Athena Technologies 16Cの取扱説明書

48ページ 1.94 mb
ダウンロード

ページに移動 of 48

Summary
  • Athena Technologies 16C - page 1

    1 SERIES 1 6 C TEMPERA TURE/PROCESS CONTROLLER In st ru ct io n Ma nu al (B as ic O pe ra ti on s) ...

  • Athena Technologies 16C - page 2

    3 I nt r od uc t io n Pr ec au ti ons Congratulations on your purchase of an Athena Series 16C T emperature/Process Controller . It is designed for ease of use and reliability wherever accurate control is required. After following the instructions for installation, simply step through and set your operating parameters using the controller’ s easy ...

  • Athena Technologies 16C - page 3

    3 In addition to presenting a potential fire hazard, high voltage and high temperature can damage equipment and cause severe injury or death. When installing or using this instrument, follow all instructions carefully and use approved safety controls. Electrical connections and wiring should be performed only by suitably trained personnel. Do not l ...

  • Athena Technologies 16C - page 4

    4 1 T a bl e o f Co nt en ts Installation 1 Dimensions and Mounting 2 Wiring 3 Output T ypes 5 Operation 6 Front Panel Controls 6 Power On 7 Security Levels 8 Operating Modes 9 Menu System Overview 10 Initial Setup Sequence 12 Parameter/Menu Descriptions 14 Input Menu 15 T emperature Input 16 Process (Linear) Input 16 Display Menu 17 Output Menu 17 ...

  • Athena Technologies 16C - page 5

    4 1 In st al lat io n Measur ements between centerlines of panel cut- outs ar e the minimum r ecommended. Unpacking and Inspection 1. Inspect shipping carton for obvious signs of mishandling. 2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged unit. 3. Verify that th ...

  • Athena Technologies 16C - page 6

    2 3 Mo un tin g Di me nsi on s Figure 2. Case Dimensions Prior to mounting the Series C in your panel, make sure that the cutout opening is of the right size, 1.771” x 1.771” (45 mm x 45 mm), and deburred to enable a smooth fit. A mini- mum of 4” (100 mm) of depth behind the panel is required. Figure 3. Series C Mechanical Components Insert t ...

  • Athena Technologies 16C - page 7

    2 3 W iri ng IMPORT ANT : All electrical wiring connections should be made only by trained personnel, and in strict accordance with the National Electrical Code and local regulations. The Series C controller has built-in circuitry to reduce the effects of electrical noise (RFI) from various sources. However , power and signal wires should always be ...

  • Athena Technologies 16C - page 8

    4 W iri ng Figure 5. Thermocouple Input W iring Make sure that you are using the appropriate thermocouple and extension wire. Connect the negative lead (generally colored red in ISA-type thermocouples) to contact #9; connect the positive lead to contact #10. Extension wires must be the same polarity as the thermo- couple. Figure 6. RTD W iring The ...

  • Athena Technologies 16C - page 9

    4 5 Ou tp ut T yp es The T ype “B” output is a mechanical device and subject to wear . T o extend the life of the r elay , set the Cycle T ime for the relay output to the longest duration that still affor ds good control. When you ordered your Series C controller specific output types were specified, designated as “B”, “E”, “F”, “ ...

  • Athena Technologies 16C - page 10

    6 7 Op er at ion Mode/Enter Key Used to enter Parameter selections, access operating modes, release latched alarms, and index through menu items. Lower Key Used to decrease values. (Hold for fast-step progression) Raise Key Used to increase values. (Hold for fast-step progression) Menu Access Key Used to enter or exit the menu system, index to the ...

  • Athena Technologies 16C - page 11

    6 7 Po we r On When power is first applied to the Series C, all segments of the LED displays will be momentarily illuminated while the instrument goes through a series of diagnostic checks to verify proper operation. A software version number will then appear in the lower display , followed by a configuration code (upper display) and the communicat ...

