    CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P A GE Dimensions .................................. 2,3 Installation Requirements: Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Boiler F oundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Chimney Requirements . . . . . . . ...

  • Slant/Fin S-150 - page 2

    2 Sentr y ...

  • Slant/Fin S-150 - page 3

    The installation must conf orm to the requirements of the author ity having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. This installation must also conf orm to the additional requirements in this Slant/Fin Instruction Book. NA TURAL GAS-FIRED BOILER LOCA TION Pro vide a le v el, ...

  • Slant/Fin S-150 - page 4

    A. Minimum boiler clearances shall be as f ollo ws: B. Pro vide accessibility clearance of 24” on sides requiring ser vicing and 18” on sides used for passage. C . All minimum clearances sho wn abo ve m ust be met. This may result in increased v alues of some minimum clearances in order to maintain the minimum clearances of others . D . Clearan ...

  • Slant/Fin S-150 - page 5

    must be suppor ted to prev ent sagging b y securing each joint with metal screws and b y providing hanger spaced no greater than 5 f eet apar t. D . V ent or breeching into chimney should not be inser ted past the inside wall of the chimne y liner . E. All venting means should be inspected frequently . See Care and Maintenance and separate User&apo ...

  • Slant/Fin S-150 - page 6

    Figure 4. Figure 6. Connecting “RECEPT ACLE B” to “MALE PLUG” inside L8148E Aquastat Bo x for Sentry P acka ged “S” and “SX” boilers. Figure 5. V ent Damper Dimensions T ABLE Figure 8. Damper V ane Figure 9. 6 Sentr y V ent S ize 4" 5" 6" 7" 8" A9 5 ⁄ 16 "1 0 5 ⁄ 16 "1 1 5 ⁄ 16 "1 2 5 ? ...

  • Slant/Fin S-150 - page 7

    B. 1. This device must be installed after the boiler dr aft hood ( between the draft hood outlet and the connector to the out- door chimney or v ent) as close to the draft hood as pr acti- cable , and without modification of the draft hood or the v ent damper . (See figures 1, 2 and 3.) 2. The inlet size of the v ent damper must be the same nomi- n ...

  • Slant/Fin S-150 - page 8

    BOILER ROOM AIR SUPPL Y AND VENTILA TION An ample supply of air is required to obtain combustion and ventilation. ALL AIR COMES FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows , doors, etc. in the whole building. When build- ings are insulated, caulked and w eather stripped, now or later on, di ...

  • Slant/Fin S-150 - page 9

    5. Using soap solution, chec k f or gas leaks in all gas piping from meter to boiler pilot and manif old. DO NO T use open flame. II. INITIAL ST ART Saf e lighting and other perf ormance cr iteria were met when testing various gas manif old and control assemb lies used on t he Sentr y Series Boilers under the ANSI-Z21.13-1991 S tandard. INSTRUCTION ...

  • Slant/Fin S-150 - page 10

    Figure 13. V alve VR8204 or VR8304 Figure 14. 2. Intermittent Pilot System (IID). FOR BOILERS EQUIPPED WITH HONEYWELL GAS V AL VE VR8204 OR VR8304 (see figures 13 and 14). SAFETY INFORMA TION FOR Y OUR SAFETY READ BEFORE OPERA TING W ARNING: If you do not f ollow these instructions e xactly , a fire or e xplosion may result causing property damage, ...

  • Slant/Fin S-150 - page 11

    a. Boiler (b urner) is ov erfiring. CA UTION! National Fuel Gas Code ANSI Z223.1-latest edition, does NO T per- mit firing at a higher input rate than the input rate indi- cated on the boiler rating plate in order to a v oid haz- ardous conditions such as e xplosion or carbon mono xide poisoning. b . P oor higher* heating v alue of gas is causing t ...

