    Order No.: 452159.67.07 FD 8602 CE INST ALLA TION and OPERA TING INSTRUCTIONS Air-to-W ater Heat Pump for Outdoor installation L A 6M R LA 12TR L A 8M R LA 16TR L A 10MR ...

  • Dimplex LA 10MR - page 2

    2 1 READ IMMEDIA TEL Y 3 1.1 Important Information 1. 2 Legal Provisions and Guidelines 1. 3 Energy-Efficient Use of the Heat Pump 2 PURPOSE OF HEA T PUMP 4 2. 1 Field of Application 2. 2 Principle of Operation 3 SCOPE OF DELIVER Y 4 3. 1 Baseline Unit 3. 2 Control Box 4 TRANSPORT 5 5 INST ALLA TION 5 5.1 General 5.2 Condensate Line 6 MOUNTING 6 6. ...

  • Dimplex LA 10MR - page 3

    3 READ IMMEDIA TEL Y 1.1 Important Information Do not open the unit unless all electrical circuits have been disconnected from the power supply . During transport, the heat pump must not be tilted more than 45 ° (in either direction). Heat pump and transport pallet are only connected by the packaging film. The air intake and discharge openings mus ...

  • Dimplex LA 10MR - page 4

    4 PURPOSE OF HEA T PUMP SCOPE OF DELIVER Y PURPOSE OF HEA T PUMP 2.1 Field of Application The air-to-water heat pump is intended for use in existing or newly built heating systems. The heat pump is designed for the cooling or heating of water for heating purposes and the supply of domestic hot water! The heat pump is suitable for mono-energetic and ...

  • Dimplex LA 10MR - page 5

    5 TRANSPORT INST ALLA TION 4 CAUTION! TRANSPORT During transport, the heat pump must not be tilted more than 45 ° (in either direction). The unit should be transported to the final installation site on a wooden pallet. The heat pump can be transported either by means of a lift truck or using 3/4" pipes to be passed through the openings provid ...

  • Dimplex LA 10MR - page 6

    6 MOUNTING 6 MOUNTING 6.1 General The following connections need to be established on the heat pump: - supply/return lines of the heating system - condensate drain - control lead to the remote control - power supply 6.2 Heating-Side Connection The connections on the heating side of the heat pump are provided with 1"external thread (flat sealin ...

  • Dimplex LA 10MR - page 7

    7 COMMISSIONING 7 COMMISSIONING 7.1 General T o ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer . Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service). 7.2 Preparatory Steps Prior to commissioning, the following items need to be checked: - All c ...

  • Dimplex LA 10MR - page 8

    8 FUNCTIONAL DESCRIPTION 8 FUNCTIONAL DESCRIPTION 8.1 Heat Pump Remote Control Unit The heat pump can be switched on and off by means of the remote control positioned inside the building. Switching off in this case means switching to a "standby" function, i.e. as long as the heat pump is supplied with mains power , the frost protection fu ...

  • Dimplex LA 10MR - page 9

    9 CLEANING / CARE 9. 1 Care T o protect the paint finish, avoid placing objects against or on the unit. The external parts of the heat pump can be wiped with a damp cloth and commercially available cleaning agents. Do not use any cleaning agents containing sand, soda, acid or chloride as these may damage the surface. T o prevent malfunctions due to ...

  • Dimplex LA 10MR - page 10

    10 CLEANING / CARE MALFUNCTIONS / TROUBLESHOOTING DECOMMISSIONING Caution - Heating Contractors Depending on the water quality and quantity , in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form impairing the proper functioning of the heating installation. A cause of this is the water har ...

  • Dimplex LA 10MR - page 11

    11 APPENDIX 12.1 DIMENSIONED DRAWING 1 2 12.2 EQUIPMENT D A T A 13 12.3 SCHEMA TICS 12.3.1 Heating mode LA 6MR 14 12.3.2 Cooling mode LA 6MR 15 12.3.3 Heating mode LA 8MR 16 12.3.4 Cooling mode LA 8MR 17 12.3.5 Heating mode LA 10MR 18 12.3.6 Cooling mode LA 10MR 19 12.3.7 Heating mode LA 12TR 20 12.3.8 Cooling mode LA 12TR 21 12.3.9 Heating mode LA ...

  • Dimplex LA 10MR - page 12

    12 Dimensioned Drawing APPENDIX: 12.1 DIMENSIONED DRAWING 35 (circumferential) Electr . connection box (inspection side) Air discharge end Condensate drain Condensate drain Condensate pan Condensate tube (plastic) Soil to sewer ( Base frame ) Feed-through Electric lines Heating water Return G 1” external thread Heating water Supply G 1” externa ...