  • Athena Technologies 16C - page 12

    8 S ec uri ty L ev els The security level feature allows you to limit access to the menus, setpoint, and operating mode selection according to the needs of your application. The security levels provided are Key Lockout , Setpoint , Setpoint plus Mode , User , Configuration , and Factory . T o view or change security level from the Process Variable ...

  • Athena Technologies 16C - page 13

    8 9 Op er ati ng M od es The Series C’ s operating modes are: Manual , Standby , Normal , Autotune , Ramp/Soak Recipe , Run and Hold . T o select a different operating mode, press the Mode/Enter key for three seconds. The operating mode that the controller is currently in will be dis- played. T o index through the available operating modes, press ...

  • Athena Technologies 16C - page 14

    10 1 1 Me nu Sy st em Ov er vie w The Parameter Menu System is organized into ten basic menus: Input, Display , Output, Control, Alarm, T une, Recipe, Supervisor , Calibration, and Option . T o access the Menus, press and hold the Menu Access key for approxi- mately 3 seconds until a menu label appears in the upper dis- play . There are additional ...

  • Athena Technologies 16C - page 15

    10 1 1 Me nu Sy st em Ov er vie w Figure 10. Series C Functional Diagram T o r eturn to Pr ocess V alue at any time, pr ess and hold Menu Access key for thr ee seconds for 3 seconds Menu System for 3 seconds Security Levels Pr ocess V ariable Display Mode Selection for 10 seconds for 3 seconds once once ...

  • Athena Technologies 16C - page 16

    12 Me nu Sy st em Ov er vie w Figure 1 1. Chart of Series 16C Menu System and Security Levels (Continued on Next Page) Mode/ Enter Key Menu Access Key (number) (number) (number) (number) (number) Notes: 1. It is recommended you start with the input menu. 2. Parameter labels displayed will vary , depending upon the controller’ s configuration. ...

  • Athena Technologies 16C - page 17

    Security Levels (Key Lockout) = No Access (Setpoint) = Setpoint V alue or Output Percentage (Manual Mode) (Setpoint plus Mode) = Plus (User) = Plus (Configuration) = Plus (Factory) = Plus 13 Mode/ Enter Key (three seconds) Functional When Option Card Installed Raise/ Lower Key * See options manual for parameter selections. Figure 1 1. Chart of Seri ...

  • Athena Technologies 16C - page 18

    Input Used to select sensor -related parameters, such as input type, limits, and scaling. Display Used to set or change decimal position and display units. Output Used to specify output usage, control methods, and alarms. Control Used to select parameters associated with the control methods. Alarm Used to select alarm parameters . Note: This menu i ...

  • Athena Technologies 16C - page 19

    15 NOTE: FOR A MORE DET AILED DESCRIPTION OF MENU P ARAMETERS, REFER TO THE GLOSSAR Y WHICH BEGINS ON P AGE 64. The first parameter that needs to be set is Input T ype . The remaining Input Menu parameters will change, depending upon whether a linear input type or a temperature input type is selected. Other menu param- eters related to the sensor r ...

  • Athena Technologies 16C - page 20

    17 Input T ype JMPØ1 JMPØ2 Thermocouple Out Out R TD Out Out V oltage <100 mV Out Out V oltage >100 mV In Out Current Process In In 16 In pu t M en u JMPØ1 JMPØ2 Input Menu (continued) Display Parameter Selection Input T ype 100 ohm compressed RTD 0-20 mA 4-20 mA 0-10 mV 0-50 mV 0-100 mV 10-50 mV 0-1 V 0-5 V 0-10 V 1-5 V Input Jumper Sett ...

  • Athena Technologies 16C - page 21

    17 Di sp lay M en u JMPØ1 Display Parameter Selection Decimal Position 0-3 Linear Inputs 0-1 T C/R TD Filter 0.1-10.0 sec Units* Fah renh eit Ce lsius Ke lvin *NOTE: Does not appear for linear inputs. Blanking , 0-9999 sec (T ime selected before setpoint diplay turns off.) Ou tp ut Me nu The first parameter that needs to be set in the Output Menu ...

