    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM APC Symmetra LX GUIDE SPECIFICATIONS FOR 4kVA-16kVA Uninterruptible Power System PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, single- phase, solid-state, static Uninterruptible Po we ...

  • APC LX - page 2

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM E. The UPS and associated equipment shall opera te in conjunction with a primary power supply and an output distribution s ystem to provide quality uninterrupted power for mission critical, electronic equipment load. F. All programming and miscellaneou ...

  • APC LX - page 3

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM F. External Service Bypass Panel (SBP): Th e maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the frame is ...

  • APC LX - page 4

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.2 SYSTEM CHARACTERISTICS A. System Capacity: The syste m shall be rated for .8 Pf output in the f ollowing frame sizes: 1. 8 kVA/ 6.4kW - Can be configured with up to (3), 3. 2kW power modules for N+1 2. 16 kVA/ 12.8kW - Can be configured with up t o ...

  • APC LX - page 5

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1) >130% for 4 seconds 2) 105% continuous 3) <130% Continuous at N+1 b. Bypass Operation: 1) 100A continuous 8. System AC-AC Efficiency: >90% at 100% load 10. Output Power Factor Rating: The UPS output shall b e .8 lagging 2.3 ENVIRONMENTAL A. ...

  • APC LX - page 6

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2. In cases where the source voltage to the UPS is nominal and the applied UPS load is equal to or less than 100% of UPS capacity, input current shall not exceed 130% of UPS output current, while providing f ull battery recharge power and importing nec ...

  • APC LX - page 7

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 2.7 AUTOMATIC BYPASS A. As part of the UPS, a system automatic bypass switch shall be provided. The system automatic bypass shall provide a break <11Ms transfer of the critical load from the Inverter output to the automatic bypass input source durin ...

  • APC LX - page 8

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. Metered Data: The following metered data, shall be available on the alphanum eric display: 1. Year, Month, Day , Hour, Minute, Second of occurring events 2. Source Input Voltage 3. Output AC voltage 4. Output AC current 5. Input Frequency 6. Battery ...

  • APC LX - page 9

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 15. Need Battery Replacement 16. The Redundant Intelligence Module is in control 17. UPS Fault 18. On Battery 19. Shutdown or unable to transfer to battery due to overload 20. Load Shutdown from Bypass. Input Frequency Volts outside lim its 21. Fault, ...

  • APC LX - page 10

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM K. Controls: The following controls or prog ramming functions shall be accomplished by use of the display unit. Pushbutton membra ne switches shall facilitate these operations. 1. Silence audible Alarm 2. Display or set the date and time 3. Enable or d ...

  • APC LX - page 11

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM B. The battery jars housed within each removable battery module shall be of the Valve Regulated Lead Acid (VRLA) type. C. The UPS shall incorporate a battery manageme nt system to continuously monitor the health of each removable battery module as we l ...

  • APC LX - page 12

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on reserve mode. 2. The UPS shall also be capable of using an RS232 port to communicate by m ean ...

  • APC LX - page 13

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 1. Inspect equipment for signs of damage. 2. Verify installation per manufacturer s instructions. 3. Inspect cabinets for foreign objects. 4. Inspect Battery Units. 5. Inspect Power Modules. B. Mechanical Inspection 1. Check all UPS and external servic ...

  • APC LX - page 14

    CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERR UPTIBLE SYSTEM 8. Verify proper charger operation. 9. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted start-up, operational training for site personnel shall include key pad operation, LED indicators, start-up a ...

Fabbricante APC Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoAPC LX possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso LX
- schede prodotto APC
- opuscoli
- o etichette energetiche APC LX
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC LX.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC LX, manuali di manutenzione, brevi manuali o manuali utente APC LX. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC LX.

Manuali per l’uso simili

Manuale completo del dispositivo APC LX, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC LX dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC LX.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC LX - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC LX, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC LX che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC LX - che ci dovrebbe aiutare nei primi passi durante l'uso APC LX
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC LX
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC LX in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su APC LX?

Utilizza il modulo sottostante

Se non hai risolto il problema con APC LX con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con APC LX è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)