    All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR C OMMERCIAL H EA TING & C OOLING 7.5 T ON - 12.5 T ON P ACKAGE G AS S ERIES CPG S ERIES RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. A TTENTION INST ALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installat ...

  • Goodman Mfg CPG SERIES - page 2

    2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the whit ...

  • Goodman Mfg CPG SERIES - page 3

    3 T HIS  PRODU CT  CO NTAI N S  OR  PRODU CES  A  CHEM IC AL  OR  CHEM IC ALS  WHICH  MAY  CA US E  SERIO US  ILLNESS  OR  DEATH  AND  WHICH  ARE  KNO WN  TO  THE  S TATE  OF  C ALIFORNIA  TO  CA US E  CA N CER ,  BIR TH  DEFECT S  OR  OT HER  RE PR OD U ...

  • Goodman Mfg CPG SERIES - page 4

    4 System design and installation should also, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. The mechanical inst allation of the packaged roof top units consist s of making final connec ...

  • Goodman Mfg CPG SERIES - page 5

    5 G ROUND L EVEL I NSTALLATIONS O NLY : • When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick. • The base should also be located where no runoff of water from higher ground can collect in ...

  • Goodman Mfg CPG SERIES - page 6

    6 • Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor . The curbs must be supported on parallel sides by roof mem- bers. The roof members must not penetrate supply and re- turn duct opening areas as damage to the unit might occur . NOTE: The unit and curb accessories are designed to allow vertical ...

  • Goodman Mfg CPG SERIES - page 7

    7 Ensure that the top of the duct connection frame is flush with the top of the roof curb. Flexible duct connectors between the unit and ducts are rec- ommended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes. RETURN SUPPL Y 13 7/8” 28 3/8” 7 3/8” 12 5/8” 5 7/8 ” 6 1/4” 36 3/8 ? ...

  • Goodman Mfg CPG SERIES - page 8

    8 Import ant: If using bottom discharge with roof curb, duct- work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installa- tion Instructions. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be inst alled in compliance with the National Roofing Cont ...

  • Goodman Mfg CPG SERIES - page 9

    9 C ONDU IT  AND  FITTINGS  MUST  BE  WEATHER ‐ TI GH T  TO  PREVENT  WATER  ENTRY  INTO  THE  BUILDING . CAUTIO N For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity , but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OV ...

  • Goodman Mfg CPG SERIES - page 10

    10 LO W VOL T AGE E N TRAN CE DI M PL ES MA RK DR IL L LOC A TI O NS HIGH VOL T AGE ENTRANC E 10 3/16” 3 3/4” 26 ½ ” ELECTRICAL ENTRANCE LOCATIONS Unit is equipped with a Low V oltage T erminal Block and has Single Point wiring to the contactor . L OW V OLTAGE C ONTROL W IRING 1. A 24V thermost at must be installed for unit operation. It may ...

  • Goodman Mfg CPG SERIES - page 11

    11 The rating plate is stamped with the model number , type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line inst allation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFP A 54/ANSI Z223.1. Natural Gas Connection ...

  • Goodman Mfg CPG SERIES - page 12

    12 PROP ANE GAS INST ALLA TIONS T O  AVOID  PROP ERTY  DAMAGE ,  PER SONAL  INJURY  OR  DEAT H  DUE  TO  FIRE  OR  EXPLO SIO N  CA US ED  BY  A  PROP ANE  GAS  LEA K ,  INS TALL  A  GAS  DETE CT ING  WARNING  DEVICE .  S INCE  RUS T  CA N  RE D UC E  THE  LEVE ...

  • Goodman Mfg CPG SERIES - page 13

    13 6. All pipe connections should be sealed with a pipe thread compound, which is resistant to the fuel used with the furnace. A soapy water solution should be used to check all joints for leaks. A 1/8" NPT plugged tap is located on the entering side of the gas valve for test gauge connection to measure supply (main) gas pressure. Another 1/8& ...

  • Goodman Mfg CPG SERIES - page 14

    14 MOV ING  MA CHIN ER Y  HA ZA RD! T O  PREVEN T  POSSIB L E  PER SONAL  INJURY  OR  DEATH ,  DISC ONNECT  POWE R  TO  THE  UNIT  AND  PADL OCK  IN  THE  “OFF”  POSIT ION  BEF OR E  SERVICING  FANS . W ARNING H EATING S TARTUP This unit is equipped with an electronic ignition de ...