  • Athena Technologies 16C - page 22

    19 18 Ou tp ut M en u Output 1 Action Reverse-acting (Heating) Direct-acting (Cooling) Output 1 Cycle T ime* 0.2; 1 to 120 seconds Output 1 Low Limit 1-100% Output 1 High Limit 1-100% Output 2 Action Reverse-acting (Heating) Direct-acting (Cooling) Output 2 Cycle T ime* 0.2; 1 to 120 seconds Output 2 Low Limit 1-100% Output 2 High Limit 1-100% *Rec ...

  • Athena Technologies 16C - page 23

    19 Ou tp ut M en u Co nt ro l Men u Display Parameter Selection Output 1 Action Reverse-acting (Heating) Direct-acting (Cooling) Output 2 Action Reverse-acting (Heating) Direct-acting (Cooling) Display Parameter Selection Deadband 1 Negative span of sensor to positive span of sensor Hysteresis Output 1 1...to span of sensor Deadband 2 Negative span ...

  • Athena Technologies 16C - page 24

    20 21 No te s O n Al ar ms Outputs can be set up as an alarm, similar to the standard alarm format. Four types of alarms are available: Process, Deviation, Inverse Band, and Normal Band. All alarms may be configured to be inhibited on power -up for a configurable time duration. Process Alarm: Activates at preset value, independent of setpoint. “H ...

  • Athena Technologies 16C - page 25

    20 21 Ou tp ut Me nu Display Parameter Selection Output 1 Alarm Action (Latching) (Normal) Output 1 Alarm Operation (Process Low) (Process High) (Inverse Band) (Normal Band) (Deviation Low) (Deviation High) Output 1 Alarm Delay 0-9999 sec Output 1 Alarm Inhibit 0-9999 sec Output 1 Alarm Setpoint Span of Sensor Output 2 Alarm Action (Latching) (Norm ...

  • Athena Technologies 16C - page 26

    22 Display Parameter Selection Damping Low Normal High Au to tun e Da mp ing M en u Note: The damping parameter specifies how aggressively the controller performs its autotuning. The “Normal” setting is a compromise between the fast recovery and overshoot. The “Low” setting provides faster recovery , but with the possibil- ity of overshoot; ...

  • Athena Technologies 16C - page 27

    22 23 Re ci pe (R am p/ So ak ) M en u Pow er F ail Resu me Set ting thi s pa rame ter to O n wi ll c ause the con trol to resu me a r ecip e wh ich was acti ve w hen a po wer fail ure occu rred . Th e rec ipe will res ume at t he s tart of the last act ive ramp or soak seg ment . Ram p/So ak E vent s (1 -8) (If al arms a re con figure d as r amp/s ...

  • Athena Technologies 16C - page 28

    25 24 NOTE: The following seven parameters are only available when multi-step ramp is selected. Display Parameter Selection Recycle Number 0-99, (Recipe Executions) Power Fail Resume Off On Ramp T imes 1-8 0-9999 mins. Ramp Events 1-8 Alarm 1 On Alarm 1 Off Alarm 2 On Alarm 2 Off Disabled Soak Levels 1 - 8 Display Units, FS Soak T imes 1-8 0-9999 m ...

  • Athena Technologies 16C - page 29

    25 T oggles with the temperature value that should be input to perform the low calibration operation. The low calibration operation is triggered by pressing the up arrow key . T oggles with the temperature value that should be input to perform the high calibration operation. The high calibration operation is triggered by pressing the up arrow key . ...

  • Athena Technologies 16C - page 30

    26 27 Aut ot un in g T o place the controller in Autotune mode: 1) Configure the controller by following the directions for Initial Setup Sequence through Step 3 on page 7. Set damping parameter . (See page 22.) 2) If the controller is not already in Standby mode, place it in Standby now as follows. Press and hold the Mode/Enter key for th ree seco ...

  • Athena Technologies 16C - page 31

    26 27 Au to tun in g If a tune error condition occurs, the upper display will toggle between and a numeric error code for three seconds before the tune process terminates. The controller will then automatically go into Standby mode when a tuning error occurs. Possible error codes are: 02 = No PID Device Configured 03 = Incorrect Output Action 05 = ...

