    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 12 SEER MODELS: H*RC018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PH) H*RC036S(25,4 6) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) Due to continuous prod uct improvement, specific ations are subject to change without notice. Visit u s on the web at www .york.com for the most up-to-date techni cal information . A ...

  • York H*RC018 THRU 060 - page 2

    036-21137-004 Rev. C (0505) 2 Unitary Products Group Physical and Electrical Dat a - 1 Phase MODEL H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC 042S06 H2RC048S06 H4RC060S06 Unit Supply V oltage 208/230 – 1 – 60 Normal V oltage Range 187 to 252 Minimum Circuit Ampacity 1 10.1 14.1 16.5 19.7 26.2 28.5 37.5 Max. Overcurrent Device Amps 2 15 25 ...

  • York H*RC018 THRU 060 - page 3

    036-21137-004 Rev. C (0505) Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems - 1 Phase Outdoor Unit H2RC018S06 H2RC024S06 H2RC030S06 H 2RC036S06 H2RC042S06 H2R C048S06 H4RC060S06 Unit Orifice (s ) 1 53 59 63 73 78 87 – Factory R-22 Charge, lbs-oz. 4 - 9 4 - 7 5 - 8 5 - 3 6 - 13 7 - 7 8 - 15 Indoor Coil 5 ...

  • York H*RC018 THRU 060 - page 4

    036-21137-004 Rev. C (0505) 4 Unitary Products Group PROCEDURES: 1. Unit factory charge list ed on the uni t n ameplate includes ref rig erant for th e cond enser , the smallest evaporator and fo r 15 f eet of interconnecting line tubing. 2. V erify the orif ice size and additional charge required for s pecific evaporator coil in t he system using ...

  • York H*RC018 THRU 060 - page 5

    036-21137-004 Rev. C (0505) Unitary Products Group 5 PROCEDURES: 1. Unit factory charge list ed on the uni t nameplate includes ref rig erant for th e condenser , the smallest evaporator and for 15 f eet of interconnecting l ine tubing. 2. V erify the orifice size and additi onal char ge required for sp ecific evaporator coil in the system using th ...

  • York H*RC018 THRU 060 - page 6

    036-21137-004 Rev. C (0505) 6 Unitary Products Group - = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 1 PH 12 SEER AC WITH N1AH / G2FD H2RC018S06 N1AHB0806 2,5,8,10 17 G2FD024(S, H)17 600 19.6 13.2 1 ...

  • York H*RC018 THRU 060 - page 7

    036-21137-004 Rev. C (0505) Unitary Products Group 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) WR A T E D C F M NET MBH SEER W/O TXV SEER + TXV 1 EER TOT AL SENS. H2RC018S06 525 675 14,17 G1F A024S14,17 600 19.2 13.0 12.00* 12.00 1 1.35 14 G1HA024H14 600 ...

  • York H*RC018 THRU 060 - page 8

    036-21137-004 Rev. C (0505) 8 Unitary Products Group H2RC036S06 1050 1350 14 G1F A036S14 1200 33.6 23 .4 1 1.50* 1 1.50 10.60 17,21 G1F A036S17,21 1200 33.0 23.0 1 1.25 * 1 1.25 10.45 17 G1F A048S17 1200 35.0 24 .4 12.00* 12.00 10.90 21 G1F A048S21 1200 34.0 25 .2 12.00* 12.00 10.70 14 G1HA036H14 1 150 33.5 23 .8 12.00* – 10.75 14 G1HA036H14 1 15 ...

  • York H*RC018 THRU 060 - page 9

    036-21137-004 Rev. C (0505) Unitary Products Group 9 *Requires 2FD Blower T ime Delay unless a st andard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace mat ch-up. H2RC048S06 1375 1775 17 G1F A048S17 1575 45.5 34.1 12.00* 12 .00 1 1.00 21 G1F A048S21 1575 46.5 34.9 12.00* 12 .00 1 1.00 21,24 G1F A060S21,24 1575 ...