  • Goodman Mfg CPG SERIES - page 15

    15 Three Phase Models 3) P ERCEN T VOLT AGE UNB ALANCE 2) M AXIMU M VOL TAGE D EVIATI ONS FROM AVER AG E VOLT AG E 1) A VERAG E V OLTA GE HOW TO USE THE FORMULA: EXAMPLE: With volt age of 220, 216, and 213 1) Average Vol tage = 220+216+ 213=649 / 3 = 216 2) Maximu m Voltage Deviat ion s from Average Vo lt age = 220 - 216 = 4 3) Percent Voltage Unba ...

  • Goodman Mfg CPG SERIES - page 16

    16 E VAPORATOR F AN R OTATION C HECK (T HREE P HASE M ODELS O NLY ) Check that fan rotates clockwise when viewed from the drive side of unit and in accordance with rotation arrow shown on blower housing. If it does not, reverse any two incoming power cables at Single Point Power Block. In this case, repeat bear- ing check. Do not attempt to change ...

  • Goodman Mfg CPG SERIES - page 17

    17 NATURAL M in . 5. 0" W . C . , M ax . 10 . 0" W . C . PR OP A N E M in . 11. 0" W . C . , M ax . 14 . 0" W . C . I N L ET GAS PR E S SUR E NOTE: Inlet Gas Pressure Must Not Exceed the Maximum V alue Shown. If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or ...

  • Goodman Mfg CPG SERIES - page 18

    18 5. Check supply fan rotation. If the supply fan is rot ating in the wrong direction, disconnect and lock off Single Point Power Block. Do not attempt to change load side wiring. Internal wiring is set at the factory to assure that the supply fan and compressors all rotate in the proper direction. V erification of correct supply fan rotation at i ...

  • Goodman Mfg CPG SERIES - page 19

    19 The pressure regulator on LP gas models is adjusted for 10.0" w .c. manifold pressure and is intended to prevent over-firing only . Do not attempt adjustment of the built-in pressure regu- lator unless the supply pressure is at least 7.0" w .c. on natu- ral gas or 14.0" w .c. on propane gas. Check the location of the ignition elec ...

  • Goodman Mfg CPG SERIES - page 20

    20 A UTOMATIC R ESET H IGH L IMIT C ONTROL (ALS) Located in the blower compartment on the blower housing, it senses air temperature within the blower compartment and protects the filters from excessive temperature. It will shut down the furnace if it senses excessive temperatures. M ANUAL R ESET F LAME R OLLOUT C ONTROL (RS) Located in the burner c ...

  • Goodman Mfg CPG SERIES - page 21

    21 Open Thermal Protection Device If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draf t and air circulator blowers remain energized until the limit switch recloses. The diag- nostic fault code for an open limit is four (4) flashes. A primary limit ...

  • Goodman Mfg CPG SERIES - page 22

    22 V L & V M S HEAVES A DJUSTMENT 1. Loosen set screw “B” using a 5/32" Allen key . 2. Making half or full turns from closed position, adjust sheave pitch diameter for desired speed. DO NOT OPEN MORE THAN FIVE FULL TURNS. 3. T ighten set screw “B” securely over flat. 4. Carefully put on belts and adjust belt tension. DO NOT FORCE B ...

  • Goodman Mfg CPG SERIES - page 23

    23 C LEAN O UTSIDE C OIL (Q UALIFIED S ERVICER O NLY ) The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. C ONDENSER , E VAPORATOR , AND I NDUCED D RAFT M OTORS Bearings on the air circulating blower motor , condenser mo- tor and t ...

  • Goodman Mfg CPG SERIES - page 24

    24 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD HORIZONT AL NOTE: High St atic airflow requires installation of High S tatic Kit (HSKT*), or factory-built High S tatic model. Unit factory sh ipped at 2.5 turns open. T ables represent dry coil without filter . T o compensate for filter , add 0.08" to measured E.S.P . SCFM correc ...