  • Dimplex LA 10MR - page 13

    13 EQUIPMENT DATA for air-to-water heat pumps for heating 1 TYPE AND COMMERCIAL DESCRIPTION LA06MRN LA08MRN LA10MRN LA12TRN LA16TRN 2 MODEL 2.1 Type reversible reversible reversible reversible reversible 2.2 Enclosure type acc. to EN 60 529 for compact unit and/or heating element IP 24 IP 24 IP 24 IP 24 IP 24 2.3 Installation site outdoors outdoors ...

  • Dimplex LA 10MR - page 14

    14 0 1 2 3 4 5 6 7 8 9 10 11 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Heizleistung in [kW ] 35 50 W asseraustritts temperatur in [°C] 0 1 2 3 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 50 35 40 0 1 2 3 4 5 6 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur i ...

  • Dimplex LA 10MR - page 15

    15 12.3.2 Cooling mode LA 6MR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Kühlleistung in [k W ] 18 8 W asseraustritts temperatur in [°C] 0 1 2 3 4 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 18 8 0 1 2 3 4 5 6 7 10 15 ...

  • Dimplex LA 10MR - page 16

    16 0 1 2 3 4 5 6 7 8 9 10 11 12 13 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Heizleistung in [kW ] 35 50 W asseraustritts temperatur in [°C] 0 1 2 3 4 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 50 35 40 0 1 2 3 4 5 6 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem p ...

  • Dimplex LA 10MR - page 17

    17 12.3.4 Cooling mode LA 8MR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 16 18 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Kühlleistung in [k W ] 18 8 W asseraus trittstemperatur in [°C] 0 1 2 3 4 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 18 8 0 1 2 3 4 5 6 7 ...

  • Dimplex LA 10MR - page 18

    18 12.3.5 Heating mode LA 10MR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 16 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Heizleistung in [kW ] 35 50 W asseraustritts temperatur in [°C] 0 1 2 3 4 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 50 35 0 1 2 3 4 5 6 7 - ...

  • Dimplex LA 10MR - page 19

    19 12.3.6 Cooling mode LA 10MR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 16 18 20 22 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Kühlleistung in [k W ] 18 8 W asseraus trittstemperatur in [°C] 0 1 2 3 4 5 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 18 8 0 1 2 ...

  • Dimplex LA 10MR - page 20

    20 12.3.7 Heating mode LA 12TR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 16 18 20 22 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Heizleistung in [kW ] 35 50 W asseraustritts temperatur in [°C] 0 1 2 3 4 5 - 2 0 - 1 0 0 1 0 2 03 04 0 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 50 35 40 0 ...

  • Dimplex LA 10MR - page 21

    21 APPENDIX: 12.3 SCHEMA TICS 12.3.8 Cooling mode LA 12TR 0 5 10 15 20 25 30 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Kühlleistung in [k W ] 18 8 W asseraus trittstemperatur in [°C] 0 1 2 3 4 5 6 7 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 18 8 0 1 2 3 4 5 6 ...

  • Dimplex LA 10MR - page 22

    22 12.3.9 Heating mode LA 16TR APPENDIX: 12.3 SCHEMA TICS 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Heizleistung in [kW ] 35 50 W asseraustritts temperatur in [°C] 0 1 2 3 4 5 6 7 - 2 0 - 1 0 0 1 02 03 04 0 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) ...

  • Dimplex LA 10MR - page 23

    23 APPENDIX: 12.3 SCHEMA TICS 12.3.10 Cooling mode LA 16TR 0 5 10 15 20 25 30 35 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Kühlleistung in [k W ] 18 8 W asseraus trittstemperatur in [°C] 0 1 2 3 4 5 6 7 8 10 15 20 25 30 35 40 45 50 Lufteintrittstem peratur in [°C] Leistungsauf nahme (incl. Pum penleistungsanteil) 18 8 0 1 2 3 ...

  • Dimplex LA 10MR - page 24

    24 12.4.1 Control LA 6MR-LA 10MR APPENDIX: 12.4 WIRING DIAGRAMS ON/OFF Call Heating/cooling Copressor Fan Reversing valve Heating circulating pump Back-up heater Attention! Low voltage Supply sensor External sensor FSK sensor Setpoint Coding On/Off Cooling Setpoint ...

  • Dimplex LA 10MR - page 25

    25 12.4.2 Load LA 6MR-LA 10MR APPENDIX: 12.4 WIRING DIAGRAMS Jumper 4kW Jumper 6kW Mains supply Back-up heater Mains supply ...

