    1 60-2285—7 R4795A Flame Safeguard Primary Contr ols The R4795A Protectorelay™ Primary Control provides solid state electronic flame safeguard protection for commercial and industrial gas or oil burn ers. It provides a prepurge period before each start, and intermittent pilot. ■ 120V models meet the requirements of Underwrit- ers Laboratories ...

  • Honeywell R4795A - page 2

    60-2285—7 2 R4795A SPECIFICATIONS • ORDERING INFORMATION Specif ications R4795A Flame Safeguard Primary Control recycles once after flame failure to try to re-establish pilot before lockout. Use with R7289A Amplifier and rectifying flame rod, recti- fying photocell, or C7012A,C Purple Peeper Ultraviolet Flame Detector; or with R7290A Amplifier ...

  • Honeywell R4795A - page 3

    3 60-2285—7 R4795A SPECIFICATIONS TERMINAL RATINGS: Terminal Load Rating 3 Pilot Valve 125 VA pilot duty. Intermittent Ignition a 360 VA. 4 Interrupted Ignition 360 VA. 5 Main Fuel Valve(s) 125 VA pilot duty, or 25 VA pilot duty plus one or more motorized valves with total rating up to 400 VA opening, 200 VA holding. 6-7 Airflow Switch 0.6A at 30 ...

  • Honeywell R4795A - page 4

    60-2285—7 4 R4795A INSTALLATION Installation Vibration Do not install the R4795A where it could be subject to excessive vibration. Vibration shortens the life of the elec- tronic and mechanical components. Weather The R4795A is not designed to be weathertight. If it is installed outdoors, use a suitable weathertight enclosure. Mounting The Subbas ...

  • Honeywell R4795A - page 5

    5 60-2285—7 R4795A INSTALLATION IMPORTANT: Do not run high voltage ignition trans- former wires in the same conduit with the flame detector wiring. 5. For ignition installations in a contaminating environ- ment, use Honeywell Specification no. R1239001 High Ten- sion Ignition Cable or equivalent. This wire is very resistant to severe conditions o ...

  • Honeywell R4795A - page 6

    60-2285—7 6 R4795A INSTALLATION Replacing RA890E,F,G with R4795A 1. Disconnect all wires from terminal 1, and splice with solderless connector. (If RA890 has no terminal 1 wiring, disregard this step.) 2. Remove line voltage controller wire from terminal 6 and connect to terminal 1. 3. Move burner motor connection from terminal 3 to ter- minal 6 ...

  • Honeywell R4795A - page 7

    7 60-2285—7 R4795A INSTALLATION Fig. 6—Flame detector wiring. M8686 BLUE WHITE F G C7027, C7035, OR C7044 ULTRAVIOLET FLAME DETECTOR BLUE YELLOW BLACK BLACK F G C7012 ULTRAVIOLET DETECTOR 1 G F X X X X X X FLAME ROD G F X X PHOTOCELL 1 C7027, C7035, AND C7044 FLAME DETECTOR LEADS ARE COLOR CODED BLUE AND WHITE. THE BLUE LEAD MUST BE CONNECTED T ...

  • Honeywell R4795A - page 8

    60-2285—7 8 R4795A CHECKOUT Check out Fig. 10—Internal view showing amplifier and test jack for flame current test. CA UTION Use extreme care while testing the R4795; line voltage can be present on most terminals when the power is On. CHECKOUT SUMMARY The following list summarizes the checkout tests re- quired for each type of installation. Ins ...

  • Honeywell R4795A - page 9

    9 60-2285—7 R4795A CHECKOUT 2. The flame current is at least two microamperes for R7289A Rectification Amplifier (color-coded green), or at least 1.5 microamperes for an R7290A Ultraviolet Amplifier (color-coded violet). IF A STEADY READING OF AT LEAST MINIMUM STRENGTH CANNOT BE OBTAINED, ONE OR MORE OF THE FOLLOWING CONDITIONS CAN EXIST: • Imp ...

  • Honeywell R4795A - page 10

    60-2285—7 10 R4795A CHECKOUT CA UTION Do not manually push in the relays. 4. Check that the pilot is lit and relay 2K is pulled in. 5. Open the manual main burner shutoff cock. Main flame should light within one second. If the burner does not light within one second, close the shutoff cock and shut off power to the relay. Proceed to step 7. 6. If ...

  • Honeywell R4795A - page 11

    11 60-2285—7 R4795A OPERATION • TROUBLESHOOTING Operation NORMAL OPERATION (REFER TO FIG. 2 AND 3.) Call for Heat (Limit Switch Closed) Terminal 1 energized. Relay 3K pulls in to close contact 3K2 and energize terminal 8 fan or burner motor. Airflow Proved Low voltage airflow switch between terminals 6 and 7 closes to energize the purge timer. ...

  • Honeywell R4795A - page 12

    60-2285—7 12 R4795A TROUBLESHOOTING F. Pilot lights and relay 2K pulls in but the main burner does not light. G. Relay 2K remains in after flame is extinguished. H. Miscellaneous problems: 1. Repeated lockouts or control failures. 2. Ignition interference (flame rod installations only). TROUBLESHOOTING PROCEDURES CA UTION 1. Use extreme care whil ...

  • Honeywell R4795A - page 13

    13 60-2285—7 R4795A TROUBLESHOOTING • SERVICE (3) Remove any flame simulating condition such as false light. (4) Note that any change made in the detector or its sighting requires a pilot turndown test. 3. If using an R7290 Ultraviolet Amplifier, replace the amplifier and recheck the flame relay dropout time. If the flame relay dropout timing i ...

  • Honeywell R4795A - page 14

    60-2285—7 14 R4795A SERVICE IMPORTANT: 1. Do not clean contacts unless absolutely necessary. 2. Use only Honeywell Contact Cleaner part no. 132569. Do not use any other type of contact cleaner. 3. Use extreme care to avoid bending the contacts or changing the specifications or configuration in any way. 4. Do not use an abrasive or a burnishing to ...

  • Honeywell R4795A - page 15

    15 60-2285—7 ...

  • Honeywell R4795A - page 16

    Home and Building Control Home and Building Control Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario M1P 2V9 Printed in United States www.honeywell.com/bbc ...

メーカー Honeywell カテゴリー Home Safety Product

Honeywell R4795Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- R4795Aの取扱説明書
- Honeywellの製品カード
- パンフレット
- またはHoneywell R4795Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Honeywell R4795Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Honeywell R4795Aの取り付け説明書、サービスマニュアル、簡易説明書、またはHoneywell R4795Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Honeywell R4795Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Honeywell R4795Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがHoneywell R4795Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのHoneywell R4795Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Honeywellの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Honeywell R4795Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははHoneywell R4795Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Honeywell R4795Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Honeywell R4795Aデバイスの基本機能を使うにあたってのヒント。 Honeywell R4795Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Honeywell R4795Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるHoneywell R4795Aのメーカー/サービスへの連絡先に関する情報。

Honeywell R4795Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもHoneywell R4795Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがHoneywell R4795Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)