    Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53 500055-01 Printed in U .S .A. Form 50PS-3SI Pg 1 7-09 Replaces: 50PS-2SI Installation, Star t-Up , and Ser v ice Instr uctions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . ...

  • Carrier PSV - page 2

    2 SAFETY CONSIDERA TIONS Installation and servicing of air -conditioning equipment can be hazardous due to system pressure and electrical compo- nents. Only trained and qua lified service personnel should install, repair , or service air-conditioning equipment. Untrained personnel can perfor m basic maintenance func- tions such as cleaning coils an ...

  • Carrier PSV - page 3

    3 Table 1 — Physical Data — 50PSH, PSV, PSD018-070 Units LEGEND *Unit sizes 006-012 not av ailable on 50PSD unit. NOTE: All units ha ve spring compressor mountings, TXV expansion de vices, and 1 / 2 - in. and 3 / 4 -in. electrical knockouts. Step 2 — Chec k Unit — Upon receipt of shipment at the jobsite, carefully check the shipment against ...

  • Carrier PSV - page 4

    4 Before installing any of the system components, be sure to examine each pipe, fitting, and valve, and remove any dirt or foreign material found in or on these components. IN SP E CT UN IT — T o prepare the unit for installation, com- plete the procedures listed below: 1. Compare the electrical data on the unit nameplate with ordering and shippi ...

  • Carrier PSV - page 5

    5 NOTES: 1. Condensate is 3 / 4 -in. FPT copper . 2. Horizontal unit shipped with filter brack et only . Th is brac ket should be removed f or retur n duct connection. 3. Discharge flange and hanger kit is factory installed. 4. Shaded areas are recommended service areas, not required. 50PSH UNIT SIZE OV ER A L L CABINET (in.) W A TER CONNECTIONS (i ...

  • Carrier PSV - page 6

    6 a50-8183 R - Confi g uration Ri g ht Return / Top Di s char g e - Top View L - Confi g uration Left Return / Top Di s char g e - Top View Ri g ht Return - Air Coil Openin g - Ri g ht S ide View Left Return - Air Coil Openin g - Left S ide View NOTES: 1. Cond ensate is 3 / 4 -in. FPT copper and is switchab le from side to front. 2. Ve r tical unit ...

  • Carrier PSV - page 7

    7 Fig. 4 — 50 PSD Dimensiona l Data 2' S ervice Acce ss Air Coil S ide G F D K J L 4 3 2 1 5 CAP T U R S Air Coil C S P Front B a ck Front-View B S P Left Return Left View - Air Coil Openin g Conden sa te 3 /4” FPT Left Ret u rn Conden sa te 3 /4” FPT Right Ret u rn 5 1.1 1.6 T U S Air Coil Front B a ck Ri g ht Return Ri g ht View - Air ...

  • Carrier PSV - page 8

    8 Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for a WSHP: • Units are for indoor use only . • Locate in areas where ambient temperatures are betwe en 39 F and 102 F and relative humidity is no greater than 75%. • Provide sufficient space for water , electrical and duct connections. • Loc ...

  • Carrier PSV - page 9

    9 Preparation — The unit should be on the ground in a well lit area. Hung units should be take n down to ground level before converting. Side to Back Discharge Conversion 1. Remove screws to free the top and discharge panels. Set screws aside for later use. Se e Fig. 7. 2. Remove the access panel and set aside. 3. Lift the discharge panel from si ...

  • Carrier PSV - page 10

    10 VE R T IC AL UN IT S ( 50P SV , P S D ) — Each unit uses a con- densate hose inside all cabinets as a trapping loop, therefore an external trap is not necessary . See Fig. 12. Each unit must be installed with its own individual vent and means to flush or blow out the condensate drain line. Do not in- stall units with a common trap or vent. VE ...

  • Carrier PSV - page 11

    11 Table 2 — Water Quality Guideline s LEGEND *Heat exchanger mate rials consi dered are co pper , cupr onickel, 304 SS (stainless ste el), 316 SS , titanium. †Closed reci rculating syst em is identifi ed by a closed pressur ized piping system. **Recircul ating open wells should ob serve the open reci rculating desig n consideratio ns. ††If ...