  • Dimplex LA 10MR - page 26

    26 APPENDIX: 12.4 WIRING DIAGRAMS 12.4.3 T erminal Diagram LA 6MR-LA 10MR Jumper 4kW ye/gn ye/gn Jumper 6kW Mains supply Mains supply for back-up heater Switch box LA 6-10 Connecting lead Connecting lead ...

  • Dimplex LA 10MR - page 27

    27 A1 Wire jumper: The jumper must be removed for external control (via potential-free contact) or when a dew point monitor (via potential-free contact) is used. B3* Thermostat, hot water B5 Control thermostat, back-up heater C1 Operating capacitor , compressor C3 Operating capacitor , fan E3 Pressostat, defrost end E4 Nozzle ring heater E10 Back-u ...

  • Dimplex LA 10MR - page 28

    28 APPENDIX: 12.4 WIRING DIAGRAMS 12.4.5 Control LA 12TR-LA 16TR Call Heating/cooling Copressor Fan Reversing valve Heating circulating pump Back-up heater Attention! Low voltage Supply sensor External sensor FSK sensor Setpoint Coding Cooling Setpoint ...

  • Dimplex LA 10MR - page 29

    29 APPENDIX: 12.4 WIRING DIAGRAMS 12.4.6 Load LA 12TR-LA 16TR Mains supply - load ...

  • Dimplex LA 10MR - page 30

    30 APPENDIX: 12.4 WIRING DIAGRAMS 12.4.7 T erminal Diagram LA 12TR-LA 16TR ye/gn Mains supply Connecting lead Switch box LA 12-16 ...

  • Dimplex LA 10MR - page 31

    31 12.4.8 Legend LA 12TR-LA 16TR A1 Wire jumper: For external control (via potential-free contact) or use of a dew point monitor (via potential-free contact) the jumper must be removed. B3* Hot water thermostat B5 Control thermostat, back-up heater E3 Pressostat defrost end E4 Nozzle ring heater E10 Back-up heater F1 Control-circuit fuse F4 Pressos ...

  • Dimplex LA 10MR - page 32

    32 12.5.1 Mono-energetic system APPENDIX: 12.5 HYDRA ULIC BLOCK DIAGRAMS Overflow valve Safety assembly Circulating pump Expansion vessel Thermostat/manual valve Shut-off valve with drain Heat consumers T emperature sensor Flexible connecting hose Electric distribution Electric heating element Heating system circulating pump Remote control External ...

  • Dimplex LA 10MR - page 33

    33 APPENDIX: 12.5 HYDRA ULIC BLOCK DIAGRAMS 12.5.2 Mono-energetic systems and domestic hot water function Overflow valve Safety assembly Circulating pump Expansion vessel Thermostat/manual valve Three-way valve Shut-off valve with drain Heat consumers Air-to-water heat pump Buffer tank Hot water tank T emperature sensor Flexible connecting hose Ele ...

  • Dimplex LA 10MR - page 34

    34 EC Declaration of Conformity APPENDIX: 12.6 EC DECLARA TION OF CONFORMITY Declaration of Conformity The undersigned Glen Dimplex Deutschland GmbH Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach her eby confirm that the design and construction of the pr oduct(s) listed below , in the version(s) placed on the market by us, conform to the r e ...

  • Dimplex LA 10MR - page 35

    Notes 35 ...

  • Dimplex LA 10MR - page 36

    Glen Dimplex Deutschland GmbH Subject to technical modifications Division Dimplex T elefax (0 92 21) 709-589 Am Goldenen Feld 18 www .dimplex.de D-95326 Kulmbach ...

Fabbricante Dimplex Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoDimplex LA 10MR possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Dimplex
- manuali per l’uso LA 10MR
- schede prodotto Dimplex
- opuscoli
- o etichette energetiche Dimplex LA 10MR
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Dimplex LA 10MR.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Dimplex LA 10MR, manuali di manutenzione, brevi manuali o manuali utente Dimplex LA 10MR. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Dimplex LA 10MR.

Manuali per l’uso simili

Manuale completo del dispositivo Dimplex LA 10MR, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Dimplex LA 10MR dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Dimplex LA 10MR.

Il manuale per l’uso completo Dimplex, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Dimplex LA 10MR - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Dimplex LA 10MR, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Dimplex LA 10MR che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Dimplex LA 10MR - che ci dovrebbe aiutare nei primi passi durante l'uso Dimplex LA 10MR
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Dimplex LA 10MR
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Dimplex LA 10MR in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Dimplex LA 10MR?

Utilizza il modulo sottostante

Se non hai risolto il problema con Dimplex LA 10MR con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Dimplex LA 10MR è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)