    D*V Model Air Cooled Self Contained Indoor Packaged Units 2-25 Tons Preliminary Application Data July 28, 2008 Page 1 ...

  • York D*V - page 2

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 95,000* Design CFM: 3,200 Energy Efficiency Ratio : 11.55 EER** Net Cooling Capacity [Btuh] : 92,000** Net Cooling CFM: 3,200 Refrigerant : R22 Charge : 8.75 Lbs./ circuit Compre ss or No./Type: 2/Scrol l Refrigerant Circuits : 2 / Independent Evaporator Coil Face Area: 8.67 [sq ft] ...

  • York D*V - page 3

    DATE: DESCRIPTION: "DPV" SERIES VER TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS GENERAL All models 5-15 tons ship as facto ry-charged unitized packages. The 20 ton model shall be shipped as separate eva po rator and condensing unit modules (nitrogen holdi ng charge only). All units may be field split and installed as separate mo ...

  • York D*V - page 4

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 90. 0 72. 0 97. 5 57. 3 106. 7 43. 8 86. 8 70. 6 94. 1 55. 9 102. 5 42. 2 300 0 80° F 91. 3 86. 7 98. 2 71. 6 107. 6 57. 8 88. 4 85. 8 94. 7 70. 2 103. 4 56. 2 85° F 96 ...

  • York D*V - page 5

    March 2008 DIMENSIONAL DATA DPV096 & DPV120 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA4 (308) 4 of 4 DPV096 AND DPV120 DIMENSIONAL DA T A Page 5 ...

  • York D*V - page 6

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 122,000* Design CFM: 4,000 Energy Efficiency Ratio : 10.60 EER** Net Cooling Capacity [Btuh] : 117,000** Net Cooling CFM: 3,600 Refrigerant : R22 Charge : 9.5 Lbs./ circuit Compre ss or No./Type: 2/Scrol l Refrigerant Circuits : 2 / Independent Evaporator Coil Face Area: 8.67 [sq ft ...

  • York D*V - page 7

    DATE: DESCRIPTION: "DPV" SERIES VER TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS GENERAL All models 5-15 tons ship as facto ry-charged unitized packages. The 20 ton model shall be shipped as separate eva po rator and condensing unit modules (nitrogen holdi ng charge only). All units may be field split and installed as separate mo ...

  • York D*V - page 8

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 10 TON B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 115. 4 91. 5 124. 8 73. 0 134. 5 53. 8 111. 0 89. 6 120. 2 71. 1 129. 8 52. 2 360 0 80° F 116. 6 109. 7 125. 8 90. 9 136. 1 72. 4 112. 6 107. 8 120. 9 89. 0 131. ...

  • York D*V - page 9

    March 2008 DIMENSIONAL DATA DPV096 & DPV120 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA5 (308) 4 of 4 DPV096 AND DPV120 DIMENSIONAL DA T A Page 9 ...

  • York D*V - page 10

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 150,000* Design CFM: 4,800 Energy Efficiency Ratio : 10.65 EER** Net Cooling Capacity [Btuh] : 144,000** Net Cooling CFM: 4,800 Refrigerant : R22 Charge : 12.13 Lbs./ circuit Compre ss or No./Type: 2/Scrol l Refrigerant Circuits : 2 / Independent Evaporator Coil Face Area: 13.03 [sq ...

  • York D*V - page 11

    DATE: DESCRIPTION: "DPV" SERIES VER TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS GENERAL All models 5-15 tons ship as facto ry-charged unitized packages. The 20 ton model shall be shipped as separate eva po rator and condensing unit modules (nitrogen holdi ng charge only). All units may be field split and installed as separate mo ...

  • York D*V - page 12

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 12 TON B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 140. 0 108. 7 151. 6 87. 4 167. 1 66. 6 135. 4 106. 7 146. 6 85. 3 160. 8 64. 5 430 0 80° F 145. 8 132. 3 152. 8 108. 0 168. 5 88. 6 139. 8 129. 4 147. 1 106. 0 1 ...

  • York D*V - page 13

    DPV144 DPV180 March 2008 DIMENSIONAL DATA DPV144 & DPV180 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA6 (308) 4 of 4 DPV0144 AND DPV180 DIMENSIONAL DA T A Page 13 ...

  • York D*V - page 14

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 186,000* Design CFM: 6,000 Energy Efficiency Ratio : 9.80 EER** Net Cooling Capacity [Btuh] : 178,000** Net Cooling CFM: 5,500 Refrigerant : R22 Charge : 13.83 Lbs./ circuit Compre ss or No./Type: 2/Scrol l Refrigerant Circuits : 2 / Independent Evaporator Coil Face Area: 13.03 [sq ...