  • Carrier PSV - page 12

    12 In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the W ater Quality Guidelines table. Consult a local water firm , independent testing facility , or local water authority for specific recommendations to maintain water quality within the pub- lished limits. GROUND-LOOP APPLI ...

  • Carrier PSV - page 13

    13 Optional pressure-rated hose assemblies designed specifi- cally for use with Carrier units are available. Similar hoses can be obtained from alternate supp liers. Supply and return hoses are fitted with swivel-joint fittings at one end to prevent kink- ing during installation. Refer to Fig. 14 for an illustration of a supply /return hose kit. Ma ...

  • Carrier PSV - page 14

    14 *Optional. AL — Alar m Relay Contacts AST A T — Aquastat BR — Blo wer Relay CB — Circuit Bre aker CC — Compressor Cont actor CO — Condensate Ov erflow Sensor COMPR — Compressor DTS — Discharge T emp Switch FP1 — Water Coil F reeze Protection Sensor FP2 — Air Coil Freez e Protection Sensor HP — High-Pressure Switch HWG — H ...

  • Carrier PSV - page 15

    15 *Optional. AL — Alarm Relay Contacts AST A T — Aquastat BM — Blow er Motor BMC — Blower Motor Capacitor BR — Blower Relay CB — Circuit Breaker CC — Compressor Contactor CO — Condensate Overflow Sensor COMPR — Compressor DTS — Discharge T emp Switch FP1 — Water Coil F reeze Protection Sensor FP2 — Air Co il F reeze Protect ...

  • Carrier PSV - page 16

    16 *Optional. AL — Alar m Rela y Contacts AST A T — Aquastat BM — Blower Motor BR — Blower Relay CB — Circuit Breaker CC — Compressor Contactor CO — Condensat e Overfl ow Sensor COMPR — Compressor DTS — Discharge T emp Switch ECM — Electronically Commutated Motor FP1 — Wat er Coil F reeze Protection Sensor FP2 — Air Coil F r ...

  • Carrier PSV - page 17

    17 Wire Nut Relay Contacts - N.C . Relay Contacts - N.O . Low Pressure Switch High Pressure Switch Splice Cap Circuit Breaker NO TES: 1. Compressor and blow er motor thermally prote cted internally . 2. All wiring to the unit must comply with NEC and local codes. 3. T ransformer is wired to 460 v (BLK/RED ) lead f o r 460/3/60 units. T ransformer i ...

  • Carrier PSV - page 18

    18 NO TES: 1. Compressor and blo wer motor thermally protected inter nally . 2. All wiring to the unit must comply with NEC and local codes. 3. T ransformer is wired to 460 v (BLK/RED) lead f or 460/3/60 units. T ransformer is energ y limiting or ma y hav e circuit breaker . 4. FP1 thermistor provides freeze protection f or water . When using antif ...

  • Carrier PSV - page 19

    19 Thermistor Ground Wire Nut Relay Con tacts - N.C. Relay Con tacts - N.O . Low Pressure Switch High Pressure Switch Splice Cap Circuit Breaker Capacitor LED G NO TES: 1. Compressor and bl ower mot or thermally protected internally . 2. All wiring to the unit must co mply with NEC and local codes. 3. 208-240 60 Hz units ar e wired f or 208v operat ...

  • Carrier PSV - page 20

    20 Fig. 21 — Units wi th Complete C and WS HP Ope n Multiple Protocol Controls WH S P-OPEN A50-8355 LEGEND BM — Blo wer Motor BR — Blower Rela y CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Nor mally Closed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T e ...

  • Carrier PSV - page 21

    21 W S HP-OPEN Fig. 22 — Units with Deluxe D and WSHP Open M ultiple Protocol Controls A50-8354 LEGEND BM — Blo wer Motor CO — Condensate Overflow LW T — Leaving W a ter T emperature N.C. — Nor mally Closed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T ...

