    F-2200 Series V ortex Flow Meter Installation and Operation Guide For software version CF 4.7 and higher 1500 North Belcher Road • Clearwater , FL 33765 • T el (727) 447-6140 • Fax (727) 442-5699 www .onicon.com • sales@onicon.com 12-15-08 ...

  • Philips F-2200 Series - page 2

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 3 SAFETY INFORMA TION This meter was calibrated at the factory before shipment. T o ensure correct use of the meter , please read this manual thoroughly . Regarding This Manual: • This manual should be passed on to the end user . • Before use, read this manual t ...

  • Philips F-2200 Series - page 3

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 4 F-2200 Series V ortex Flow Meter Installation and Operation Guide Addendum December 12, 2008 CAUTION Insulating the entire neck of the  ow meter will increase heat transfer to the electronics enclosure and may in some cases cause premature failure of the electr ...

  • Philips F-2200 Series - page 4

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 5 T ABLE OF CONTENTS 1.0 INTRODUCTION ............................................................................................................. .7 1.1 Purpose of This Guide ......................................................................................... ...

  • Philips F-2200 Series - page 5

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 6 ...

  • Philips F-2200 Series - page 6

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 7 SECTION 1.0: INTRODUCTION W e, at ONICON INCORPORA TED, would like to thank you for purchasing our F-2200 Series V ortex Flow Meter . As our valued customer , our commitment to you is to provide fast reliable service and assistance, while continuing to offer you n ...

  • Philips F-2200 Series - page 7

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 8 ACCURACY V olumetric  ow ±1% of reading accuracy (±2% for ¾” & smaller sizes) Mass  ow ±1.5% of reading accuracy (±2.5% for ¾” & smaller sizes) OPERA TING TEMPERA TURE RANGE Media temperature 25° to 464° F Ambient temperature 0° to 132° ...

  • Philips F-2200 Series - page 8

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 9 1.4 ADDITIONAL REQUIRED MA TERIALS Installer is responsible for providing suitable  anges and fasteners to connect the meter to the process piping. In addition, most installations will also require one reducer , one expander , pipe supports and a suf cient l ...

  • Philips F-2200 Series - page 9

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 10 SECTION 2.0: UNP ACKING F-2000 series vortex  ow meters are shipped in one package. Additional items, if ordered, will be shipped in separate packaging. All shipments are insured for damage in transit. Carefully inspect each package and notify the freight carr ...

  • Philips F-2200 Series - page 10

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 11 SECTION 3.0: INST ALLA TION INFORMA TION The F-2000 series vortex  ow meter must be installed by a technician quali ed to work with pressurized liquid, steam and/or gas  ow and must conform to all federal, state and local building codes. ONICON will be h ...

  • Philips F-2200 Series - page 11

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 12 The diagrams shown below illustrate the correct meter orientation for vertical and horizontal pipe. Nominal Meter Size (in.) Meter Body Diameter (in.) Maximum Pipe ID Difference (in.) 1” 1.05 0.016 1 1/2” 1.61 0.016 2” 2.07 0.024 3” 3.07 0.024 4” 4.03 0 ...

  • Philips F-2200 Series - page 12

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 13 3.1.3 Straight, Unimpeded Inlet And Outlet Runs D = Meter Size (Nominal diameter in inches) W ith a  ow straightener , the inlet pipe length may be reduced by 50%. For example, with a control valve upstream, the inlet length is 25D instead of 50D. The minimum ...

  • Philips F-2200 Series - page 13

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 14 3.1.5 Locating The Meter In A Pipline That Runs Parallel T o A W all Wherever possible, the distance between the pipe centerline and the wall should be greater than 20”. This will allow for access to the electronics enclosure compartment where wire terminations ...

  • Philips F-2200 Series - page 14

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 15 3.2 MECHANICAL INST ALLA TION 3.2.1 Orient The Display For Convenient V iewing Both the electronics enclosure and the display itself can be rotated to four different orientations to change the viewing angle for the display . If necessary , this should be done bef ...

  • Philips F-2200 Series - page 15

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 16 3.2.1.2 Rotating the display T o rotate the display ,  rst unscrew the cover using the special tool provided for this purpose. Once the cover is removed, the (4) Philips head screws that secure the display are exposed. T o rotate the display , remove these scr ...

  • Philips F-2200 Series - page 16

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 17 3.3.2 T emperature Measurements ONICON F-2000 series vortex meters are supplied with an internal PT 1000 type RTD temperature sensor located within the shedder bar . This sensor provides an accurate temperature measurement at the point where the  ow rate is be ...

  • Philips F-2200 Series - page 17

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 18 SECTION 4.0: ST ART UP AND TROUBLESHOOTING 4.1 ST ART UP When the power is applied to the F-2000 series vortex meter , alphanumeric characters will appear on the display . Initially , the meter will operate in a “TEST” mode where self diagnostic checks are pe ...

  • Philips F-2200 Series - page 18

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 19 4.3 OPERA TING THE DISPLA Y Please read the entire procedure before proceeding. W iring diagrams are located in the Appendix. A worksheet for checking off the following steps and recording measured values is located on the next page. i There are 3 user interface ...

  • Philips F-2200 Series - page 19

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 20 4.4 ERROR HANDLING The meter can detect errors in either the test or the measurement modes. When in the measurement mode, a blinking vertical bar will appear in the top left corner of the display indicating an error has been detected. If the error reporting funct ...

  • Philips F-2200 Series - page 20

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 21 REPORTED PROBLEM POSSIBLE SOLUTIONS A non-zero fl ow indi- cated when no actual fl ow is in the pipe. • Mains interference due to improper Earth ground connection. The protective Earth PE terminal should be properly grounded (see page 17). • Excessive mecha ...

  • Philips F-2200 Series - page 21

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 22 SECTION 5.0: FLOW STRAIGHTENER FOR VORTEX FLOW METERS DESCRIPTION The optional  ow straightener accessory for ONICON F-2000 Series V ortex Flow Meters is a wafer -style  ow conditioner that is designed to be installed between two recessed  anges (provide ...

  • Philips F-2200 Series - page 22

    F-2200 Series V ortex Flow Meter Installation and Operation Guide • Revised 12/08 23 OBSTRUCTION SEE TABLE 1 UPSTREAM DIMENSION B 2 DIAMETERS 5 DIAMETERS ONICON F-2000 SERIES STEAM METER, NOTE 1 300# ANSI FLANGE ECCENTRIC REDUCER, NOTE 2 FLOW STRAIGHTENER, NOTE 3 (600# ANSI FLANGE OPTNL) MINIMUM UPSTREAM PIPE RUN MINIMUM DOWNSTREAM PIPE RUN REQUI ...

メーカー Philips カテゴリー Automobile Parts

Philips F-2200 Seriesのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- F-2200 Seriesの取扱説明書
- Philipsの製品カード
- パンフレット
- またはPhilips F-2200 Seriesの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Philips F-2200 Seriesの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Philips F-2200 Seriesの取り付け説明書、サービスマニュアル、簡易説明書、またはPhilips F-2200 Seriesのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Philips F-2200 Seriesの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Philips F-2200 Seriesデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがPhilips F-2200 Seriesを使用するのを助ける技術的文書のことです。説明書は通常、全てのPhilips F-2200 Seriesユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Philipsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Philips F-2200 Seriesの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははPhilips F-2200 Seriesの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Philips F-2200 Seriesに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Philips F-2200 Seriesデバイスの基本機能を使うにあたってのヒント。 Philips F-2200 Seriesのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Philips F-2200 Seriesに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるPhilips F-2200 Seriesのメーカー/サービスへの連絡先に関する情報。