  • York D*V - page 15

    DATE: DESCRIPTION: "DPV" SERIES VER TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS GENERAL All models 5-15 tons ship as facto ry-charged unitized packages. The 20 ton model shall be shipped as separate eva po rator and condensing unit modules (nitrogen holdi ng charge only). All units may be field split and installed as separate mo ...

  • York D*V - page 16

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 15 TON B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 175. 4 138. 5 189. 7 110. 0 207. 4 82. 9 168. 8 135. 5 182. 8 107. 8 200. 6 81. 8 540 0 80° F 177. 1 165. 8 191. 0 137. 5 209. 1 111. 5 171. 2 163. 1 184. 0 134. ...

  • York D*V - page 17

    DPV144 DPV180 March 2008 DIMENSIONAL DATA DPV144 & DPV180 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA7 (308) 4 of 4 DPV144 AND DPV180 DIMENSIONAL DA T A Page 17 ...

  • York D*V - page 18

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 244,000* Design CFM: 8,000 Energy Efficiency Ratio : 10.10 EER** Net Cooling Capacity [Btuh] : 236,000** Net Cooling CFM: 6,800 Refrigerant : R22 Charge : 18.35 Lbs./ circuit Compre ss or No./Type: 2/Scrol l Refrigerant Circuits : 2 / Independent Evaporator Coil Face Area: 19.00 [sq ...

  • York D*V - page 19

    DATE: DESCRIPTION: "DPV" SERIES VER TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS GENERAL All models 5-15 tons ship as facto ry-charged unitized packages. The 20 ton model shall be shipped as separate eva po rator and condensing unit modules (nitrogen holdi ng charge only). All units may be field split and installed as separate mo ...

  • York D*V - page 20

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 20 TON B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 230. 3 184. 1 248. 7 146. 4 269. 3 108. 2 221. 9 180. 3 239. 8 142. 7 258. 3 104. 3 720 0 80° F 233. 3 221. 4 250. 2 182. 6 270. 6 146. 3 223. 9 216. 6 241. 0 178 ...

  • York D*V - page 21

    March 2008 DIMENSIONAL DATA DPV240 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA8 (308) 4 of 4 DPV240 DIMENSIONAL DA T A Page 21 ...

  • York D*V - page 22

    DESCRIPTION: PROJECT: TAG: DATE: Gross Cooling Ca pa city [Btuh] : 304,000* Design CFM: 10,000 Energy Efficiency Ratio : 9.60 EER** Net Cooling Capacity [Btuh] : 286,000** Net Cooling CFM: 8,800 Refrigerant : R22 Charge : 14.65 Lbs./ circuit Compre ss or No./Type: 3/Scrol l Refrigerant Circuits : 3 / Independent Evaporator Coil Face Area: 19.797 [s ...

  • York D*V - page 23

    DATE: DESCRIPTION: "DPV" SERIES VER Johnson Controls maintains a continuous product improvement policy, t he refore specifications are subject to change without noti ce. March 2008 MECHANICAL SPECIFICATIONS DPV300 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA9 (308) 2 of 4 TICAL INDOOR SYSTEM GENERAL MECHANICAL SPECIFICATIONS G ...

  • York D*V - page 24

    DATE: DESCRIPTION: Am bient Condense r Air Tempe r atu re F ° 5 9 F ° 5 8 25 TON B W E B W E 62° F 67° F 72° F 62° F 67°F 72° F CFM EDB TC SC TC SC TC SC TC SC TC SC TC SC 75° F 285. 6 225. 4 308. 9 180. 1 339. 4 136. 0 275. 0 220. 8 297. 5 175. 4 325. 1 133. 6 900 0 80° F 291. 7 271. 6 311. 4 224. 0 342. 3 182. 2 281. 0 267. 2 299. 6 219 ...

  • York D*V - page 25

    March 2008 DIMENSIONAL DATA DPV300 VERTICAL UNIT AIR-COOLED SELF-CONTAINED Form YK145.12-PA9 (308) 4 of 4 DPV300 DIMENSIONAL DA T A Page 25 ...

メーカー York カテゴリー Air Conditioner

York D*Vのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- D*Vの取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork D*Vの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York D*Vの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York D*Vの取り付け説明書、サービスマニュアル、簡易説明書、またはYork D*Vのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York D*Vの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York D*Vデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork D*Vを使用するのを助ける技術的文書のことです。説明書は通常、全てのYork D*Vユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York D*Vの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork D*Vの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York D*Vに関してこのドキュメントで見つけることができる全てのヒントの目次
3. York D*Vデバイスの基本機能を使うにあたってのヒント。 York D*Vのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York D*Vに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork D*Vのメーカー/サービスへの連絡先に関する情報。

York D*Vについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork D*Vの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork D*Vで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)