    FieldPoint ™ Operating Instructions FP-AI-110 and cFP-AI-110 Eight-Channel, 16-Bit Analog Input M odules These operating instructions descri be ho w to install and use the FP-AI-110 and cFP-AI-110 analog input modules (referred to inclusiv ely as the [c]FP-A I-110). F or information about configuring and accessing the [c]F P- AI-110 ov er a netwo ...

  • National Instruments FP-Al-110 - page 2

    FP-AI-110 and cFP-AI-110 2 ni.com T o install the FP- AI-110, refer to Figure 1 and complete the follow ing steps: 1. Slide the terminal base key to either position X (used for an y module) or position 1 (used for the FP- AI-110). 2. Align the FP- AI-110 alignmen t sl ots with the guide rails on the terminal base. 3. Press firmly to seat the FP- AI ...

  • National Instruments FP-Al-110 - page 3

    © National Instruments Corp. 3 FP-AI-110 and cFP-AI-110 (10 lb ⋅ in.) of torque. The nylon coating on the screws pre vents them from loosening. Figure 2. Installing the cFP-AI-110 Wiring the [c]FP-AI-110 The FP-TB- x terminal base ha s connections for each of the eight input channels and for an external power su pply to power field de vice s. Th ...

  • National Instruments FP-Al-110 - page 4

    FP-AI-110 and cFP-AI-110 4 ni.com is 2 A or less and the maximum current through any V SUP terminal is 1 A or less . Install a 2 A maximum, fast-acting fuse between t he external power supply and the V terminal on each channel. The wiring diagrams in this document sho w fuses where appropriate. T able 1 lists the terminal assign ments for the signa ...

  • National Instruments FP-Al-110 - page 5

    © National Instruments Corp. 5 FP-AI-110 and cFP-AI-110 T aking Measurements with the [c]FP-AI-110 The [c]FP- AI-110 has eight single- ended input cha nnels. All eight channels share a common ground referen ce that is isolated from other modules in the FieldPoint system. Figure 3 shows the analog input circuitry on one channel. Figure 3. FP- AI-11 ...

  • National Instruments FP-Al-110 - page 6

    FP-AI-110 and cFP-AI-110 6 ni.com Figure 5 sho ws how to connect a v oltage source with an extern al power supply to one channel of the [c]FP-AI-110. Figure 5. Voltage Source with Ex ternal Powe r Supply Measuring Current with the [c]FP-AI-110 The input ranges for current sources are 0 –20, 4 –20, and ± 20 mA. The module reads current flowing ...

  • National Instruments FP-Al-110 - page 7

    © National Instruments Corp. 7 FP-AI-110 and cFP-AI-110 Figure 6. Current Source without External Power Supply Figure 7 sho ws how to connect a cu rrent sour ce with an external power supply to one channel of the [c]FP-AI-110. Figure 7. Current Source with Ex ternal Power Supply Input Ranges T o prev ent inaccurate readings, c hoose an input range ...

  • National Instruments FP-Al-110 - page 8

    FP-AI-110 and cFP-AI-110 8 ni.com Overranging The [c]FP- AI-110 has an overranging feature that meas ures a little beyond the nominal values of each rang e. For example, the actual measurement limit of the ± 10 V range is ± 10.4 V . The overrang ing feature enables the [c]FP- AI-110 to compensate for field de vices with span errors of up to + 4% ...

  • National Instruments FP-Al-110 - page 9

    © National Instruments Corp. 9 FP-AI-110 and cFP-AI-110 sampling rate is faster than th e rate at which the network module polls the [c]FP-AI-110 for data. Status Indicators The [c]FP-AI-110 has tw o green status LEDs, POWER and READY . After you insert the [c] FP-AI-110 into a terminal base or backplane and apply po wer to th e connected network ...

  • National Instruments FP-Al-110 - page 10

    FP-AI-110 and cFP-AI-110 10 ni.com working v oltages of 250 V rms 1 . Safety standards (such as those published by UL and IEC) requir e the use of double insulation between hazardous voltages and an y human-accessi ble parts or circuits. Never try to use any isolation produ ct between human-accessible parts (such as DIN rails or monito ring station ...

  • National Instruments FP-Al-110 - page 11

    © National Instruments Corp. 11 FP-AI-110 and cFP-AI-110 • Operate the [c]FP-AI-110 only at or belo w Pollution Degree 2. Pollution Degree 2 means th at only nonconductiv e pollution occurs in most case s. Occasionally , howe ver , a temporary conductivity caused by conde nsation must be e xpected. • Operate the [c]FP-AI-110 at or below Measur ...