  • Slant/Fin S-150 - page 12

    3. W ater lines: slightest leaks should be corrected. 4. Lo w water cutoff , for operation (see instructions fur- nished with unit). 2 . W A TER LEVEL CHECK DURING HEA TING SEASON A. Check w ater pressure regularly and add water slowly to system when needed. If much water is added, v enting may be necessary . B . Regular loss of water from water bo ...

  • Slant/Fin S-150 - page 13

    S EQUENCE OF OPERA TION FOR SENTR Y BOILERS EQUIPPED WITH CONTINUOUS BURNING PILO TS F OR DIA GRAMS SHO WN ON P A GE 14. 13 Sentr y LIGHTED PILO T HEA TS THERMOCOUPLE AND KEEPS PILO TST A T OPEN. THERMOST A T CALLS FOR HEA T HIGH LIMIT CONT ACTS CLOSED? LOW W A TER CUT -OFF (WHEN USED) CONT ACTS CLOSED? VENT D AMPER RELA Y ENERGIZED . VENT D AMPER ...

  • Slant/Fin S-150 - page 14

    WIRING DIA GRAM — CONTINUOUS PILOT 14 Sentr y CA UTION: Label all wires prior to disconnection when ser vicing controls. Wiring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin S-150 - page 15

    15 Sentr y WIRING DIA GRAM — INTERMITTENT IGNITION (IID) CA UTION: Label all wires prior to disconnection when ser vicing controls. W iring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin S-150 - page 16

    P UMP OR V AL VE ZONING OF W A TER BOILERS COMBINA TION CONTROLS WITH T TV Z TERMINALS* 16 Sentr y Pump Zoning system using R845A Rela y . One R845A needed f or each circulator . NO TE: Pumps are powered from C1 . T otal pump load must not e xceed 7.4 amp rating of combination control pump s witch. Zone valv e zoning system using Honeywell V8043F z ...

  • Slant/Fin S-150 - page 17

    17 Sentr y GENERAL TROUBLESHOO TING GUIDE FOR SER VICEPEOPLE BURNERS F AIL T O OPERA TE CA USE 1. Saf ety pilot out, or flame too lo w . 2. Gas supply v alv e shut off . 3. Electric s witch open. 4. Blo wn or def ectiv e line fuse. 5. Oper ating or limit control contacts open or dir ty . 6 . Def ectiv e gas v alv e or pressure regulator; or plugged ...

  • Slant/Fin S-150 - page 18

    PIPING A HEA TING - COOLING SYSTEM T O A W A TER BOILER AND CHILLER The chiller must be piped in parallel with the boiler . Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller . Hand v alv es (shown) or automatic valv es must be installed to prev ent circulation of chilled water in t he boiler or hot ...

  • Slant/Fin S-150 - page 19

    (a) Seal an y unused openings in the common v enting system. (b) Visually inspect the v enting system f or proper siz e and hor- i zontal pitch and determine there is no blockage or restric- tion, leakage, corrosion and other deficiencies which could cause an unsaf e condition. (c) Insof ar as is pr actical, close all building doors and windo ws an ...

  • Slant/Fin S-150 - page 20

    SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontar io www .slantfin.com ...

メーカー Slant/Fin カテゴリー Boiler

Slant/Fin S-150のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- S-150の取扱説明書
- Slant/Finの製品カード
- パンフレット
- またはSlant/Fin S-150の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Slant/Fin S-150の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Slant/Fin S-150の取り付け説明書、サービスマニュアル、簡易説明書、またはSlant/Fin S-150のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Slant/Fin S-150の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Slant/Fin S-150デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSlant/Fin S-150を使用するのを助ける技術的文書のことです。説明書は通常、全てのSlant/Fin S-150ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Slant/Finの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Slant/Fin S-150の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSlant/Fin S-150の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Slant/Fin S-150に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Slant/Fin S-150デバイスの基本機能を使うにあたってのヒント。 Slant/Fin S-150のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Slant/Fin S-150に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるSlant/Fin S-150のメーカー/サービスへの連絡先に関する情報。

Slant/Fin S-150についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもSlant/Fin S-150の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがSlant/Fin S-150で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)