  • Slant/Fin S-150 - page 1

    CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P A GE Dimensions .................................. 2,3 Installation Requirements: Boiler Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Boiler F oundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Chimney Requirements . . . . . . . ...

  • Slant/Fin S-150 - page 2

    2 Sentr y ...

  • Slant/Fin S-150 - page 3

    The installation must conf orm to the requirements of the author ity having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest edition. This installation must also conf orm to the additional requirements in this Slant/Fin Instruction Book. NA TURAL GAS-FIRED BOILER LOCA TION Pro vide a le v el, ...

  • Slant/Fin S-150 - page 4

    A. Minimum boiler clearances shall be as f ollo ws: B. Pro vide accessibility clearance of 24” on sides requiring ser vicing and 18” on sides used for passage. C . All minimum clearances sho wn abo ve m ust be met. This may result in increased v alues of some minimum clearances in order to maintain the minimum clearances of others . D . Clearan ...

  • Slant/Fin S-150 - page 5

    must be suppor ted to prev ent sagging b y securing each joint with metal screws and b y providing hanger spaced no greater than 5 f eet apar t. D . V ent or breeching into chimney should not be inser ted past the inside wall of the chimne y liner . E. All venting means should be inspected frequently . See Care and Maintenance and separate User&apo ...

  • Slant/Fin S-150 - page 6

    Figure 4. Figure 6. Connecting “RECEPT ACLE B” to “MALE PLUG” inside L8148E Aquastat Bo x for Sentry P acka ged “S” and “SX” boilers. Figure 5. V ent Damper Dimensions T ABLE Figure 8. Damper V ane Figure 9. 6 Sentr y V ent S ize 4" 5" 6" 7" 8" A9 5 ⁄ 16 "1 0 5 ⁄ 16 "1 1 5 ⁄ 16 "1 2 5 ? ...

  • Slant/Fin S-150 - page 7

    B. 1. This device must be installed after the boiler dr aft hood ( between the draft hood outlet and the connector to the out- door chimney or v ent) as close to the draft hood as pr acti- cable , and without modification of the draft hood or the v ent damper . (See figures 1, 2 and 3.) 2. The inlet size of the v ent damper must be the same nomi- n ...

  • Slant/Fin S-150 - page 8

    BOILER ROOM AIR SUPPL Y AND VENTILA TION An ample supply of air is required to obtain combustion and ventilation. ALL AIR COMES FROM OUTSIDE, directly through wall openings to the boiler or through unsealed openings around windows , doors, etc. in the whole building. When build- ings are insulated, caulked and w eather stripped, now or later on, di ...

  • Slant/Fin S-150 - page 9

    5. Using soap solution, chec k f or gas leaks in all gas piping from meter to boiler pilot and manif old. DO NO T use open flame. II. INITIAL ST ART Saf e lighting and other perf ormance cr iteria were met when testing various gas manif old and control assemb lies used on t he Sentr y Series Boilers under the ANSI-Z21.13-1991 S tandard. INSTRUCTION ...

  • Slant/Fin S-150 - page 10

    Figure 13. V alve VR8204 or VR8304 Figure 14. 2. Intermittent Pilot System (IID). FOR BOILERS EQUIPPED WITH HONEYWELL GAS V AL VE VR8204 OR VR8304 (see figures 13 and 14). SAFETY INFORMA TION FOR Y OUR SAFETY READ BEFORE OPERA TING W ARNING: If you do not f ollow these instructions e xactly , a fire or e xplosion may result causing property damage, ...

  • Slant/Fin S-150 - page 11

    a. Boiler (b urner) is ov erfiring. CA UTION! National Fuel Gas Code ANSI Z223.1-latest edition, does NO T per- mit firing at a higher input rate than the input rate indi- cated on the boiler rating plate in order to a v oid haz- ardous conditions such as e xplosion or carbon mono xide poisoning. b . P oor higher* heating v alue of gas is causing t ...

  • Slant/Fin S-150 - page 12

    3. W ater lines: slightest leaks should be corrected. 4. Lo w water cutoff , for operation (see instructions fur- nished with unit). 2 . W A TER LEVEL CHECK DURING HEA TING SEASON A. Check w ater pressure regularly and add water slowly to system when needed. If much water is added, v enting may be necessary . B . Regular loss of water from water bo ...

