  • Athena Technologies OTC25 N - page 1

    DIGIT AL TEMPERA TURE CONTR OLLERS SERIES O TC25 N/L/P Instruction Manual ...

  • Athena Technologies OTC25 N - page 2

    Congratulations on your purchase of an Athena Series OTC25 Digital T emperature Controller . It is designed for ease of use and reliability wherever accurate temperature control is required. After following the instructions for installation, simply step through and set each of the unit’ s parameters using the OTC25’ s easy menu system. If you s ...

  • Athena Technologies OTC25 N - page 3

    T able of Contents Installation 1 Mounting 1 Wiring 2 Operation 2 OTC25 N On/Off Controller 4 OTC25 L Limit Controller 5 OTC25 P PID Controller 7 Calibration 10 Error Codes 11 IEC Requirements 11 W arranty/Repair Information 12 T echnical Specifications 14 ...

  • Athena Technologies OTC25 N - page 4

    1 Installation Pre-Installation Instructions 1. Inspect shipping carton for obvious signs of mishandling. 2. After removing the controller from the shipping carton, inspect it carefully for damage. Never attempt to install and use a damaged unit. 3. Verify that the ordering code number indicated on the side of the controller matches what was ordere ...

  • Athena Technologies OTC25 N - page 5

    2 Operation Athena Series OTC25 Digital T emperature Controller Just a few easy steps are required before your OTC25 can be placed into service. After completing the mounting and wiring procedures as previously instructed, set each controller parameter using the simple front-panel keys as instructed. Power On When power is first applied to the OTC2 ...

  • Athena Technologies OTC25 N - page 6

    O TC25 N Operation F igure 5a. Series O TC25 N Parameters and Default Settings Parameter Descriptions Default Display This parameter determines whether the OTC25 N’ s display shows the Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Paramete ...

  • Athena Technologies OTC25 N - page 7

    O TC25 N Operation The Calibration High and Calibration Low selections ar e accessi- ble only when the calibration jumper is installed as instructed on page 10 (F igure 6). OTC25 N On/Off T emperature Controller Normal Operation The factory default display setting of the OTC25 N is for Actual Te mperature . The default display may be changed to set ...

  • Athena Technologies OTC25 N - page 8

    5 O TC25 L Operation OTC25 L Limit Controller Normal Operation The factory default display setting of the OTC25 L is for Actual Te mperature . The default display may be changed to setpoint temperature by selecting Limit Setpoint at the Default Display parameter selection. When the Default Display is changed to Limit Setpoint, the limit setpoint te ...

  • Athena Technologies OTC25 N - page 9

    6 O TC25 L Operation Parameter Descriptions Default Display This parameter determines whether the OTC25 L ’ s display shows the Limit Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Parameter Key . This will cause the alternate value to be d ...

  • Athena Technologies OTC25 N - page 10

    7 O TC25 P Operation OTC25 P PID T emperature Controller Normal Operation The factory default display setting of the OTC25 P is for Actual Te mperature . The default display may be changed to setpoint temperature by selecting Setpoint at the Default Display parameter selection. When the Default Display is changed to Setpoint, the setpoint temperatu ...

  • Athena Technologies OTC25 N - page 11

    F igure 5c. Series O TC25 P Parameters and Default Settings Parameter Descriptions Default Display This parameter determines whether the OTC25 P’ s display shows the Setpoint or the actual temperature by default. Regardless of the selection made here, the operator can observe the other value by momentarily pressing the Parameter Key . This will c ...

  • Athena Technologies OTC25 N - page 12

    O TC25 P Operation Proportional Band Proportional Band is a PID parameter that represents the amount of deviation of the controlled variable required to move through the full range, expressed in % of span or degrees of temperature. This para- meter can also be expressed as “Gain” (the wider the band, the lower the gain). Rate Rate is a PID para ...

  • Athena Technologies OTC25 N - page 13

    10 Calibration Procedure 1. Prior to applying power to the unit, install the calibration jumper on the microprocessor board as shown in Figure 6. 2. With the instrument still unpowered, connect a calibration reference source to the thermocouple input terminals on the OTC25. 3. Apply power . Allow at least 15 minutes for the controller to warm up be ...

  • Athena Technologies OTC25 N - page 14

    The maximum supply current is line voltage dependent: 60 mA for an 100-250 Vac input fuse rating: 2AG, 0.5 A Output Specifications Output 1 T ype Max current Voltage Leakage T (T riac) 2 A 400 Vpk 1 mA B (Relay) 5 A 380 V — Output 2 T ype Max current Voltage Leakage T (SSR) 0.5 A 400 Vpk 1 mA B (Relay) 5 A 380 V — CLEANING INSTRUCTIONS 1. Remov ...

