    Installation & Operation Manual H-IM-79D February , 2004 Part Number 25001401 Replaces H-IM-79C (12/03) ™ ...

  • Heatcraft Refrigeration Products H-IM-79D - page 2

    2 Beacon II Board layout ........................................................................................................ 3 Installation T ips ................................................................................................................... 4 Brazing Power Supply Wiring ..................................................... ...

  • Heatcraft Refrigeration Products H-IM-79D - page 3

    3 Beacon II Board Layout BEACON II BOARD Heater Relay Fan Relay LED Display Room Sensor Defrost Sensor Suction Sensor Suction Pressure Expansion Va l v e Connection Selection Buttons 24V T erminal Block © 2004, Heatcraft Refrigeration Products LLC ...

  • Heatcraft Refrigeration Products H-IM-79D - page 4

    4 Installation T ips • Use a minimum 18 gauge wire for all low voltage connections. • The Beacon II board gets its 24 V AC power supply from a transformer mounted in the electrical end of each evaporator . On 208-240 volt systems the multi-tap transformer is shipped from our factory wired for 240 volts. If your supply voltage is 208 volt you mu ...

  • Heatcraft Refrigeration Products H-IM-79D - page 5

    5 Refrigerant Line Brazing ( CAUTION ) The electric expansion valve and the suction temperature sensor on the suction line are factory installed. Care must be taken when brazing these lines at the evaporator . T oo high a temperature may destroy these components. Heat absorbing compounds or “wet rags” must be used to protect the electric expans ...

  • Heatcraft Refrigeration Products H-IM-79D - page 6

    6 WIRING (cont ’ d.) • Multiple units – The multi-in and multi-out are the communication connections. Connection sequence must follow the multi-out terminal to the multi-in terminal and the multi-out back to the multi-in terminal in a daisy chain loop. • Alarm circuit - The onboard alarm is a dry set of NC contacts which closes to indicate ...

  • Heatcraft Refrigeration Products H-IM-79D - page 7

    7 BOX TEMPERA TURE CONTROL SETTINGS • There is an on board room thermostat on the Beacon II board which can be adjusted to the desired room temperature. The temperature dif ferential is 2 ° F. T emperature Differential When a system is in the cooling mode and the box setpoint is 35 ° F , the system will continue to cool until the box temperatur ...

  • Heatcraft Refrigeration Products H-IM-79D - page 8

    8 CU M M = Master Evaporator CU = Condensing unit Start-Up Operation SINGLE SYSTEM with 1 EV APORA TOR • Check all wiring connections to be sure they are correct and tight. • On condensing unit - Check the setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure switch setting on freezer units. I ...

  • Heatcraft Refrigeration Products H-IM-79D - page 9

    9 SINGLE SYSTEM with MUL TIPLE EV APORA TORS • Check all wiring connections to be sure they are correct and tight. • On Condensing unit - Check the setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure switch setting on freezer units. It must be set to 0 PSIG cutout, 10 PSIG cut-in to allow po ...

  • Heatcraft Refrigeration Products H-IM-79D - page 10

    10 MUL TIPLE SYSTEMS with MUL TIPLE EV APORA TORS (Requires a Smart Controller) • Check all wiring connections to be sure they are correct and tight. • On condensing units - Check setting of T ime Delay relay . It should be set at 1 minute (the second marker). - Check the Low Pressure Switch setting on freezer units. It must be set to 0 PSIG cu ...

  • Heatcraft Refrigeration Products H-IM-79D - page 11

    11 INITIAL POWER ON At the initial application of power to the system, the compressor and the evaporator fans will be in a 4 minute hold-off cycle and will not start immediately . When there is a call for COOLING, the expansion valve (EEV) opens, then the compressor is started. The compressor will then run for a minimum of 2 minutes in the “ hold ...

  • Heatcraft Refrigeration Products H-IM-79D - page 12

    12 PROGRAMMING AND REVIEWING SETTINGS/CHANGES The Program Review button is used to program, review and change all program settings for the system. Press “ PROGRAM REVIEW ” button. The Setpoint item will appear on the LED. After a few seconds delay the Setpoint value will display . Each time the button is pressed a different setpoint item is dis ...

  • Heatcraft Refrigeration Products H-IM-79D - page 13

    13 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont ’ d.) Use the “ PROGRAM REVIEW ” button to select these items: • Defrost T ype – “ A-E ” - Selection is made for air defrost or electric defrost coil. This will automatically set the system factory defaults for air defrost and electric defrost. (See default settings.) Please note tha ...

