TIONS F ACT OR Y S UPPLIED A CCESSORIES T HERMOST A T (CHT90-120) T wo-stage cool and two-stage heat thermostat with subbase, Manual changeover , Fan ON or AUT O. Note: A variety of thermostat con fi gurations can be used on this equipment based on the application needs. For example our CHTS36-60 can be used if two- ...

  • Franklin SS-PCB50 - page 12

    12 SS-PCB50 P RODUCT S PECIFICA TIONS Q UALITY M AKES THE D IFFERENCE ! All of our systems are designed and manufactured with the same high-quality standards, regardless of size or ef fi ciency . W e have designed these units to signi fi cantly reduce the most frequent causes of product failure. They are simple to service and forgiving to operate ...

Fabbricante Franklin Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoFranklin SS-PCB50 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Franklin
- manuali per l’uso SS-PCB50
- schede prodotto Franklin
- opuscoli
- o etichette energetiche Franklin SS-PCB50
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Franklin SS-PCB50.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Franklin SS-PCB50, manuali di manutenzione, brevi manuali o manuali utente Franklin SS-PCB50. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Franklin SS-PCB50.

Manuali per l’uso simili

Manuale completo del dispositivo Franklin SS-PCB50, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Franklin SS-PCB50 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Franklin SS-PCB50.

Il manuale per l’uso completo Franklin, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Franklin SS-PCB50 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Franklin SS-PCB50, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Franklin SS-PCB50 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Franklin SS-PCB50 - che ci dovrebbe aiutare nei primi passi durante l'uso Franklin SS-PCB50
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Franklin SS-PCB50
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Franklin SS-PCB50 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Franklin SS-PCB50?

Utilizza il modulo sottostante

Se non hai risolto il problema con Franklin SS-PCB50 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Franklin SS-PCB50 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)