  • Athena Technologies OTC25 N - page 15

    12 W arranty/Repair Inf ormation T wo-Y ear Limited Warranty THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS OF MA TERIAL AND WORKMANSHIP . IT IS SOLD SUBJECT TO OUR MUTUAL AGREEMENT THA T THE LIABILITY OF A THENA CONTROLS, INCORPORA TED IS TO REPLACE OR REPAIR THIS EQUIPMENT A T ITS FACTOR Y , PROVIDED THA T IT IS RETURNED WITH TRANSPORT A TIO ...

  • Athena Technologies OTC25 N - page 16

    13 W arranty/Repair Inf ormation Unit Repairs It is recommended that units requiring service be returned to an authorized service center . Before a controller is returned for ser- vice, please consult the service center nearest you. In many cases, the problem can be cleared up over the telephone. When the unit needs to be returned, the service cent ...

  • Athena Technologies OTC25 N - page 17

    14 Mechanical Characteristics Display 7-segment LED, alphanumeric: 3 digits Display Height 0.56" (14.22 mm) Color Orange Front-Panel Cutout 3.622" x 3.622" (92 mm x 92 mm) Bezel Outside Dimensions 3.780" x 3.780" (96 mm x 96 mm) Bezel Height 0.250" (6.35 mm) Case Depth 3.515" (89.28 mm) Weight < 15 oz (425 g) C ...

  • Athena Technologies OTC25 N - page 18

    15 T echnical Specif ications Input Source (T emperature Sensor) Thermocouple Range: T ype J OTC25 N/L: 6 to 926° F (-14 to 496° C) OTC25 P: 32 to 999° F (0 to 537° C) T ype K OTC25 N/L: N/A OTC25 P: 0 to 999° F (-17 to 537° C) Output Source (Power to Heater) Solid-State Relay (Output 1) 120/250 Vac, Zero-V oltage Switched, 2 A Continuous/ 10 ...

  • Athena Technologies OTC25 N - page 19

    16 NO TES ...

  • Athena Technologies OTC25 N - page 20

    17 Keep This Information in a Safe Place Configured Parameters Reference Information Series OTC25 T emperature Controller Model Number: _____________________ Zone Location: _____________________ Firmware V ersion No. : _______________ (Displayed when the controller is powered up after all the segments on both lines of the display have been tested). ...

  • Athena Technologies OTC25 N - page 21

    18 NO TES ...

  • Athena Technologies OTC25 N - page 22

    19 Keep This Information in a Safe Place Configured Parameters Reference Information Series OTC25 T emperature Controller Model Number: _____________________ Zone Location: _____________________ Firmware V ersion No. : _______________ (Displayed when the controller is powered up after all the segments on both lines of the display have been tested). ...

  • Athena Technologies OTC25 N - page 23

    20 NO TES ...

  • Athena Technologies OTC25 N - page 24

    For technical assistance, call toll free 1-800-782-6776 (in the U .S.) or 610-828- 2490 (fr om an ywhere in the w orld), or e-mail techsupport@athenacontrols.com. Athena Controls, Inc. 5145 Campus Drive Plymouth Meeting, P A 19462 USA T oll-free: 800.782.6776 T el: 610.828.2490 Fax: 610.828.7084 techsupport@athenacontrols.com athenacontrols.com 900 ...

メーカー Athena Technologies カテゴリー Weather Radio

Athena Technologies OTC25 Nのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- OTC25 Nの取扱説明書
- Athena Technologiesの製品カード
- パンフレット
- またはAthena Technologies OTC25 Nの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Athena Technologies OTC25 Nの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Athena Technologies OTC25 Nの取り付け説明書、サービスマニュアル、簡易説明書、またはAthena Technologies OTC25 Nのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Athena Technologies OTC25 Nの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Athena Technologies OTC25 Nデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAthena Technologies OTC25 Nを使用するのを助ける技術的文書のことです。説明書は通常、全てのAthena Technologies OTC25 Nユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Athena Technologiesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Athena Technologies OTC25 Nの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAthena Technologies OTC25 Nの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Athena Technologies OTC25 Nに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Athena Technologies OTC25 Nデバイスの基本機能を使うにあたってのヒント。 Athena Technologies OTC25 Nのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Athena Technologies OTC25 Nに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAthena Technologies OTC25 Nのメーカー/サービスへの連絡先に関する情報。

Athena Technologies OTC25 Nについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAthena Technologies OTC25 Nの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAthena Technologies OTC25 Nで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)