  • Heatcraft Refrigeration Products H-IM-79D - page 14

    14 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont ’ d.) • Alarm High T emperature - “ ALH ” - T emperature at which a high box temperature alarm will be triggered. This does not apply during defrost. Defaults: electric defrost +5 ° F and air defrost +50 ° F. • Alarm Low T emperature - “ ALL ” - T emperature at which a Low Box T em ...

  • Heatcraft Refrigeration Products H-IM-79D - page 15

    15 PROGRAMMING AND REVIEWING SETTINGS/CHANGES (cont ’ d.) Use this button to “ CLEAR/TEST ” Pressing this button ONCE will return the LED display to the default display . With the system in the OFF mode, pressing and holding this button will start the “ TEST ” mode. In the “ TEST ” mode it will cycle through each output for 10 seconds ...

  • Heatcraft Refrigeration Products H-IM-79D - page 16

    16 ST A TUS INDICA T OR LED • ERRORS E 1 - Room temperature sensor shorted, open or not installed E 2 - Defrost temperature sensor shorted, open or not installed E 3 - Suction temperature sensor shorted, open or not installed E 4 - Suction pressure transducer shorted, open or not installed E 5 - Outdoor temperature sensor shorted E 6 - Low superh ...

  • Heatcraft Refrigeration Products H-IM-79D - page 17

    17 Defrost DEFROST TIMING When power is first applied to the system, its timer starts counting time. If 4 defrost are programmed, it will initiate a defrost every 6 hours from when power was first applied. Beacon II does not have a real time clock. Beacon II does provide the ability to delay the starting of the first defrost. DEFROST DELA Y ST ART ...

  • Heatcraft Refrigeration Products H-IM-79D - page 18

    18 ELECTRIC DEFROST MODE When a defrost is initiated, the EEV closes, the compressor is allowed to pumpdown and shut of f. The evaporator fans are cycled of f and the defrost heaters are energized. On multiple evaporator systems, all controllers must terminate their defrost, either on temperature or fail-safe time, before the master controller will ...

  • Heatcraft Refrigeration Products H-IM-79D - page 19

    19 ERROR INDICA TOR LED At initial power up, each Beacon board checks for system errors. The system error check involves checking the various temperature sensors to determine whether any of these sensors are shorted or open. The system will pumpdown and cycle off and will not restart until the fault is cleared or the circuit breaker reset, for the ...

  • Heatcraft Refrigeration Products H-IM-79D - page 20

    20 CHECKING OPERA TION OF EXP ANSION V AL VE (EEV) T o check if the expansion valve is closing properly: Install a pressure gauge-set to suction line at the condensing unit. With the system running, close the valve on the liquid line, at the condensing unit. The system should pumpdown and shut of f on the Low Pressure switch (LPS). If the system do ...

  • Heatcraft Refrigeration Products H-IM-79D - page 21

    21 POWER F AILURES In the event of a power failure Beacon II will automatically close the expansion valve to prevent refrigerant from migrating throughout the system. After power returns, with 24 V AC at the board, the system will restart in the cooling mode after the four-minute hold of f period. SP ARE SENSOR TERMINALS Beacon II provides a set of ...

  • Heatcraft Refrigeration Products H-IM-79D - page 22

    22 System Defaults T able 2. System Defaults P ARAMETERS CODE AIR ELECTRIC Refrigerant rEF R-22 R-404A Box T emperature bot 35 ° F- 1 0 ° F Superheat SUP 8 ° F8 ° F Slave Evaporator SLA No No No. of Defrost per Day dFn 24 Defrost Fail-safe time dFF 40 min. 30 min. Defrost End T emperature dFt 45 ° F6 0 ° F Defrost Delay Start T ime dFS 0 hrs. ...

  • Heatcraft Refrigeration Products H-IM-79D - page 23

    23 T able 3. Parts List HRPD P ART P ART DESCRIPTION NUMBER Beacon II Control Board 28910101 *T emperature Sensor kit – White Leads 89904902 T ransformers: 120/24 volt – 40 V A 22529601 240/24 volt - 40 V A 22529602 460/24 volt – 40 V A 22529603 575/24 volt – 40 V A 22529701 Pilot Relay 2251 1401 Contactor for Compressor 40 amp with 24 volt ...

  • Heatcraft Refrigeration Products H-IM-79D - page 24

    24 Beacon II T roubleshooting Guide PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check Primary Power Supply Disconnect 1. Check fuses and circuit breakers 2. Check V oltage to Evaporator Transformer Go to 2. Check field wiring for breaks LED is not lit. 3. Check T ransformer Secondary Output Volts next step 3. Replace if necessary 4. Check V oltage ...

  • Heatcraft Refrigeration Products H-IM-79D - page 25

    25 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check wiring connection to the board • Correct field wiring to the board 2. Low Pressure Safety (LPS) T ripped: • Check for correct refrigerant type • Change setpoint to match refrigerant • Check refrigerant charge • Add more refrigerant to proper charge • Check LPS setting • Correct LPS ...

