    Fiberglass Cooling Towers Part Number: 882.00440.00 Bulletin Number: SC6-610.6 Effective: 9/10/07 Write Down Your Serial Numbers Here For Future Reference: _________________________ _________________________ _________________________ _________________________ _________________________ _________________________ We are committed to a continuing progr ...

  • Sterling 882.00440.00 SC6-610.6 - page 2

    Fiberglass Cooling Towers ii Shipping Information Unpacking and Inspection You should inspect your equipm ent for possible shipping damage. Thoroughly check the equipment for any damage that m ight have occu rred in transit, such as broken or loose wiring and components, loose hardware and mounting screws, etc. In the Event of Shipping Damage Accor ...

  • Sterling 882.00440.00 SC6-610.6 - page 3

    Fiberglass Cooling Towers iii Table of Contents CHAPTER 1: SAFETY ................................................................ 6 1-1 How to Use Th is M anual ................................................................................. 6 Safety Symbols Used in this Manual ..................................................................... ...

  • Sterling 882.00440.00 SC6-610.6 - page 4

    Fiberglass Cooling Towers iv 6-3 Parts Li st ....................................................................................................... 24 6-4 Electrical Sc hematic s .................................................................................... 25 ...

  • Sterling 882.00440.00 SC6-610.6 - page 5

    Fiberglass Cooling Towers v List of Figures Figure 1: Structural Stee l Support Requirements ......................................................................... 11 Figure 2: Rigging Arrangement .................................................................................................. .. 13 Figure 3: Cooling Tower with To wer Reservoir ...

  • Sterling 882.00440.00 SC6-610.6 - page 6

    Fiberglass Cooling Towers Chapter 1: Safety Page 6 of 25 Chapter 1: Safety 1-1 How to Use This Manual Use this manual as a guide and reference for installing, operating, and maintaining your equipment. The purpose is to assist you in a pplying efficient, proven techniques that enhance equipment productivity. This manual covers only light corrective ...

  • Sterling 882.00440.00 SC6-610.6 - page 7

    Fiberglass Cooling Towers Chapter 1: Safety Page 7 of 25 1-2 Warnings and Precautions Our equipment is designed to provide safe and reliable operation when installed and operated within design specifications, following national and local safety codes. To avoid possible personal injury or equi pm ent damage when installing, operating, or maintaining ...

  • Sterling 882.00440.00 SC6-610.6 - page 8

    Fiberglass Cooling Towers Chapter 2: Functional Description Page 8 of 25 Chapter 2: Functional Description 2-1 Models Covered in This Manual This manual covers fiberglass cooling tower m odels. Model numbers are listed on the serial tag. A model number followed by –Q is specially-constructed, and the information in this manual may not apply. Make ...

  • Sterling 882.00440.00 SC6-610.6 - page 9

    Fiberglass Cooling Towers Chapter 2: Functional Description Page 9 of 25 2-4 Optional Features Side Outlet. The side outlet is used when th e tower basin is used as a reservoir. Starter Package. The starter package includes a st arter, a re mote On/Off switc h, a thermostat, and a well. Basin Reservoir. The basin reservoir includes an automatic flo ...

  • Sterling 882.00440.00 SC6-610.6 - page 10

    Fiberglass Cooling Towers Chapter 3: Installation Page 10 of 25 Chapter 3: Inst allation 3-1 Tower Installation Location Roof Installation Select a location over or nearest to the heavi est building structural members. These members should be outside load-bearing walls, building co l umns, or roof joists. You may need to spread the load over severa ...

  • Sterling 882.00440.00 SC6-610.6 - page 11

    Fiberglass Cooling Towers Chapter 3: Installation Page 11 of 25 Figure 1: Structural St eel Support Requirements TSE50 Structural steel A C C B B C C D 2 X 2 angle to support tower basin, flush with top of structural steel rails Model A B C D number in. cm in. cm in. cm in. cm SF2003 52 132.1 50 127.0 16 40.6 78 175.3 SF2004 52 132.1 50 127.0 16 40 ...

  • Sterling 882.00440.00 SC6-610.6 - page 12

    Fiberglass Cooling Towers Chapter 3: Installation Page 12 of 25 3-2 Assembling the Cooling Tower in the Field Your cooling tower may have been shipped on two skids to reduce shipping charges. One skid contains the lower section, identifie d by the black fill wrapped in plastic on the inside of the lower section. The second skid contains the top tow ...

  • Sterling 882.00440.00 SC6-610.6 - page 13

    Fiberglass Cooling Towers Chapter 3: Installation Page 13 of 25 Do not let the rigging transfer any load to the cooling tower shell. Provide support to the bottom of the cooling tower when riggi ng. Do not rig from the corners of the o p tional base. Do not ri g less than 8 inches from the corners. 3-3 Rigging Handle the fiberglass cooling tower sh ...

  • Sterling 882.00440.00 SC6-610.6 - page 14

    Fiberglass Cooling Towers Chapter 3: Installation Page 14 of 25 Install the piping according to the piping diagra ms in Figure 3 on page 14, Figure 4 on page 14, and Figure 5 on page 15. Figure 3: Cooling Tower with To wer Reservoir Piping Diagram inlet Type 2 Type 2 pressure gauge Do not apply excessive torque to fittings Caution! Overflow 3/4&quo ...

  • Sterling 882.00440.00 SC6-610.6 - page 15

    Fiberglass Cooling Towers Chapter 3: Installation Page 15 of 25 Figure 5: Flexible PVC Outlet Coupler Tower outlet Flexible PVC coupling (from AEC) Outlet pipe must be supported from building structure or tower steel Clamps (from AEC) (from Sterling) Flexible PVC Coupling (from Sterlin g ) ...

