    1 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Application Enginee ring BULLE TIN Safety Safety Instructions ................................................................. 2 Safety Icon Explanation ........................................................ 2 Instructions Pertaining to Ris ...

  • Emerson AE8-1385 - page 2

    2 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Safety Instructions Copeland Scroll ® compressors with CoreSense ™ Diagnostics technology are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety . Safey ico ...

  • Emerson AE8-1385 - page 3

    3 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only . • Molded electrical plug must be used when required. • Refer to origi ...

  • Emerson AE8-1385 - page 4

    4 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN INTRODUCTION Overview CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air conditioning and heat pump systems. The CoreSense Diagnostics module is easily installed in the unit electrical panel near the com ...

  • Emerson AE8-1385 - page 5

    5 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN OPERA TION Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload. The protection termina ...

  • Emerson AE8-1385 - page 6

    6 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN off. This event will cause a lockout of the compressor and indicates that the module is mis-wired or the contactor coil is shorted to ground. NOTICE Code 10 is not speci fi ed on the module label. Resetting Alert Codes When the CoreSense Diag ...

  • Emerson AE8-1385 - page 7

    7 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ALERT TRIP / LOCK POWER 1 Long Run Time 2 Compressor (Pressure) Trip 3 Pressure Switch Cycling 4 Locked Rotor 5 Compressor (Mod Run) Trip 6 Open Start Circuit 7 Open Run Circuit 8 Welded Contactor 9 Low Voltage DC SOL operating range: 18-28VDC ...

  • Emerson AE8-1385 - page 8

    8 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN 2- S t a g e Th e rmo s tat I ndoor Uni t O utdoor Uni t C R Y1 Y2 C R L Y Y2 L DC So l en o i d S ole noi d CoreSense Hi gh / Low Pr essu re S wi t ch CC C o m p r esso r Conta c t or C R Y1 Y2 L C R Y1 Y2 L Prot Figure 4 Wiring Diagram ...

  • Emerson AE8-1385 - page 9

    9 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Alert Code Alert Condition Lockout Level Lockout Indication Normal Run Solid Green Normal operation, no trip. N/A N/A Code1 Y ellow Flash 1 Long run time. Compressor is running for more than 18 hours at full load. (Code1 is disabled in Heat Pu ...

  • Emerson AE8-1385 - page 10

    10 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Status Description T roubleshooting Information Solid Green “RUN” Module has power and operating normally Supply voltage is present at module terminals Solid Red “TRIP” Thermostat demand signal Y is present, but the compressor is not ...

  • Emerson AE8-1385 - page 11

    11 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Y ellow “ALERT” Flash Code 4 Locked Rotor 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) • Check wiring connections 3. Excessive liquid refrigerant in compressor 4. Compressor bearings ...

  • Emerson AE8-1385 - page 12

    12 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Red “LOCKOUT” Flash Code 5 Y ellow Off Compressor (Moderate Run) T rip Compressor is locked out after 4 consecutive or 10 total compressor (moderate run) trip events 1. Evaporator blower is not running • Check blower relay coil and cont ...

Fabbricante Emerson Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoEmerson AE8-1385 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson
- manuali per l’uso AE8-1385
- schede prodotto Emerson
- opuscoli
- o etichette energetiche Emerson AE8-1385
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson AE8-1385.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson AE8-1385, manuali di manutenzione, brevi manuali o manuali utente Emerson AE8-1385. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson AE8-1385.

Manuali per l’uso simili

Manuale completo del dispositivo Emerson AE8-1385, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson AE8-1385 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson AE8-1385.

Il manuale per l’uso completo Emerson, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson AE8-1385 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson AE8-1385, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson AE8-1385 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson AE8-1385 - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson AE8-1385
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson AE8-1385
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson AE8-1385 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson AE8-1385?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson AE8-1385 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson AE8-1385 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)