  • Heatcraft Refrigeration Products H-IM-79D - page 26

    26 Beacon II T roubleshooting Guide (continued) PROBLEM Step ACTION ITEM IF OK IF NOT OK E9 Multi-out to Multi-in 1. Check for 24 volts power to the board 1. If no voltage, see “ LED is not lit ” above Communication Wiring for low voltage, see “ 88888 LED display ” (only shows after initial 2. Check for crossed communication wiring Go to 2. ...

  • Heatcraft Refrigeration Products H-IM-79D - page 27

    27 PROBLEM Step ACTION ITEM IF OK IF NOT OK 1. Check system operation: Is it running? 1. Check power to condensing unit Check position of Service Mode switches Check compressor overloads and contactor 2. Check system charge 2. Add or remove refrigerant to proper charge 3. Check for proper operating superheat 3. Check EEV operation Check control boa ...

  • Heatcraft Refrigeration Products H-IM-79D - page 28

    28 Wiring ...

  • Heatcraft Refrigeration Products H-IM-79D - page 29

    29 Wiring ...

  • Heatcraft Refrigeration Products H-IM-79D - page 30

    30 Wiring ...

  • Heatcraft Refrigeration Products H-IM-79D - page 31

    31 Wiring Part No. 29684301 ...

  • Heatcraft Refrigeration Products H-IM-79D - page 32

    32 Wiring Part No. 29684201 ...

  • Heatcraft Refrigeration Products H-IM-79D - page 33

    33 Wiring Part No. 29684001 ...

  • Heatcraft Refrigeration Products H-IM-79D - page 34

    34 EV APORA TORS All evaporator units should be checked once a month or more often for proper defrosting because the amount and pattern of frosting can vary greatly . It is dependent on the coil temperature, the temperature of the room, the type of product being stored, how often new product is brought into the room and the percentage of time the d ...

  • Heatcraft Refrigeration Products H-IM-79D - page 35

    35 Service Record Date of Start-up Location Address CONDENSING UNIT MODEL # SERIAL # COOLER UNIT MODEL # SERIAL # FREEZER UNIT MODEL # SERIAL # ELECTRICAL • Check Primary Supply voltage. If 208 V , change transformer wiring in the Cooler and Freezer to the 208 V tap  YES • Check Compressor Amps for COOLER and FREEZER compressors. Should matc ...

  • Heatcraft Refrigeration Products H-IM-79D - page 36

    36 2175 West Park Place Blvd. • Stone Mountain, GA 30087 770-465-5600 • Fax: 770-465-5990 • www .heatcraftrpd.com Since product improvement is a continuing effort, we reserve the right to make changes in specifications without notice. RECORD OUTDOOR TEMPERA TURE ______ ° F SYSTEM VOL T AGE ______V olts ______PH ______Hz Cooler Compressor Amp ...

Fabbricante Heatcraft Refrigeration Products Categoria Refrigerator

I documenti che otteniamo dal fabbricante del dispositivoHeatcraft Refrigeration Products H-IM-79D possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Heatcraft Refrigeration Products
- manuali per l’uso H-IM-79D
- schede prodotto Heatcraft Refrigeration Products
- opuscoli
- o etichette energetiche Heatcraft Refrigeration Products H-IM-79D
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Heatcraft Refrigeration Products H-IM-79D.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Heatcraft Refrigeration Products H-IM-79D, manuali di manutenzione, brevi manuali o manuali utente Heatcraft Refrigeration Products H-IM-79D. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Heatcraft Refrigeration Products H-IM-79D.

Manuale completo del dispositivo Heatcraft Refrigeration Products H-IM-79D, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Heatcraft Refrigeration Products H-IM-79D dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Heatcraft Refrigeration Products H-IM-79D.

Il manuale per l’uso completo Heatcraft Refrigeration Products, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Heatcraft Refrigeration Products H-IM-79D - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Heatcraft Refrigeration Products H-IM-79D, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Heatcraft Refrigeration Products H-IM-79D che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Heatcraft Refrigeration Products H-IM-79D - che ci dovrebbe aiutare nei primi passi durante l'uso Heatcraft Refrigeration Products H-IM-79D
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Heatcraft Refrigeration Products H-IM-79D
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Heatcraft Refrigeration Products H-IM-79D in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Heatcraft Refrigeration Products H-IM-79D?

Utilizza il modulo sottostante

Se non hai risolto il problema con Heatcraft Refrigeration Products H-IM-79D con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Heatcraft Refrigeration Products H-IM-79D è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)