  • Sterling 882.00440.00 SC6-610.6 - page 16

    Fiberglass Cooling Towers Chapter 3: Installation Page 16 of 25 3-6 Setting Up the Water Balancing Valve Install the plug provided in the unused water in let on the side of the tower. Tighten and check for leaks. To prevent damage to the tower fill materi al, use the water throttling valve and pressure gauge to regulate the water pressure to the to ...

  • Sterling 882.00440.00 SC6-610.6 - page 17

    Fiberglass Cooling Towers Chapter 4: Operation Page 17 of 25 Chapter 4: Operation 4-1 Bleed-Off and Evaporation Rates A proper bleed-off rate is important to limit the concentration of minerals and foreign materials in re-circulated water. A bleed-off e qual to the evaporation rate, normally about two gallons per hour per ton (7. 57 liters per hour ...

  • Sterling 882.00440.00 SC6-610.6 - page 18

    Fiberglass Cooling Towers Chapter 5: Maintenance Page 18 of 25 Chapter 5: Maintenance 5-1 Preventative Maintenance Water Treatment Control of slime, algae, and bacteria growth is extremely important. Cooling towers and reservoir pump tanks are superb environments for microorganism growth. Warm water, organic debris, and air encourage bacterial grow ...

  • Sterling 882.00440.00 SC6-610.6 - page 19

    Fiberglass Cooling Towers Chapter 5: Maintenance Page 19 of 25 5-2 Corrective Maintenance Replacing Nozzles and Fill The PVC fill used in these cooling towers provides years of maintenance-free service under normal conditions. If you discover dirty water or defective nozzle(s) dama ge the fill, you can order a replacement kit from the parts departm ...

  • Sterling 882.00440.00 SC6-610.6 - page 20

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 20 of 25 Chapter 6: Appendix 6-1 Technical Assistance Parts Department Call Toll-Free 7am–6pm CST [ 800 ] 423-3183 or call [ 262 ] 641-8 610 Our Parts Department is ready to provide th e parts to keep your s ystems up and running. OEM replacement parts ensure operation at d esign specifications. ...

  • Sterling 882.00440.00 SC6-610.6 - page 21

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 21 of 25 6-2 Drawings and Specifications C A0536711 A Fan guard B Top View Access Fan motor Fan blade Nozzle adaptor Nozzle door Rigid PVC tower fill Water diverter Motor support assembly Side View Cutaway View Supply piping D Return pipin g E Figure 7: Dimensions and Weights Dimensions Weights Mo ...

  • Sterling 882.00440.00 SC6-610.6 - page 22

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 22 of 25 Figure 8: Tower Performance c Cooling Fan NEC Nominal Model capacity Nozzles motor amp draw air flow number tons Kcal/hr no. hp kW rpm 460/3/60 cfm cmh SF2003 50 151,200 1 2 1.5 1,200 3.4 12,000 20,388 SF2004 75 226,800 4 5 3.7 1,200 7.6 18,000 30,582 SF2005 100 302,400 4 5 3.7 900 7.6 23 ...

  • Sterling 882.00440.00 SC6-610.6 - page 23

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 23 of 25 Figure 9: Cooling Tower Nozzle Capacity ...

  • Sterling 882.00440.00 SC6-610.6 - page 24

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 24 of 25 6-3 Parts List Figure 10: Supplied Parts for Field Assembly Part Number Quantity Description A0101485 1 Silicone A0533163 110 Stainless steel flat washers, 5/16” A0539417 55 Stainless steel screws, 5/16”-18 x 1 3/4” A0533167 55 Stainless steel hex nut, 5/16”-18 A0534122 55 Stainle ...

  • Sterling 882.00440.00 SC6-610.6 - page 25

    Fiberglass Cooling Towers Chapte r 6: Appendix Page 25 of 25 6-4 Electrical Schematics Figure 12: Typical Wiring Diagram 115/1/60 208-230-460/3/60 Starter with overloads M Fan ON/OFF switch Thermostat Immerse bulb in tank Non-fused disconnect at tower Fused disconnect switch ...

メーカー Sterling カテゴリー Fan

Sterling 882.00440.00 SC6-610.6のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 882.00440.00 SC6-610.6の取扱説明書
- Sterlingの製品カード
- パンフレット
- またはSterling 882.00440.00 SC6-610.6の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Sterling 882.00440.00 SC6-610.6の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Sterling 882.00440.00 SC6-610.6の取り付け説明書、サービスマニュアル、簡易説明書、またはSterling 882.00440.00 SC6-610.6のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Sterling 882.00440.00 SC6-610.6の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Sterling 882.00440.00 SC6-610.6デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSterling 882.00440.00 SC6-610.6を使用するのを助ける技術的文書のことです。説明書は通常、全てのSterling 882.00440.00 SC6-610.6ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Sterlingの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Sterling 882.00440.00 SC6-610.6の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSterling 882.00440.00 SC6-610.6の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Sterling 882.00440.00 SC6-610.6に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Sterling 882.00440.00 SC6-610.6デバイスの基本機能を使うにあたってのヒント。 Sterling 882.00440.00 SC6-610.6のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Sterling 882.00440.00 SC6-610.6に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるSterling 882.00440.00 SC6-610.6のメーカー/サービスへの連絡先に関する情報。

Sterling 882.00440.00 SC6-610.6についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもSterling 882.00440.00 SC6-610.6の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがSterling 882.00440.00 SC6-610.6で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)