    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM APC Symmetra LX GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, single- phase, solid-state, static Uninterruptible Po we ...

  • APC LX - page 2

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM E. The UPS and associated equipment shall opera te in conjunction with a primary power supply and an output distribution s ystem to provide quality uninterrupted power for mission critical, electronic equipment load. F. All programming and miscellaneou ...

  • APC LX - page 3

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM F. External Service Bypass Panel (SBP): Th e maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is ...

  • APC LX - page 4

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.2 SYSTEM CHARACTERISTICS A. System Capacity: The syste m shall be rated for .8 Pf output in the f ollowing frame sizes: 1. 8 kVA/ 6.4kW - Can be configured with up to (3), 3. 2kW power modules for N+1 2. 16 kVA/ 12.8kW - Can be configured with up t o ...

  • APC LX - page 5

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1) >130% for 4 seconds 2) 105% continuous 3) <130% Continuous at N+1 b. Bypass Operation: 1) 100A continuous 8. System AC-AC Efficiency: >90% at 100% load 10. Output Power Factor Rating: The UPS output shall b e .8 lagging 2.3 ENVIRONMENTAL A. ...

  • APC LX - page 6

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2. In cases where the source voltage to the UPS is nominal and the applied UPS load is equal to or less than 100% of UPS capacity, input current shall not exceed 130% of UPS output current, while providing f ull battery recharge power and importing nec ...

  • APC LX - page 7

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.7 AUTOMATIC BYPASS A. As part of the UPS, a system automatic bypass switch shall be provided. The system automatic bypass shall provide a break <11Ms transfer of the critical load from the Inverter output to the automatic bypass input source durin ...

  • APC LX - page 8

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. Metered Data: The following metered data, shall be available on the alphanum eric display: 1. Year, Month, Day , Hour, Minute, Second of occurring events 2. Source Input Voltage 3. Output AC voltage 4. Output AC current 5. Input Frequency 6. Battery ...

  • APC LX - page 9

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 15. Need Battery Replacement 16. The Redundant Intelligence Module is in control 17. UPS Fault 18. On Battery 19. Shutdown or unable to transfer to battery due to overload 20. Load Shutdown from Bypass. Input Frequency Volts outside lim its 21. Fault, ...

  • APC LX - page 10

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM K. Controls: The following controls or prog ramming functions shall be accomplished by use of the display unit. Pushbutton membra ne switches shall facilitate these operations. 1. Silence audible Alarm 2. Display or set the date and time 3. Enable or d ...

  • APC LX - page 11

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. The battery jars housed within each removable battery module shall be of the Valve Regulated Lead Acid (VRLA) type. C. The UPS shall incorporate a battery manageme nt system to continuously monitor the health of each removable battery module as we l ...

  • APC LX - page 12

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on reserve mode. 2. The UPS shall also be capable of using an RS232 port to communicate by m ean ...

  • APC LX - page 13

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. Inspect equipment for signs of damage. 2. Verify installation per manufacturer s instructions. 3. Inspect cabinets for foreign objects. 4. Inspect Battery Units. 5. Inspect Power Modules. B. Mechanical Inspection 1. Check all UPS and external servic ...

  • APC LX - page 14

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 8. Verify proper charger operation. 9. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted start-up, operational training for site personnel shall include key pad operation, LED indicators, start-up a ...

メーカー APC カテゴリー Power Supply

APC LXのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- LXの取扱説明書
- APCの製品カード
- パンフレット
- またはAPC LXの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、APC LXの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、APC LXの取り付け説明書、サービスマニュアル、簡易説明書、またはAPC LXのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、APC LXの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

APC LXデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAPC LXを使用するのを助ける技術的文書のことです。説明書は通常、全てのAPC LXユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

APCの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. APC LXの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAPC LXの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。APC LXに関してこのドキュメントで見つけることができる全てのヒントの目次
3. APC LXデバイスの基本機能を使うにあたってのヒント。 APC LXのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。APC LXに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAPC LXのメーカー/サービスへの連絡先に関する情報。

APC LXについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAPC LXの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAPC LXで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)