  • Carrier PSV - page 22

    22 W S HP-OPEN Fig. 23 — Units wit h Complete C, ECM an d WSHP Open Multiple Protocol Controls A50-8356 LEGEND CO — Condensate Overflow LW T — Leaving Water T emperature N.C. — Nor mally Closed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier PSV - page 23

    23 W S HP-OPEN Fig. 24 — Units wi th Deluxe D, ECM and WSHP Open Multiple Protocol C ontrols A50-8353 LEGEND CO — C ondensate Ov erflow LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier PSV - page 24

    24 012207-1BT4 8 5BT LED1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION) FAN S PEED (DO-7) (MED OR LOW) OA DAMPER (AO-2) FAN S PEED (DO- 8 ) (HIGH OR FAN ON ) LWT (Inp u t 6) S AT (LAT) (Inp u ...

  • Carrier PSV - page 25

    25 Table 4 — 50PSH, PSV, PSD Elec trical Data — PSC Motor LEGEND NO TE: Unit siz es 006-012 are n ot av ailable on 50PSD u nits. Table 5 — 50PSH, PSV, PSD Electrical Data — PSC High-Stati c Motor LEGEND NO TE: Unit sizes 006-012 are n ot av ailable with PSC high-st atic motors. 50PS UNIT SIZE RA TED VO LT AG E V- P h - H z VO L TAG E MIN/MA ...

  • Carrier PSV - page 26

    26 Table 6 — 50PSH, PSV, PSD Electrical Da ta, ECM Motor LEGEND NO TES: 1. The 460-v units using an ECM (ele ctronically commut ated motor) f an motor , modulating HWR, and/or an internal secondary pump will require a neutral wire from th e supply side in order to f eed the accessor y with 265-v . 2. Unit sizes 006-0 12 are not av ailable with EC ...

  • Carrier PSV - page 27

    27 Step 9 — Wire Field Contr o ls TH E RM OS T A T C ON NE CT IO N S — The thermostat should be wired directly to the ECM control board. See Fig. 27. W A TER FREE ZE PROTECTION — The Aquazone™ con- trol allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for wat ...

  • Carrier PSV - page 28

    28 WS HP OP EN WI R ING — The WSHP Open controller will be factory mounted to the unit control panel and wired to the Complete C or Deluxe D control board, however , the system wiring will need to be completed utilizing WSHP Open con- troller wiring diagrams and the Third Party Integration (TPI) Guide. Factory installation in cludes harness, L WT ...

  • Carrier PSV - page 29

    29 3. W ire each terminal on the sensor to the same terminal on the controller . See Fig. 15-25. T a ble 10 shows the recom- mended Rnet wiring scheme. Table 10 — Rnet Wiring NO TE: The wire should be connected to the terminal shown. W iring a Supply Air T emperature (SA T) Sensor — The SA T sensor is required for reheat applications. If the ca ...

  • Carrier PSV - page 30

    30 DEHUMIDIFICA TION MODE — The dehumidification mode setting provides field selection of humidity control. When oper- ating in the normal mode, the cooling airflow sett ings are deter- mined by the cooling tap setting in T able 1 1 . When dehumidifi- cation is enabled, there is a reduction in airflow in cooling to in- crease the moisture removal ...

  • Carrier PSV - page 31

    31 Table 12 — PSC Blo wer Motor P erformance Data LEGEND NO TES: 1. Shaded ar eas denote ESP where operat ion is not recommended. 2. Units f actor y shipped on medium speed. Othe r speeds require field selection. 3. All airflo w is rated and shown abov e at the lower v oltage if unit is dual voltage r ated, e .g., 208 v fo r 208/230 v units. 4. O ...

  • Carrier PSV - page 32

    32 PRE-ST A R T -UP System Chec kout — When the installation is complete, follow the system checkout procedure outlined below before starting up the system. Be sure: 1. V oltage is within the utilizati on range specifications of the unit compressor and fan moto r and voltage is balanced for 3-phase units. 2. Fuses, breakers and wire are correct s ...

  • Carrier PSV - page 33

    33 Heating/Cooling Thermostat T ype — Switch 3 provides se- lection of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Sele ct ON fo ...