  • Athena Technologies 16C - page 32

    28 Ma nu al T uni ng Manual T uning Procedure (Zeigler -Nichols PID Method) This tuning method may be used for non-temperature control processes or if the spread between ambient temperature and process operating temperature is small. For best results, the use of a recording device is required when tuning with this method. 1) For temperature control ...

  • Athena Technologies 16C - page 33

    28 29 Er r or Co de s If an err or code cannot be clear ed by using the actions pr ovided, contact factory . Display Problem Actions Open Sensor Check sensor , wiring, and Input. Reversed Sensor Check the type selection in the Input menu, and check sensor polarity . Loop Break Correct problem and reset controller . Checksum Error Press any key RAM ...

  • Athena Technologies 16C - page 34

    30 T ec hn ic al Sp ec ifi ca ti on s Operating Limits Ambient T emperature 32°F to 140°F (0°C to 60°C) Relative Humidity T olerance 90%, Non-Condensing Power 100 to 250 V 50/60 Hz (Single-Phase) 100 to 250 Vdc 24 V ac/dc Power Consumption Less than 6 VA Performance Accuracy ±0.20% of Full Scale (±0.10% T ypical), ±1 Digit Setpoint Resolutio ...

  • Athena Technologies 16C - page 35

    30 31 T ec hn ic al Sp ec ifi ca ti on s Input T ype Thermocouple B, C, E, J, K, N, NIC, NNM, R, S, T , Platinel II Maximum lead resistance 100 ohms for rated accuracy RTD Platinum 2- and 3-wire, 100 ohms at 0° C, DIN curve standard (0.00385) 1000 ohms available Linear 0-50 mV/10-50 mV , 0-5 V/1-5 V 0-20 mA/4-20 mA, 0-100 mV , 0-10 V Output Device ...

  • Athena Technologies 16C - page 36

    32 33 Or de rin g Co de s Code Input T ype C T T hermocouple CR RTD C S Compressed RTD CM M il liv ol t L in ea r CV V olt Linear CC Current Linear CA All CB TD & T/C Code Option 00 None Alarms 10 Dual SSR, N.O . 20 Dual Open Collector 21 Dual 24 Vdc 22 Dual SSR, N.C. 23 Relay, N.O . Communications 30 RS-232/Athena+ RS-485, Athena+ with Contact ...

  • Athena Technologies 16C - page 37

    32 33 The Series C contr oller is pr ecalibrated at the factory . Under normal cir cumstances, the factory calibration should be valid for the life of the instrument. If r ecalibration should be r equired, allow the contr oller to warm up for 15 minutes and follow these steps car efully . Re ca lib ra ti on Pr oc ed ur es 1) Remove power from the c ...

  • Athena Technologies 16C - page 38

    34 Qu ic k-H el ps 1. T o return the unit to last operating mode (Normal, Standby , FOP , or T une): Action Display From Menu System: Press and hold PV + SV + Mode for 3 sec. From Security Level Menu: Press PV+ SV + Mode 2. T o enter Standby operating mode: Action Display From Normal Press and hold operating mode: for 3 sec. Press Press + PV + SV F ...

  • Athena Technologies 16C - page 39

    34 35 Qu ic k-H el ps 5. T o abort Autotuning Action Display and return to normal Press and hold operation: for 3 sec. Press Press PV + SV 6. T o enter FOP (Manual) Action Display operating mode: Press and hold for 3 sec. Press + PV + % of Power Value Press to set new % of Power Value Press to + PV + set % of Power % of Power for Output 2 Value if ...

  • Athena Technologies 16C - page 40

    36 W arr an ty/ Re pa irs T wo-Y ear Limited Warranty THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MA TERIAL AND WORKMANSHIP . IT IS SOLD SUB JECT TO OUR MUTU AL A GREE MENT THA T THE LIAB ILIT Y OF A THENA CONTROLS, INCORPORA TED IS TO REPLACE OR REP AIR THIS EQUIPMENT A T ITS FACTOR Y , PROVIDED THA T IT IS RETURNED WITH TRANSPORT A TIO ...