  • Goodman Mfg CPG SERIES - page 25

    25 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD DOWN SHOT CP G 09 0 S T A ND AR D BE L T DR I VE DO W N S HO T CFM RPM BHP CF M RP M B HP CFM RP M BHP CF M RP M BHP CF M R P M B HP CF M RPM BHP 0. 1 35 2 2 75 0 1. 14 32 2 8 70 6 0. 94 29 64 6 6 1 0 . 7 3 0. 3 33 37 8 00 1. 1 9 3 102 7 56 1 2 800 7 06 0 .7 6 2 50 4 661 0. 59 0. 5 33 ...

  • Goodman Mfg CPG SERIES - page 26

    26 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - HIGH ST A TIC (“AA” MODELS ONL Y) NOTE: High St atic airflow requires installation of High S tatic Kit (HSKT*), or factory-built High S tatic model. Unit factory sh ipped at 2.5 turns open. T ables represent dry coil without filter . T o compensate for filter , add 0.08" to measured E.S ...

  • Goodman Mfg CPG SERIES - page 27

    27 APPENDIX B ELECTRICAL DA T A M I N M AX Q ty RL A LR A Q ty H P RLA H P F L A 20 8/ 230 -6 0- 3 187 253 2 13 .1 83 .1 2 1/ 4 1. 40 BD ST D STA T I C 1 . 5 5. 0 4 60-6 0-3 414 506 2 6. 1 41 .0 2 1/ 4 0. 80 BD S T D STA TI C 1 . 5 2. 5 5 75-6 0-3 518 633 2 4. 4 3 3 2 1 / 4 0. 60 BD S T D STA TI C 1 . 5 2. 3 20 8/ 230 -6 0- 3 187 253 2 14 .5 98 .0 ...

  • Goodman Mfg CPG SERIES - page 28

    28 APPENDIX C UNIT DIMENSIONS HORIZONTAL DISCHARGE VERTICAL DISCHARGE (BOTTOM OF UNIT) NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package. RETURN SUPPL Y 13 7/ 8” ...

  • Goodman Mfg CPG SERIES - page 29

    29 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . NOTE 2 PLF BL RS CM2 L1 L2 L3 C T1 T3 T2 GR YL RD BK YL RD BK PU BK OR PU BR BR BK RD RD RD RD PK S2 S1 GND WH WH YL YL/ PK YL/ PK BL/ PK Y ...

  • Goodman Mfg CPG SERIES - page 30

    30 CPG(090/102/120/150)2104B*/7B* THREE PHASE 460-575/60 HZ BELT DRIVE WIRING DIAGRAM HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring ...

  • Goodman Mfg CPG SERIES - page 31

    31 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG(090/102/120/150)2103B* THRE ...

  • Goodman Mfg CPG SERIES - page 32

    32 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG(090/102/120/150)2103B* THRE ...

Fabbricante Goodman Mfg Categoria Heating System

I documenti che otteniamo dal fabbricante del dispositivoGoodman Mfg CPG SERIES possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Goodman Mfg
- manuali per l’uso CPG SERIES
- schede prodotto Goodman Mfg
- opuscoli
- o etichette energetiche Goodman Mfg CPG SERIES
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Goodman Mfg CPG SERIES.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Goodman Mfg CPG SERIES, manuali di manutenzione, brevi manuali o manuali utente Goodman Mfg CPG SERIES. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Goodman Mfg CPG SERIES.

Manuali per l’uso simili

Manuale completo del dispositivo Goodman Mfg CPG SERIES, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Goodman Mfg CPG SERIES dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Goodman Mfg CPG SERIES.

Il manuale per l’uso completo Goodman Mfg, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Goodman Mfg CPG SERIES - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Goodman Mfg CPG SERIES, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Goodman Mfg CPG SERIES che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Goodman Mfg CPG SERIES - che ci dovrebbe aiutare nei primi passi durante l'uso Goodman Mfg CPG SERIES
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Goodman Mfg CPG SERIES
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Goodman Mfg CPG SERIES in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Goodman Mfg CPG SERIES?

Utilizza il modulo sottostante

Se non hai risolto il problema con Goodman Mfg CPG SERIES con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Goodman Mfg CPG SERIES è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)