Carrier 30MPA - page 1
Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without not ice and without inc urring obligations. Catalog No . 04-533000 54-01 Printed in U .S.A. Fo rm 30MP-1SI Pg 1 910 1-10 Replaces: Ne w Installation Instr uctions CONTENTS Page GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
-
Carrier 30MPA - page 2
2 INST ALLA TION Location — Do not store units in an area exposed to weath- er because of sensitive contro l mechanisms and electronic devices. Locate unit indoors. See Fig. 4 and 5 for unit dimen- sional details. When considering location, consult National Electrical Code (NEC) and local code requirements. Allow sufficient space for wiring, pipi ...
-
Carrier 30MPA - page 3
3 52.30 1328 [] STD UNIT 55.00 1397 [] OPTIONAL SOUND ENCLOSURE 57.00 [1448] 29.13 740 [] STD UNIT 32.00 813 [] 62.50 1588 [] OPTIONAL SOUND ENCLOSURE 32.12 [816] MOBILITY KIT (WHEEL) OPTIONAL 3.85 98 [] E D F OPTIONAL SOUND ENCLOSURE 48.42 [1230] OPTIONAL SOUND ENCLOSURE 65.05 [1652] 4.00 [102] ISOLATOR-OPTIONAL C B A 4.03 102 [] 1.75 44 [] 4.46 [ ...
-
Carrier 30MPA - page 4
4 Fig. 5 — Dimensions — 30MPW015-045 Units NO TES: 1. Operating weight includes w eight of water and refrigerant. 2. Denotes center of gravity . 3. Dimensions are shown in inc hes. Dimensions in [ ] are in millimeters . 4. Allow 36-in. (914 mm) clear ance on control panel end, opposite control panel end and a b ov e the unit. All clearan ...
-
Carrier 30MPA - page 5
5 Table 1A — 30MPA Air-Cooled and 30MPW Liquid-Cooled Unit s — English * With optional hot gas b ypass. NO TES: 1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers. 2. 30MPW units are shipped with full operating charge. UNIT 30MP A,MPW 015 020 030 040 045 NOMINAL T ON S 15 20 30 40 45 OPERA TING ...
-
Carrier 30MPA - page 6
6 T abl e 1B — 30MPA Air-Cooled a nd 30MPW Liquid-Cooled Units — SI * With optional hot gas b ypass. NO TES: 1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers. 2. 30MPW units are shipped with full operating charge. UNIT 30MP A,MPW 015 020 030 040 045 NOMINAL KW 54 71 10 8 13 8 161 OPERA TING WT ...
-
Carrier 30MPA - page 7
7 Step 3 — Place the Unit NOTE: These units ar e not suitable for unpr otected outdoor use . Carrier recommends that these units be located in the base- ment or on the ground floor . However , if it is necessary to lo- cate the unit on an upper floor , be sure the structure has been designed to support the unit weight. If necessary , add structur ...
-
Carrier 30MPA - page 8
8 NO TES: 1. Chiller must b e installed le v el to maintain proper compressor oil return. 2. Wiring and pip ing shown are general points-of- connection guides only and are not intended for a spe- cific installation. Wiring and piping shown are f or a q uick ov erview of system and are not in accordance with recognized standards. Units should b e in ...
-
Carrier 30MPA - page 9
9 NO TES: 1. Chiller must b e installed lev el to maintain proper compr essor oil return. 2. Wir ing and piping show n are general poi nts-of-connection guides only and ar e not intended for a specific installa tion. Wiring and pip- ing shown are f or a q uic k ov erview of system and are no t in accor- dance with recognize d standards . Units shou ...
-
Carrier 30MPA - page 10
10 3. Install the inside coupling half over the gasket and then install the outer half. Connect with nuts and bolts. T ighten the nuts equally on both sides. Ensure there is no gap be- tween the two halves of the coupling. 4. Alternately tighten the nuts with a wrench to draw the coupling halves together uniformly . The joint is now complete. 30MPW ...
-
Carrier 30MPA - page 11
11 120 1 100 80 e Drop (kPa) 40 60 Water Pressur e 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Liters/second 12 3 5 4 40 30 35 1 5 4 3 2 25 30 Drop () 15 20 Water Pressure 5 10 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 GPM Fig. 11 — Condenser W ater Pressure Drop ENGLISH SI LEGEND 1 — 30MP015 2 ...
-
Carrier 30MPA - page 12
12 120 3 100 1 80 e Drop (kPa) 40 60 Water Pressur e 20 0 0123456789 1 0 1 1 1 2 1 3 Liters/second 1 2 3 4 5 0 5 10 15 20 25 30 35 40 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 Water Pressure Drop () GPM 15 4 3 2 Fig. 12 — Ev aporator W ater Pressure Drop ENGLISH SI LEGEND 1 — 30MP015 2— 30MP020 3— 30MP030 4 ...
-
Carrier 30MPA - page 13
13 Step 6 — Fill the Chilled W ater Loop W A TER SYSTEM CLEANING — P r o pe r wa t e r sy s t em cleaning is of vital importance. Excessive particulates in the water system can cause excessive pump seal wear , reduce or stop flow , and cause damage of other com ponents. W ater quality should be maintained within the limits indicated in T able 2 ...
-
Carrier 30MPA - page 14
14 Ensure the following when filling the system: 1. Remove temporary bypass piping and cleaning/flushing equipment. 2. Check to make sure all drain plugs are installed. 3. Open the blow-down valve to flush the strainer . Normally , a closed system needs to be filled only once. The actual filling process is generally a fairly simple procedure. All a ...
-
Carrier 30MPA - page 15
15 EXAMPLE: Supply voltage is 240-3-60. AB = 243 v BC = 236 v AC = 238 v A verage V oltage = 243 + 236 + 238 3 = 239 v Determine maximum deviation from average voltage: (AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v Maximum deviation is 4 v . Determine percent voltage imbalance: % V oltage Imbalance = 100 x 4 239 =1 . 7 % This ...
-
Carrier 30MPA - page 16
Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53300054-0 1 Printed in U .S.A. Form 30MP-1SI Pg 16 910 1-10 Replaces: Ne w Copy right 2010 Carrier Cor poration Fig. 16 — T y pical Low V oltag e Control Wiring NO TES: 1. F actory ...