  • Carrier PSV - page 34

    34 HWR APPLICA TION CONSIDERA TIONS — Unlike most hot gas reh eat options, the HWR opt ion will operate over a wide range of entering-water temperatures (EWT s). Special flow regulation (wat er regulating valve) is no t required for low EWT conditions. However , below 55 F , supply-air temperatu res cannot be maintained at 72 F because the coolin ...

  • Carrier PSV - page 35

    35 Deluxe D Contr ol Accessory Relay Configura- tions — The following accessory relay settings are applica- ble for Deluxe D control: CYCLE WITH F AN — In this configuration, the accessory relay 1 will be ON any time the Fan Enable relay is on. CYCLE WITH COMPRESSOR — In this configuration, the accessory relay 2 will be ON any time the Compre ...

  • Carrier PSV - page 36

    36 4. Check the temperature of both supply and discharge water . Compare to T ables 20-30. If temperature is within range, proceed. If temperature is outside the range, check the cooling refrigerant pressures in T ables 20-30. 5. Check air temperature drop across the coil when com- pressor is operating. Air temperature drop should be between 15 and ...

  • Carrier PSV - page 37

    37 Table 22 — 50PSH, PSV, PSD012 Typical Unit Operating Pressures and Temperatures LEGEND Table 23 — 50PSH, PSV, PSD018 Typical Unit Operating Pressures and Temperatures LEGEND Table 24 — 50PSH, PSV, PSD024 Typical Unit Operating Pressures and Temperatures LEGEND ENTERING WATE R TEMP (F) WAT E R FLO W (GPM/ton) FULL LO AD COOLING — WITHOUT ...

  • Carrier PSV - page 38

    38 Table 25 — 50PSH, PSV, PSD030 Typical Unit Operating Pressures and Temperatures LEGEND Table 26 — 50PSH, PSV, PSD036 Typical Unit Operating Pressures and Temperatures LEGEND Table 27 — 50PSH, PSV, PSD042 Typical Unit Operating Pressures and Temperatures LEGEND ENTERING WA T E R TEMP (F) WATE R FLO W (GPM/ton) FULL LO AD COOLING — WI THOU ...

  • Carrier PSV - page 39

    39 Table 28 — 50PSH, PSV, PSD048 Typical Unit Operating Pressures and Temperatures LEGEND Table 29 — 50PSH, PSV, PSD060 Typical Unit Operating Pressures and Temperatures LEGEND Table 30 — 50PSH, PSV, PSD070 Typical Unit Operating Pressures and Temperatures LEGEND ENTERING WA T E R TEMP (F) WATE R FLO W (GPM/ton) FULL LO AD COOLING — WITHO U ...

  • Carrier PSV - page 40

    40 Unit Start-Up with WSHP Open Controls The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options and powerful capabilities. The unit comes from the factory pre-programmed and needs minimal set up to function in a BAS (Building Auto- mation System) system or provide additional capabilities to Carrie ...

  • Carrier PSV - page 41

    41 f. Press OK to apply and sav e to a particular day of the week. g. Continue to add the same or dif ferent sched ule spe- cific days of the week. T o add exceptions to the schedule: i. Press Add softkey . ii. Select exception type from follow ing: • Date • Date Range • W eek-N-Day • Calender Reference 9. Go back to Home Screen. 10. Remove ...

  • Carrier PSV - page 42

    42 Calculate the total volume of fluid in the piping system. See T able 32. Use the percentage by volume in T able 33 to deter- mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well- mixed sample using a hydrom- eter to measure specific gravity . FREEZE PROTECTION SELECTION — Th e 30 F FP 1 factory setting ( ...

  • Carrier PSV - page 43

    43 application, all compressor relays and related functions will operate per their associated DIP switch 2 setting on S1. HE A TI NG ST A GE 3 — In Heating Stage 3 mode, the Fan Enable, Fan Speed and Compressor relays remain on. The EH1 output is turned on immediately . With continuing Heat S tage 3 demand, EH2 will turn on after 10 minutes. EH1 ...

  • Carrier PSV - page 44

    44 NOTE: Scheduling can either be controlled via the unit or the BAS, but not both. INDOOR FAN — Th e i ndoor fan will operate in any one of three modes depending on the user configuration selected. Fan mode can be selected as Auto, Continuous, or Always On. In Auto mode, the fan is in intermittent operation during both occupied and unoccupied pe ...

