    All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR C OMMERCIAL H EA TING & C OOLING 7.5 T ON - 12.5 T ON P ACKAGE G AS S ERIES CPG S ERIES RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION. A TTENTION INST ALLING PERSONNEL Prior to installation, thoroughly familiarize yourself with this Installat ...

  • Goodman Mfg CPG SERIES - page 2

    2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the whit ...

  • Goodman Mfg CPG SERIES - page 3

    3 T HIS  PRODU CT  CO NTAI N S  OR  PRODU CES  A  CHEM IC AL  OR  CHEM IC ALS  WHICH  MAY  CA US E  SERIO US  ILLNESS  OR  DEATH  AND  WHICH  ARE  KNO WN  TO  THE  S TATE  OF  C ALIFORNIA  TO  CA US E  CA N CER ,  BIR TH  DEFECT S  OR  OT HER  RE PR OD U ...

  • Goodman Mfg CPG SERIES - page 4

    4 System design and installation should also, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. The manufacturer assumes no responsibility for equipment installed in violation of any code or regulation. The mechanical inst allation of the packaged roof top units consist s of making final connec ...

  • Goodman Mfg CPG SERIES - page 5

    5 G ROUND L EVEL I NSTALLATIONS O NLY : • When the unit is installed on the ground adjacent to the building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick. • The base should also be located where no runoff of water from higher ground can collect in ...

  • Goodman Mfg CPG SERIES - page 6

    6 • Curb insulation, cant strips, flashing and general roofing material are furnished by the contractor . The curbs must be supported on parallel sides by roof mem- bers. The roof members must not penetrate supply and re- turn duct opening areas as damage to the unit might occur . NOTE: The unit and curb accessories are designed to allow vertical ...

  • Goodman Mfg CPG SERIES - page 7

    7 Ensure that the top of the duct connection frame is flush with the top of the roof curb. Flexible duct connectors between the unit and ducts are rec- ommended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes. RETURN SUPPL Y 13 7/8” 28 3/8” 7 3/8” 12 5/8” 5 7/8 ” 6 1/4” 36 3/8 ? ...

  • Goodman Mfg CPG SERIES - page 8

    8 Import ant: If using bottom discharge with roof curb, duct- work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installa- tion Instructions. Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be inst alled in compliance with the National Roofing Cont ...

  • Goodman Mfg CPG SERIES - page 9

    9 C ONDU IT  AND  FITTINGS  MUST  BE  WEATHER ‐ TI GH T  TO  PREVENT  WATER  ENTRY  INTO  THE  BUILDING . CAUTIO N For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity , but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OV ...

  • Goodman Mfg CPG SERIES - page 10

    10 LO W VOL T AGE E N TRAN CE DI M PL ES MA RK DR IL L LOC A TI O NS HIGH VOL T AGE ENTRANC E 10 3/16” 3 3/4” 26 ½ ” ELECTRICAL ENTRANCE LOCATIONS Unit is equipped with a Low V oltage T erminal Block and has Single Point wiring to the contactor . L OW V OLTAGE C ONTROL W IRING 1. A 24V thermost at must be installed for unit operation. It may ...

  • Goodman Mfg CPG SERIES - page 11

    11 The rating plate is stamped with the model number , type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line inst allation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFP A 54/ANSI Z223.1. Natural Gas Connection ...

  • Goodman Mfg CPG SERIES - page 12

    12 PROP ANE GAS INST ALLA TIONS T O  AVOID  PROP ERTY  DAMAGE ,  PER SONAL  INJURY  OR  DEAT H  DUE  TO  FIRE  OR  EXPLO SIO N  CA US ED  BY  A  PROP ANE  GAS  LEA K ,  INS TALL  A  GAS  DETE CT ING  WARNING  DEVICE .  S INCE  RUS T  CA N  RE D UC E  THE  LEVE ...

  • Goodman Mfg CPG SERIES - page 13

    13 6. All pipe connections should be sealed with a pipe thread compound, which is resistant to the fuel used with the furnace. A soapy water solution should be used to check all joints for leaks. A 1/8" NPT plugged tap is located on the entering side of the gas valve for test gauge connection to measure supply (main) gas pressure. Another 1/8& ...