  • York H*RC018 THRU 060 - page 10

    036-21137-004 Rev. C (0505) 10 Unitary Products Group COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER W/O TXV SEER + TXV 2 EER TOT AL SENS. 1 PH 12 SEER AC - V ARIABLE SPEED 3 H2RC018S06 P1DUA12V/PV8A12****UH G1F A024 S14 14 600 19.6 13.4 – 13.00 12.55 P1DU ...

  • York H*RC018 THRU 060 - page 11

    036-21137-004 Rev. C (0505) Unitary Products Group 11 H2RC048S06 P1DUC20V/PV8C20****UH G1F A048S21 21 1 610 46.5 34.9 – 12.10 1 1.15 P1DUC20V/PV8C20****UH G2FD048(S,H)21 21 1610 46.5 34.9 – 12.25 1 1.05 P1XDD20V G2FD048(S,H)24 24 1610 47.0 35.4 – 12.40 1 1.00 P1XUC16V G1F A048S21 21 1480 46.0 34.4 – 12.10 10.90 P1XUC16V G2FD048(S,H)21 21 14 ...

  • York H*RC018 THRU 060 - page 12

    036-21137-004 Rev. C (0505) 12 Unitary Products Group All dimensions are in inches. T hey are subject to change without notice. Certified dimensi ons will be provided upon request. ACCESSORIES* Refer to Price Manual for specific model numbers. Hard St art Kit - Provides increased starting torque for areas with low voltage. Compressor Blanket - Desi ...

  • York H*RC018 THRU 060 - page 13

    036-21137-004 Rev. C (0505) Unitary Products Group 13 TYPICAL INST ALLA TION TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE 60” OVERHEAD CLEARANCE 10” CLEARANCE COIL AREA WEA THERPROOF DISCONNECT SWITCH THERMOST A T TO FURNACE OR AIR HANDLER TERMINAL BLOCK ...

  • York H*RC018 THRU 060 - page 14

    036-21137-004 Rev. C (0505) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 15

    036-21137-004 Rev. C (0505) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 16

    036-21137-004 Rev. C (0505) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 17

    036-21137-004 Rev. C (0505) Unitary Products Group 17 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 18

    036-21137-004 Rev. C (0505) 18 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 19

    036-21137-004 Rev. C (0505) Unitary Products Group 19 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 20

    036-21137-004 Rev. C (0505) 20 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 21

    036-21137-004 Rev. C (0505) Unitary Products Group 21 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 22

    036-21137-004 Rev. C (0505) 22 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 23

    036-21137-004 Rev. C (0505) Unitary Products Group 23 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 24

    Subject to change without notice. Printe d in U.S.A. 036-21137-004 Rev. C (0505) Copyright © by Y ork International Corp. 2005. All rights reserved. Supersedes: 036-21137-004 Rev. B (0105) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW ...

メーカー York カテゴリー Air Conditioner

York H*RC018 THRU 060のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- H*RC018 THRU 060の取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork H*RC018 THRU 060の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York H*RC018 THRU 060の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York H*RC018 THRU 060の取り付け説明書、サービスマニュアル、簡易説明書、またはYork H*RC018 THRU 060のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York H*RC018 THRU 060の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York H*RC018 THRU 060デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork H*RC018 THRU 060を使用するのを助ける技術的文書のことです。説明書は通常、全てのYork H*RC018 THRU 060ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York H*RC018 THRU 060の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork H*RC018 THRU 060の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York H*RC018 THRU 060に関してこのドキュメントで見つけることができる全てのヒントの目次
3. York H*RC018 THRU 060デバイスの基本機能を使うにあたってのヒント。 York H*RC018 THRU 060のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York H*RC018 THRU 060に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork H*RC018 THRU 060のメーカー/サービスへの連絡先に関する情報。

York H*RC018 THRU 060についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork H*RC018 THRU 060の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork H*RC018 THRU 060で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)