  • Carrier PSV - page 45

    45 speed. Should this be insuffic ient, and the SA T rises further reaching the maximum heating SA T limit, the fan will be indexed to the maximum speed. If the SA T still continues to rise 5 F above the maximum limit, all heating stages will be disabled. During Heating mode, the reve rsing valve output will be held in the heating position (either ...

  • Carrier PSV - page 46

    46 screen. The following conditions must be true for economizer operation: • SA T reading is available. • L WT reading is available. • If oc cupied, the SP T is greater than the occupied cooling set point or le ss than the o ccupied heating set point and the condenser water is suitable. • Space temperature reading is valid. • If unoccupie ...

  • Carrier PSV - page 47

    47 Table 35 — Complete C Contr ol LED Code and Fault Descript ions LEGEND WSHP Open T est Mode — T o enter WSHP Open test mode, navigate from the BAC view 6 h ome screen to the config- uration screen. Choose the servic e screen and enable unit test. The controller will then test the following: F AN T ES T — T ests all fan speeds, sequenc es f ...

  • Carrier PSV - page 48

    48 SER VICE Perform the procedures ou tlined below periodically , as indicated. Filter s — Filters must be clean for maximum performance. Inspect filters every month under normal operating conditions. Replace when necessary . W ater Coil — Keep all air out of the water coil. Check open loop systems to be sure the well head is not allowing air t ...

  • Carrier PSV - page 49

    49 Checkin g System Char ge — Units are shipped with full operating charge. If rechar ging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier . Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer . 2. Connect pressure gage to di schar ge line ...

  • Carrier PSV - page 50

    50 WSHP Open Contr oller — W ith the WSHP Open con- troller option, the 100 most recent alarms can be viewed using the BAC view 6 alarm status and alarm history . T o view the alarms: 1. Navigate to the Alarm S tatus screen from the Home screen using the arrow softkeys. The screen will display the current alarm status , either normal or Alarm, an ...

  • Carrier PSV - page 51

    51 The bulb must be secured to the pipe using a copper strap. The use of heat transfer paste between the bulb and the pipe will also help ensure optimum performance. The bulb must also be properly insulated to eliminate any influence on valve operation by the surrounding conditions. Cork tape is the recommended insulation as it can be molded tight ...

  • Carrier PSV - page 52

    52 See T ables 37-39 for additional troubleshooting information. Table 37 — ECM Tro ubleshooting IMPOR T ANT : Always recover the refrigerant from the system with suitable approved tools, recovery equipment, and practices prior to attempting to remove or repair any TXV . IMPORTANT: Due to the hygroscopic nature of the PO E oi l i n P ur on refrig ...

  • Carrier PSV - page 53

    53 Fig. 40 — ECM Pin Connector s a50-8448 ...

  • Carrier PSV - page 54

    54 Stopped or Malfunctioned ECM Motor — Refer to Fig. 41 to determine the possible cause of a stopped or mal- functioned ECM motor . Follow the instructions in the b oxes. Fig. 41 — ECM T roubl eshooting Flow Dia gram a50-8447 ...

  • Carrier PSV - page 55

    55 Moisture Check — T o perform moisture check: • Check that connectors are orie ntated “down” (or as recom- mended by equipment manufacturer). • Arrange harnesses with “drip loop” under motor . • Check if condensate drain is plugged. • Check for low airflow (too much latent capacity). • Check for undercharged condition. • Che ...

  • Carrier PSV - page 56

    56 Table 39 — WSHP Troubleshooting ( cont) LEGEN D F A UL T HEA TING COOLING POSSIBLE CA USE SOL UTION Conden sate Fault — Code 6 X X Block ed drain Check f or bloc kage and clean drain . X X Improper trap Check trap dimensions and location ahead of v ent. X P oor drainage Check f or piping slope awa y from unit. Check slope of unit t owa rd ou ...