  • Goodman Mfg CPG SERIES - page 14

    14 MOV ING  MA CHIN ER Y  HA ZA RD! T O  PREVEN T  POSSIB L E  PER SONAL  INJURY  OR  DEATH ,  DISC ONNECT  POWE R  TO  THE  UNIT  AND  PADL OCK  IN  THE  “OFF”  POSIT ION  BEF OR E  SERVICING  FANS . W ARNING H EATING S TARTUP This unit is equipped with an electronic ignition de ...

  • Goodman Mfg CPG SERIES - page 15

    15 Three Phase Models 3) P ERCEN T VOLT AGE UNB ALANCE 2) M AXIMU M VOL TAGE D EVIATI ONS FROM AVER AG E VOLT AG E 1) A VERAG E V OLTA GE HOW TO USE THE FORMULA: EXAMPLE: With volt age of 220, 216, and 213 1) Average Vol tage = 220+216+ 213=649 / 3 = 216 2) Maximu m Voltage Deviat ion s from Average Vo lt age = 220 - 216 = 4 3) Percent Voltage Unba ...

  • Goodman Mfg CPG SERIES - page 16

    16 E VAPORATOR F AN R OTATION C HECK (T HREE P HASE M ODELS O NLY ) Check that fan rotates clockwise when viewed from the drive side of unit and in accordance with rotation arrow shown on blower housing. If it does not, reverse any two incoming power cables at Single Point Power Block. In this case, repeat bear- ing check. Do not attempt to change ...

  • Goodman Mfg CPG SERIES - page 17

    17 NATURAL M in . 5. 0" W . C . , M ax . 10 . 0" W . C . PR OP A N E M in . 11. 0" W . C . , M ax . 14 . 0" W . C . I N L ET GAS PR E S SUR E NOTE: Inlet Gas Pressure Must Not Exceed the Maximum V alue Shown. If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or ...

  • Goodman Mfg CPG SERIES - page 18

    18 5. Check supply fan rotation. If the supply fan is rot ating in the wrong direction, disconnect and lock off Single Point Power Block. Do not attempt to change load side wiring. Internal wiring is set at the factory to assure that the supply fan and compressors all rotate in the proper direction. V erification of correct supply fan rotation at i ...

  • Goodman Mfg CPG SERIES - page 19

    19 The pressure regulator on LP gas models is adjusted for 10.0" w .c. manifold pressure and is intended to prevent over-firing only . Do not attempt adjustment of the built-in pressure regu- lator unless the supply pressure is at least 7.0" w .c. on natu- ral gas or 14.0" w .c. on propane gas. Check the location of the ignition elec ...

  • Goodman Mfg CPG SERIES - page 20

    20 A UTOMATIC R ESET H IGH L IMIT C ONTROL (ALS) Located in the blower compartment on the blower housing, it senses air temperature within the blower compartment and protects the filters from excessive temperature. It will shut down the furnace if it senses excessive temperatures. M ANUAL R ESET F LAME R OLLOUT C ONTROL (RS) Located in the burner c ...

  • Goodman Mfg CPG SERIES - page 21

    21 Open Thermal Protection Device If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draf t and air circulator blowers remain energized until the limit switch recloses. The diag- nostic fault code for an open limit is four (4) flashes. A primary limit ...

  • Goodman Mfg CPG SERIES - page 22

    22 V L & V M S HEAVES A DJUSTMENT 1. Loosen set screw “B” using a 5/32" Allen key . 2. Making half or full turns from closed position, adjust sheave pitch diameter for desired speed. DO NOT OPEN MORE THAN FIVE FULL TURNS. 3. T ighten set screw “B” securely over flat. 4. Carefully put on belts and adjust belt tension. DO NOT FORCE B ...

  • Goodman Mfg CPG SERIES - page 23

    23 C LEAN O UTSIDE C OIL (Q UALIFIED S ERVICER O NLY ) The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. C ONDENSER , E VAPORATOR , AND I NDUCED D RAFT M OTORS Bearings on the air circulating blower motor , condenser mo- tor and t ...

  • Goodman Mfg CPG SERIES - page 24

    24 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD HORIZONT AL NOTE: High St atic airflow requires installation of High S tatic Kit (HSKT*), or factory-built High S tatic model. Unit factory sh ipped at 2.5 turns open. T ables represent dry coil without filter . T o compensate for filter , add 0.08" to measured E.S.P . SCFM correc ...

