Summary
  • Lennox International Inc. 505 - page 1

    02/06 505,021M *2P0206* *P505021M* E 2006 Lennox Industries Inc. Dallas, T exas, USA Humiditrol ® EDA Series Unit The Dave Lennox Signature t Collection Humiditrol ® En- hanced Dehumidification Accessory (EDA) is designed for installation with a Lennox R−410A split−system out door unit an d an air handler or a furnace with a variable speed bl ...

  • Lennox International Inc. 505 - page 2

    Page 2 EDA 01/06 W ARNING This cased product contains fiberglass wool. Dis- turbing the insulation during inst allation, mainte- nance, or rep air will expose you to fiberglass wool dust. Breathing this may cause lung cancer . (Fiber- glass wool is known to the St ate of California to cause cancer .) Fiberglass wool may also cause respiratory , ski ...

  • Lennox International Inc. 505 - page 3

    Page 3 EDA INST ALLA TION/ SERVICE INSTRUCTIONS Installation Dimensions and Arrangement Figure 1 AIR FLOW AIR FLOW UP-FLOW FURNACE UP-FLOW AIR HANDLER EDA−024B: 12−1/2 EDA−036C: 12−1/2 EDA−060D: 14 V aries by indoor coil model; see LENNOX Engineering Handbook. V aries by air handler model; see LENNOX Engineering Handbook for dimensions. 4 ...

  • Lennox International Inc. 505 - page 4

    Page 4 EDA 01/06 Component Functions Charge Compensator The charge compensator (shown i n figure 5) serves to maintain the proper amount of refrigerant circulating in larger systems. [Some systems do not require a charge compensator , but do require a simi- lar kit to connect into the system (see Engineering Hand- book)] The charge compensator s ...

  • Lennox International Inc. 505 - page 5

    Page 5 EDA INST ALLA TION/ SERVICE INSTRUCTIONS General Installation Information W ARNING Improper installation, adjustment, alteration, ser- vice or maintenance can cause personal injury , loss of life, or damage to property . Installation and service must be performed by a qualified installer or service agency . The EDA unit may be used in upflow ...

  • Lennox International Inc. 505 - page 6

    Page 6 EDA 01/06 Required Part s (all applications) EDA Unit, with check/flow restrictor & label Appropriate SignatureS t at t Thermostat 46M98 − Outdoor Sensor 84X49 − T wisted Pair Wire Appropriate Insulation and Piping Kit Required Part s (2−St age Heat Pump appl.) 12P61 − 75V A T ransformer (for HP applications) Installation Process ...

  • Lennox International Inc. 505 - page 7

    Page 7 EDA INST ALLA TION/ SERVICE INSTRUCTIONS INDOOR UNIT OUTDOOR UNIT air−flow V apor Line Liquid Line Liquid Line from Outdoor Unit Liquid Line to Indoor TXV TXV V apor Line Liquid Line MUST BE INSULA T ED MUST BE INSULA TED EDA CHARGE COMPENSA TOR 7/8 X 7/8 X 3/8 TEE UPFLOW POSITION Electrical Inlet T o Charge Compensator side connection (so ...

  • Lennox International Inc. 505 - page 8

    Page 8 EDA 01/06 Leak T esting, Evacuating, Charging IMPORT ANT The 3−way diverting valve actuator shaft set screw (see f i gure 7) is factory set and is not to be adjusted. 3−way Diverting V alve Operation NOTE − During system operation, the 3-way valve requires 24-volt power to drive between cooling and dehumidifica- tion. Th e 3−way dive ...

  • Lennox International Inc. 505 - page 9

    Page 9 EDA INST ALLA TION/ SERVICE INSTRUCTIONS Insulating and Sealing the Unit IMPORT ANT All piping, metering devices, and connections must be insulated to prevent moisture damage caused by sweating. Seal the unit so that warm air is not allowed into the cabi- net. This is especially import ant when the unit is inst alled in an unconditioned area ...

  • Lennox International Inc. 505 - page 10

    Page 10 EDA 01/06 EDA Unit Operation Th e EDA coil is added to an HV A C system downstream of th e indoor coil. In dehumidification mode, the coil becomes an extension of the condenser coil and injects heat into the indoor air stream. This dehumidification mode allows significantly improved control of the humidity in the conditioned space without o ...