  • Carrier PSV - page 57

    57 Table 39 — WSHP Troubleshooting ( cont) LEGEND F A UL T HEA TING COOLING POSSIBLE CAUSE SOLUTION High Head Pressure X Reduced or no airflo w in heating Check f or dir ty air filter and clean or replace. Check f an motor operation and airflow restrictions . External static too high. Check b lower performance per T ables 11-13. X Reduced or no w ...

  • Carrier PSV - page 58

    58 APPENDIX A — WSHP OPEN SCREEN CONFIGURA TION LEGEND SCREEN NAME P OINT NAME PA SS WO RD LEVEL EDITABLE RANG E DEFAULT NOTES Equipment Status Operati ng Mode No P assword Required Off, F an Only , Economize , Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operat ing mode SPT F Displa ys SPT SA T F Displa ys SA T Con ...

  • Carrier PSV - page 59

    59 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA SS WOR D LEVEL EDITABLE RANGE DEFAULT NOTES Unit Maintenance Operating Mode No P assw ord required Off, F an Only ,Econo mize, Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operating mode F an Operating Mode Auto /Continuou s/Alwa ...

  • Carrier PSV - page 60

    60 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PASS WO RD LEVEL EDITABLE RANG E DEFAULT NOTES Configuration Set Points Occupied Heating User/Admin P assw ord le vel access X 40 - 90 F 72 F Defines the Occu pied Heating Set P oint Occupied Cooling X 55 - 99 F 76 F Defines the Occu pied Cooling Set P oint Unoccu ...

  • Carrier PSV - page 61

    61 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SWO RD LEVE L EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration F an Mode Admin P ass word lev el access only X Aut o/Continuous/ Always On Continuous Aut o= Intermittant operation during both occupied and unoccupied periods/ Continuou s = Intermit ...

  • Carrier PSV - page 62

    62 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PAS SW ORD LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Service Configuration # of F an Speeds Admin P assword lev el access only X 1,2,3 3 Used to set number of fan mot or speeds G Output T ype X F an On/F an Low F an On When set to F an On, G output is ener ...

  • Carrier PSV - page 63

    63 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SWO RD LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Alarm Configuration SPT Occupied Alarm Hysteresis Admin P a ss word lev el access only X2 - 2 0 F 5 F Defines the h ysteresis applied above the cooling and belo w the heating set points bef ore an alarm c ...

  • Carrier PSV - page 64

    64 ...

  • Carrier PSV - page 65

    65 ...

  • Carrier PSV - page 66

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500055-01 Printed in U .S.A. Form 50PS-3SI Pg 66 7-09 Replaces: 50PS-2SI Copy right 2009 Carrier Cor poration ...

  • Carrier PSV - page 67

    CL-1 50PSH,PSV ,PSD ST ART -UP CHECKLIST CUSTOMER: ___________________________ JOB NAME: _____________________________ __________ MODEL NO.:___________________________ SERIAL NO.:____________________ DA TE: _________ I. PRE-ST ART -UP DOES THE UNIT VOL T AGE CORRESPOND WI TH THE SUPPL Y VOL T AGE A V AILABLE? (Y/N) HA VE THE POWER AND CONTROL WIRIN ...

  • Carrier PSV - page 68

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500055-01 Printed in U.S .A. Form 50PS-3SI Pg CL-2 7-09 Replaces: 50PS-2SI Copy right 2009 Carrier Cor poration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

メーカー Carrier カテゴリー Heat Pump

Carrier PSVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- PSVの取扱説明書
- Carrierの製品カード
- パンフレット
- またはCarrier PSVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Carrier PSVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Carrier PSVの取り付け説明書、サービスマニュアル、簡易説明書、またはCarrier PSVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Carrier PSVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Carrier PSVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがCarrier PSVを使用するのを助ける技術的文書のことです。説明書は通常、全てのCarrier PSVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Carrierの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Carrier PSVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははCarrier PSVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Carrier PSVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Carrier PSVデバイスの基本機能を使うにあたってのヒント。 Carrier PSVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Carrier PSVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるCarrier PSVのメーカー/サービスへの連絡先に関する情報。

Carrier PSVについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもCarrier PSVの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがCarrier PSVで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)