    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 12 SEER MODELS: H*RC018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PH) H*RC036S(25,4 6) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) Due to continuous prod uct improvement, specific ations are subject to change without notice. Visit u s on the web at www .york.com for the most up-to-date techni cal information . A ...

  • York H*RC018 THRU 060 - page 2

    036-21137-004 Rev. C (0505) 2 Unitary Products Group Physical and Electrical Dat a - 1 Phase MODEL H2RC018S06 H2RC024S06 H2RC030S06 H2RC036S06 H2RC 042S06 H2RC048S06 H4RC060S06 Unit Supply V oltage 208/230 – 1 – 60 Normal V oltage Range 187 to 252 Minimum Circuit Ampacity 1 10.1 14.1 16.5 19.7 26.2 28.5 37.5 Max. Overcurrent Device Amps 2 15 25 ...

  • York H*RC018 THRU 060 - page 3

    036-21137-004 Rev. C (0505) Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Systems - 1 Phase Outdoor Unit H2RC018S06 H2RC024S06 H2RC030S06 H 2RC036S06 H2RC042S06 H2R C048S06 H4RC060S06 Unit Orifice (s ) 1 53 59 63 73 78 87 – Factory R-22 Charge, lbs-oz. 4 - 9 4 - 7 5 - 8 5 - 3 6 - 13 7 - 7 8 - 15 Indoor Coil 5 ...

  • York H*RC018 THRU 060 - page 4

    036-21137-004 Rev. C (0505) 4 Unitary Products Group PROCEDURES: 1. Unit factory charge list ed on the uni t n ameplate includes ref rig erant for th e cond enser , the smallest evaporator and fo r 15 f eet of interconnecting line tubing. 2. V erify the orif ice size and additional charge required for s pecific evaporator coil in t he system using ...

  • York H*RC018 THRU 060 - page 5

    036-21137-004 Rev. C (0505) Unitary Products Group 5 PROCEDURES: 1. Unit factory charge list ed on the uni t nameplate includes ref rig erant for th e condenser , the smallest evaporator and for 15 f eet of interconnecting l ine tubing. 2. V erify the orifice size and additi onal char ge required for sp ecific evaporator coil in the system using th ...

  • York H*RC018 THRU 060 - page 6

    036-21137-004 Rev. C (0505) 6 Unitary Products Group - = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 1 PH 12 SEER AC WITH N1AH / G2FD H2RC018S06 N1AHB0806 2,5,8,10 17 G2FD024(S, H)17 600 19.6 13.2 1 ...

  • York H*RC018 THRU 060 - page 7

    036-21137-004 Rev. C (0505) Unitary Products Group 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) WR A T E D C F M NET MBH SEER W/O TXV SEER + TXV 1 EER TOT AL SENS. H2RC018S06 525 675 14,17 G1F A024S14,17 600 19.2 13.0 12.00* 12.00 1 1.35 14 G1HA024H14 600 ...

  • York H*RC018 THRU 060 - page 8

    036-21137-004 Rev. C (0505) 8 Unitary Products Group H2RC036S06 1050 1350 14 G1F A036S14 1200 33.6 23 .4 1 1.50* 1 1.50 10.60 17,21 G1F A036S17,21 1200 33.0 23.0 1 1.25 * 1 1.25 10.45 17 G1F A048S17 1200 35.0 24 .4 12.00* 12.00 10.90 21 G1F A048S21 1200 34.0 25 .2 12.00* 12.00 10.70 14 G1HA036H14 1 150 33.5 23 .8 12.00* – 10.75 14 G1HA036H14 1 15 ...

  • York H*RC018 THRU 060 - page 9

    036-21137-004 Rev. C (0505) Unitary Products Group 9 *Requires 2FD Blower T ime Delay unless a st andard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace mat ch-up. H2RC048S06 1375 1775 17 G1F A048S17 1575 45.5 34.1 12.00* 12 .00 1 1.00 21 G1F A048S21 1575 46.5 34.9 12.00* 12 .00 1 1.00 21,24 G1F A060S21,24 1575 ...