  • National Instruments FP-Al-110 - page 12

    FP-AI-110 and cFP-AI-110 12 ni.com Safety Guidelines for Hazardous V oltages If hazardous voltages are connected to the module, take the follow ing precautions. A hazardous voltage is a v oltage greater than 42.4 V peak or 60 VDC to earth ground. Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local ...

  • National Instruments FP-Al-110 - page 13

    © National Instruments Corp. 13 FP-AI-110 and cFP-AI-110 Effecti ve resolution by inpu t signal range and f ilter setting Input charac teristics by f ilter setting Normal-mode rejection .. .............. ..... 95 dB (with 50/60 Hz filter) Nonlinearity .......... ........... ......... ........ 0.0015% (monotonicity 1 guaranteed ov er the operating ...

  • National Instruments FP-Al-110 - page 14

    FP-AI-110 and cFP-AI-110 14 ni.com Input current 25 °C........... ...................... .......... 400 pA typ, 1 nA max 70 °C ............. ........... ........... ........ 3 nA typ, 15 nA max Input noise (with 50 or 60 Hz filter enabled) ± 60 mV range ...... ........... ........... . ± 3 LSB 1 peak-to-peak ± 300 mV range ...... ........... . ...

  • National Instruments FP-Al-110 - page 15

    © National Instruments Corp. 15 FP-AI-110 and cFP-AI-110 Note Full scale is the maximum value of the nominal input range. F or example, for the ± 10 V input range, full scale is 10 V and ± 0.01% of full scale is 1 mV . Gain error drift ........... ......... ........... ... ± 20 ppm/°C Offset error drift W ith 50 or 60 Hz filte r enabled ...... ...

  • National Instruments FP-Al-110 - page 16

    FP-AI-110 and cFP-AI-110 16 ni.com Physical Char acteristics Indicators ............ ........... ........... ........ Green POWER and READY indicators W eight FP-AI-110..... ............. .............. ... 140 g (4.8 oz) cFP-AI-110 ....... ............ .............. 110 g (3.7 oz) Power Requirements Power from network module ............ 350 mW S ...

  • National Instruments FP-Al-110 - page 17

    © National Instruments Corp. 17 FP-AI-110 and cFP-AI-110 Operating shock (IEC 60068-2-27)........... ........... ........ 50 g, 3 ms half sine, 18 shocks at 6 orientations; 30 g, 11 ms half sine, 18 shocks at 6 orientations Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for m ...

  • National Instruments FP-Al-110 - page 18

    FP-AI-110 and cFP-AI-110 18 ni.com CE Compliance This product meets the essentia l requirements of applicable European Directi ves, as amended for CE ma rking, as follows: Lo w-V oltage Directi ve (s afety). ..... ... 73/23/EEC Electromagnet ic Compatibility Directiv e (EMC) ... ........... ......... ........ 89/336/EEC Note Refer to the Declaratio ...

  • National Instruments FP-Al-110 - page 19

    © National Instruments Corp. 19 FP-AI-110 and cFP-AI-110 Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating i ...

  • National Instruments FP-Al-110 - page 20

    © 2003–2005 Nati onal Instruments Corp. All rights reserved. 373280A-01 Jun05 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks. Other product and company names ment ioned herein are trad ...

メーカー National Instruments カテゴリー Music Mixer

National Instruments FP-Al-110のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- FP-Al-110の取扱説明書
- National Instrumentsの製品カード
- パンフレット
- またはNational Instruments FP-Al-110の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、National Instruments FP-Al-110の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、National Instruments FP-Al-110の取り付け説明書、サービスマニュアル、簡易説明書、またはNational Instruments FP-Al-110のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、National Instruments FP-Al-110の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

National Instruments FP-Al-110デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがNational Instruments FP-Al-110を使用するのを助ける技術的文書のことです。説明書は通常、全てのNational Instruments FP-Al-110ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

National Instrumentsの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. National Instruments FP-Al-110の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははNational Instruments FP-Al-110の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。National Instruments FP-Al-110に関してこのドキュメントで見つけることができる全てのヒントの目次
3. National Instruments FP-Al-110デバイスの基本機能を使うにあたってのヒント。 National Instruments FP-Al-110のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。National Instruments FP-Al-110に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるNational Instruments FP-Al-110のメーカー/サービスへの連絡先に関する情報。

National Instruments FP-Al-110についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもNational Instruments FP-Al-110の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがNational Instruments FP-Al-110で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)