  • Goodman Mfg CPG SERIES - page 25

    25 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - ST ANDARD DOWN SHOT CP G 09 0 S T A ND AR D BE L T DR I VE DO W N S HO T CFM RPM BHP CF M RP M B HP CFM RP M BHP CF M RP M BHP CF M R P M B HP CF M RPM BHP 0. 1 35 2 2 75 0 1. 14 32 2 8 70 6 0. 94 29 64 6 6 1 0 . 7 3 0. 3 33 37 8 00 1. 1 9 3 102 7 56 1 2 800 7 06 0 .7 6 2 50 4 661 0. 59 0. 5 33 ...

  • Goodman Mfg CPG SERIES - page 26

    26 APPENDIX A BLOWER PERFORMANCE DA T A BEL T DRIVE - HIGH ST A TIC (“AA” MODELS ONL Y) NOTE: High St atic airflow requires installation of High S tatic Kit (HSKT*), or factory-built High S tatic model. Unit factory sh ipped at 2.5 turns open. T ables represent dry coil without filter . T o compensate for filter , add 0.08" to measured E.S ...

  • Goodman Mfg CPG SERIES - page 27

    27 APPENDIX B ELECTRICAL DA T A M I N M AX Q ty RL A LR A Q ty H P RLA H P F L A 20 8/ 230 -6 0- 3 187 253 2 13 .1 83 .1 2 1/ 4 1. 40 BD ST D STA T I C 1 . 5 5. 0 4 60-6 0-3 414 506 2 6. 1 41 .0 2 1/ 4 0. 80 BD S T D STA TI C 1 . 5 2. 5 5 75-6 0-3 518 633 2 4. 4 3 3 2 1 / 4 0. 60 BD S T D STA TI C 1 . 5 2. 3 20 8/ 230 -6 0- 3 187 253 2 14 .5 98 .0 ...

  • Goodman Mfg CPG SERIES - page 28

    28 APPENDIX C UNIT DIMENSIONS HORIZONTAL DISCHARGE VERTICAL DISCHARGE (BOTTOM OF UNIT) NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package. RETURN SUPPL Y 13 7/ 8” ...

  • Goodman Mfg CPG SERIES - page 29

    29 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . NOTE 2 PLF BL RS CM2 L1 L2 L3 C T1 T3 T2 GR YL RD BK YL RD BK PU BK OR PU BR BR BK RD RD RD RD PK S2 S1 GND WH WH YL YL/ PK YL/ PK BL/ PK Y ...

  • Goodman Mfg CPG SERIES - page 30

    30 CPG(090/102/120/150)2104B*/7B* THREE PHASE 460-575/60 HZ BELT DRIVE WIRING DIAGRAM HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring ...

  • Goodman Mfg CPG SERIES - page 31

    31 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG(090/102/120/150)2103B* THRE ...

  • Goodman Mfg CPG SERIES - page 32

    32 HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICI NG OR INST A LLING THIS UNIT . M UL TIPL E POW ER SOUR CES MA Y BE P RESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAM AGE, PERSONAL INJURY OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. CPG(090/102/120/150)2103B* THRE ...

Manufacturer Goodman Mfg Category Heating System

Documents that we receive from a manufacturer of a Goodman Mfg CPG SERIES can be divided into several groups. They are, among others:
- Goodman Mfg technical drawings
- CPG SERIES manuals
- Goodman Mfg product data sheets
- information booklets
- or energy labels Goodman Mfg CPG SERIES
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodman Mfg CPG SERIES.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodman Mfg CPG SERIES, service manual, brief instructions and user manuals Goodman Mfg CPG SERIES. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodman Mfg CPG SERIES.

A complete manual for the device Goodman Mfg CPG SERIES, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodman Mfg CPG SERIES by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodman Mfg CPG SERIES.

A complete Goodman Mfg manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodman Mfg CPG SERIES - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodman Mfg CPG SERIES, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodman Mfg CPG SERIES, that we can find in the current document
3. Tips how to use the basic functions of the device Goodman Mfg CPG SERIES - which should help us in our first steps of using Goodman Mfg CPG SERIES
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodman Mfg CPG SERIES
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodman Mfg CPG SERIES in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodman Mfg CPG SERIES?

Use the form below

If you did not solve your problem by using a manual Goodman Mfg CPG SERIES, ask a question using the form below. If a user had a similar problem with Goodman Mfg CPG SERIES it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)