  • York H*RC018 THRU 060 - page 10

    036-21137-004 Rev. C (0505) 10 Unitary Products Group COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER W/O TXV SEER + TXV 2 EER TOT AL SENS. 1 PH 12 SEER AC - V ARIABLE SPEED 3 H2RC018S06 P1DUA12V/PV8A12****UH G1F A024 S14 14 600 19.6 13.4 – 13.00 12.55 P1DU ...

  • York H*RC018 THRU 060 - page 11

    036-21137-004 Rev. C (0505) Unitary Products Group 11 H2RC048S06 P1DUC20V/PV8C20****UH G1F A048S21 21 1 610 46.5 34.9 – 12.10 1 1.15 P1DUC20V/PV8C20****UH G2FD048(S,H)21 21 1610 46.5 34.9 – 12.25 1 1.05 P1XDD20V G2FD048(S,H)24 24 1610 47.0 35.4 – 12.40 1 1.00 P1XUC16V G1F A048S21 21 1480 46.0 34.4 – 12.10 10.90 P1XUC16V G2FD048(S,H)21 21 14 ...

  • York H*RC018 THRU 060 - page 12

    036-21137-004 Rev. C (0505) 12 Unitary Products Group All dimensions are in inches. T hey are subject to change without notice. Certified dimensi ons will be provided upon request. ACCESSORIES* Refer to Price Manual for specific model numbers. Hard St art Kit - Provides increased starting torque for areas with low voltage. Compressor Blanket - Desi ...

  • York H*RC018 THRU 060 - page 13

    036-21137-004 Rev. C (0505) Unitary Products Group 13 TYPICAL INST ALLA TION TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application MINIMUM 18” SERVICE ACCESS CLEARANCE ON ONE SIDE 60” OVERHEAD CLEARANCE 10” CLEARANCE COIL AREA WEA THERPROOF DISCONNECT SWITCH THERMOST A T TO FURNACE OR AIR HANDLER TERMINAL BLOCK ...

  • York H*RC018 THRU 060 - page 14

    036-21137-004 Rev. C (0505) 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 15

    036-21137-004 Rev. C (0505) Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 16

    036-21137-004 Rev. C (0505) 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 17

    036-21137-004 Rev. C (0505) Unitary Products Group 17 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 18

    036-21137-004 Rev. C (0505) 18 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 19

    036-21137-004 Rev. C (0505) Unitary Products Group 19 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 20

    036-21137-004 Rev. C (0505) 20 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 21

    036-21137-004 Rev. C (0505) Unitary Products Group 21 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 22

    036-21137-004 Rev. C (0505) 22 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per degree abo ve the listed temperature and decre ases by 1060 BTUH per 1000 CFM per ...

  • York H*RC018 THRU 060 - page 23

    036-21137-004 Rev. C (0505) Unitary Products Group 23 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per ...

  • York H*RC018 THRU 060 - page 24

    Subject to change without notice. Printe d in U.S.A. 036-21137-004 Rev. C (0505) Copyright © by Y ork International Corp. 2005. All rights reserved. Supersedes: 036-21137-004 Rev. B (0105) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York H*RC018 THRU 060 can be divided into several groups. They are, among others:
- York technical drawings
- H*RC018 THRU 060 manuals
- York product data sheets
- information booklets
- or energy labels York H*RC018 THRU 060
All of them are important, but the most important information from the point of view of use of the device are in the user manual York H*RC018 THRU 060.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York H*RC018 THRU 060, service manual, brief instructions and user manuals York H*RC018 THRU 060. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York H*RC018 THRU 060.

Similar manuals

A complete manual for the device York H*RC018 THRU 060, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York H*RC018 THRU 060 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York H*RC018 THRU 060.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York H*RC018 THRU 060 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York H*RC018 THRU 060, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York H*RC018 THRU 060, that we can find in the current document
3. Tips how to use the basic functions of the device York H*RC018 THRU 060 - which should help us in our first steps of using York H*RC018 THRU 060
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York H*RC018 THRU 060
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York H*RC018 THRU 060 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York H*RC018 THRU 060?

Use the form below

If you did not solve your problem by using a manual York H*RC018 THRU 060, ask a question using the form below. If a user had a similar problem with York H*RC018 THRU 060 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)