  • Slant/Fin S-150 - page 13

    S EQUENCE OF OPERA TION FOR SENTR Y BOILERS EQUIPPED WITH CONTINUOUS BURNING PILO TS F OR DIA GRAMS SHO WN ON P A GE 14. 13 Sentr y LIGHTED PILO T HEA TS THERMOCOUPLE AND KEEPS PILO TST A T OPEN. THERMOST A T CALLS FOR HEA T HIGH LIMIT CONT ACTS CLOSED? LOW W A TER CUT -OFF (WHEN USED) CONT ACTS CLOSED? VENT D AMPER RELA Y ENERGIZED . VENT D AMPER ...

  • Slant/Fin S-150 - page 14

    WIRING DIA GRAM — CONTINUOUS PILOT 14 Sentr y CA UTION: Label all wires prior to disconnection when ser vicing controls. Wiring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin S-150 - page 15

    15 Sentr y WIRING DIA GRAM — INTERMITTENT IGNITION (IID) CA UTION: Label all wires prior to disconnection when ser vicing controls. W iring errors can cause improper and dangerous operation. “V er ify proper operation after ser vicing. ” ...

  • Slant/Fin S-150 - page 16

    P UMP OR V AL VE ZONING OF W A TER BOILERS COMBINA TION CONTROLS WITH T TV Z TERMINALS* 16 Sentr y Pump Zoning system using R845A Rela y . One R845A needed f or each circulator . NO TE: Pumps are powered from C1 . T otal pump load must not e xceed 7.4 amp rating of combination control pump s witch. Zone valv e zoning system using Honeywell V8043F z ...

  • Slant/Fin S-150 - page 17

    17 Sentr y GENERAL TROUBLESHOO TING GUIDE FOR SER VICEPEOPLE BURNERS F AIL T O OPERA TE CA USE 1. Saf ety pilot out, or flame too lo w . 2. Gas supply v alv e shut off . 3. Electric s witch open. 4. Blo wn or def ectiv e line fuse. 5. Oper ating or limit control contacts open or dir ty . 6 . Def ectiv e gas v alv e or pressure regulator; or plugged ...

  • Slant/Fin S-150 - page 18

    PIPING A HEA TING - COOLING SYSTEM T O A W A TER BOILER AND CHILLER The chiller must be piped in parallel with the boiler . Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller . Hand v alv es (shown) or automatic valv es must be installed to prev ent circulation of chilled water in t he boiler or hot ...

  • Slant/Fin S-150 - page 19

    (a) Seal an y unused openings in the common v enting system. (b) Visually inspect the v enting system f or proper siz e and hor- i zontal pitch and determine there is no blockage or restric- tion, leakage, corrosion and other deficiencies which could cause an unsaf e condition. (c) Insof ar as is pr actical, close all building doors and windo ws an ...

  • Slant/Fin S-150 - page 20

    SLANT/FIN CORPORA TION, Green vale, N.Y . 11548 • Phone: (516) 484-2600 F AX: (516) 484-5921 • Canada: Slant/Fin L TD/L TEE , Mississauga, Ontar io www .slantfin.com ...

Manufacturer Slant/Fin Category Boiler

Documents that we receive from a manufacturer of a Slant/Fin S-150 can be divided into several groups. They are, among others:
- Slant/Fin technical drawings
- S-150 manuals
- Slant/Fin product data sheets
- information booklets
- or energy labels Slant/Fin S-150
All of them are important, but the most important information from the point of view of use of the device are in the user manual Slant/Fin S-150.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Slant/Fin S-150, service manual, brief instructions and user manuals Slant/Fin S-150. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Slant/Fin S-150.

A complete manual for the device Slant/Fin S-150, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Slant/Fin S-150 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Slant/Fin S-150.

A complete Slant/Fin manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Slant/Fin S-150 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Slant/Fin S-150, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Slant/Fin S-150, that we can find in the current document
3. Tips how to use the basic functions of the device Slant/Fin S-150 - which should help us in our first steps of using Slant/Fin S-150
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Slant/Fin S-150
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Slant/Fin S-150 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Slant/Fin S-150?

Use the form below

If you did not solve your problem by using a manual Slant/Fin S-150, ask a question using the form below. If a user had a similar problem with Slant/Fin S-150 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)