  • Lennox International Inc. 505 - page 11

    Page 1 1 EDA INST ALLA TION/ SERVICE INSTRUCTIONS Cooling Mode (Dehumidification OFF) Figure 10 illustrates refrigerant flow in cooling mode (dehu- midification mode OFF), The liquid refrigerant from the outdoor unit enters the EDA module . Since there is no demand for dehumidification, the 3−way diverting valve assembly directs the flow back out ...

  • Lennox International Inc. 505 - page 12

    Page 12 EDA 01/06 Check List n Checkpoint What to Check Action Thermost at and Sensor Wiring Confirm Sensor connected to SignatureS tat t using twisted p air wire (see wiring diagram figure 13) Thermost at Humiditrol ® Installer Settings Confirm HUMIDITROL is enabled (see figure 8) Thermost at Humiditrol ® User Settings Confirm HUMIDITROL − Deh ...

  • Lennox International Inc. 505 - page 13

    Page 13 EDA INST ALLATION/ SERVICE INSTRUCTIONS Air Resist ance T able 2 shows air volume and tot al air resist ance for the available EDA models. T able 2 Air Resistance Air V olume T otal Air Resist ance Model No. cfm L/s in. w.g. Pa EDA−024B 400 190 0.05 12 600 285 0.10 25 800 380 0.15 37 1000 470 0.22 55 EDA−036C 600 285 0.05 12 800 380 0.0 ...

  • Lennox International Inc. 505 - page 14

    Page 14 EDA 01/06 Figure 12 T ypical EDA/Condensing Unit Wiring Diagram INDOOR UNIT B4 FA N Blue Y ellow Black K1 1st, cut yellow wire here. Use Wirenuts *OUTDOOR RELA Y  NOT REQUIRED WITH SINGLE- SPEED OUTDOOR FAN EDA Violet Orange OUTDOOR WIRING (VSM APPLICA TION ONL Y) Purple Black Black Purple VA LV E ACTUA TOR Y ellow Y ellow 2 2nd, rewire ...

  • Lennox International Inc. 505 - page 15

    Page 15 EDA INST ALLA TION/ SERVICE INSTRUCTIONS T ypical EDA/Heat Pump Wiring Diagram Figure 13 B4 FA N Blue Y ellow Black K1 1st, cu t yellow wire here. Use Wirenuts *OUTDOOR RELA Y  NOT REQUIRED WITH SINGLE- SPEED OUTDOOR FAN EDA Violet Orange Purple Black Black Purple VA LV E ACTUA TOR Y ellow Y ellow 2 2nd, rewire yellow wire as shown 7 5 1 ...

  • Lennox International Inc. 505 - page 16

    Page 16 EDA 01/06 Up flow/horizont al NOTE − AIR HANDLER REQUIRES FIELD−F ABRICA TED TRANSITION BETWEEN BLOWER OUTLET AND EDA COIL. [If furnace] Select indoor coil MUST BE TXV ONL Y Figure 14 Humiditrol ® Enhanced Dehumidification Accessory (EDA) Decision T ree Select EDA (REFER TO EDA ENGINEERING HANDBOOK) X = PREFERRED MA TCH−UP A = ALLOWE ...

メーカー Lennox International Inc. カテゴリー Dehumidifier

Lennox International Inc. 505のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 505の取扱説明書
- Lennox International Inc.の製品カード
- パンフレット
- またはLennox International Inc. 505の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Lennox International Inc. 505の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Lennox International Inc. 505の取り付け説明書、サービスマニュアル、簡易説明書、またはLennox International Inc. 505のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Lennox International Inc. 505の製品を使用するにあたって最も人気のある説明書を閲覧できます。

Lennox International Inc. 505デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLennox International Inc. 505を使用するのを助ける技術的文書のことです。説明書は通常、全てのLennox International Inc. 505ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Lennox International Inc.の取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Lennox International Inc. 505の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLennox International Inc. 505の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Lennox International Inc. 505に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Lennox International Inc. 505デバイスの基本機能を使うにあたってのヒント。 Lennox International Inc. 505のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Lennox International Inc. 505に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLennox International Inc. 505のメーカー/サービスへの連絡先に関する情報。

Lennox International Inc. 505についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもLennox International Inc. 505の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがLennox International Inc. 505で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)