  • Athena Technologies 16C - page 41

    37 W arr an ty/ Re pa irs Unit Repairs It is recommended that units requiring service be returned to an authorized service center . Before a controller is returned for service, please consult the ser vice center nearest you. In man y ca ses, the pro blem can be clea red up o ver the tele phon e. When the unit needs to be returned, the service cente ...

  • Athena Technologies 16C - page 42

    38 39 IE C Re qu ir em ent s The maximum supply current is line voltage dependent: 230 mA for a 24 Vac/dc input fuse rating=700 mA 60 mA for an 85 - 250 Vac input fuse rating=100 mA Output Specifications Output T ype Max current Voltage Leakage B 5 A 250 V ac 1000 M ohms T 1 A 250 Vpk 1 mA S 20 mA 5 V NA CLEANING INSTRUCTIONS 1. Remove power from t ...

  • Athena Technologies 16C - page 43

    38 39 Alarm Delay - the time delay between the detection of the alarm condi- tion and the initiation and indication of the output action. Alarm Inhibit - prevents low setpoint alarm activation during cold startup applications. Bias - allows the operator to compensate for any difference between sensor temperature and the point to be measured. The pr ...

  • Athena Technologies 16C - page 44

    40 41 input failure, or a heater or load failure. Loop Break Time - the time interval from when the controller detects a loop break condition and the initiation of the failsafe state. Lowest Reading - records the lowest process value read by the controller . May be reset to zero by using the Raise or Lower arrow keys. Lower Setpoint Limit - prohibi ...

  • Athena Technologies 16C - page 45

    40 41 Quick Setup Instructions - Series 16C T emperature Controller Experienced users, already familiar with the Series 16C, and using the controller with PID outputs, may follow these condensed instructions to autotune the controller and get started quickly once the instrument is prop- erly mounted and wired, and the Security Level is set to . Onc ...

  • Athena Technologies 16C - page 46

    42 43 Keep This Information in a Safe Place Configured Parameters Reference Data Series C T emperature Controllers Model Number Zone Location Firmware Version No. (Displayed when the controller is powered up after all the segments on both lines of the display have been tested.) Dear Customer: Please keep this information handy – in case your cont ...

  • Athena Technologies 16C - page 47

    42 43 No te s ...

  • Athena Technologies 16C - page 48

    44 At hen a Con tro ls , I nc . 51 45 Ca mpu s D ri ve P ly mo u th M e et in g , P A 19 46 2 U. S .A . T el : ( 61 0) 828 -2 490 Fa x: (6 10) 82 8- 708 4 T ol l-F re e i n U .S .: 1- 800 -78 2- 677 6 In ter ne t: www . at hen ac ont rol s. com For T oll-FreeT echnical Assistance in the USA, Call T oll Free: 1-800-782-6776 900M 011U0 0 REV ISION ? ...

メーカー Athena Technologies カテゴリー Weather Radio

Athena Technologies 16Cのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 16Cの取扱説明書
- Athena Technologiesの製品カード
- パンフレット
- またはAthena Technologies 16Cの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Athena Technologies 16Cの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Athena Technologies 16Cの取り付け説明書、サービスマニュアル、簡易説明書、またはAthena Technologies 16Cのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Athena Technologies 16Cの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Athena Technologies 16Cデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAthena Technologies 16Cを使用するのを助ける技術的文書のことです。説明書は通常、全てのAthena Technologies 16Cユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Athena Technologiesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Athena Technologies 16Cの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAthena Technologies 16Cの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Athena Technologies 16Cに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Athena Technologies 16Cデバイスの基本機能を使うにあたってのヒント。 Athena Technologies 16Cのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Athena Technologies 16Cに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAthena Technologies 16Cのメーカー/サービスへの連絡先に関する情報。

Athena Technologies 16Cについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAthena Technologies 16Cの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAthena Technologies 16Cで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)