    NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. Index Page SAFETY CONSIDERATIONS .....................................................1 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE ........................................................................1-2 IN ...

  • Bryant GAMA 331JAV - page 2

    2. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged. 3. After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricit ...

  • Bryant GAMA 331JAV - page 3

    CAUTION: Application of this furnace should be in- doors with special attention given to vent sizing and material, gas input rate, air temperature rise, and unit sizing. Improper installation or misapplication of the furnace can require excessive servicing or cause prema- ture component failure. Installation must conform to regulations of serving g ...

  • Bryant GAMA 331JAV - page 4

    I. LOCATION A. General CAUTION: DO NOT install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are followed. DO NOT use this furnace during construction when adhesives, sealers, and/or new carpets are being installed and curing. If the furnace is required during construction, use clean ou ...

  • Bryant GAMA 331JAV - page 5

    c. If furnace is installed to obtain return air is taken directly from hallway or space adjacent to furnace, all air for combustion must come from outdoors. 2. Air from outside the structure requires 1 of the following methods: a. If combustion air is taken from outdoors through 2 vertical ducts, the openings and ducts MUST have at least 1 sq in. o ...

  • Bryant GAMA 331JAV - page 6

    IV. FILTER ARRANGEMENT WARNING: Never operate unit without a filter or with filter access door removed. A failure to follow this warning could result in fire, personal injury, or death. The 2 factory-supplied filters are shipped in the blower compart- ment. After return-air duct has been connected to furnace, install filters in a V-formation inside ...

  • Bryant GAMA 331JAV - page 7

    WARNING: Use the proper length of pipes to avoid stress on gas control manifold. A failure to follow this warning could result in a gas leak causing fire, explosion, personal injury, or death. CAUTION: Use a backup wrench at furnace gas control when connecting gas pipe to furnace to avoid damaging gas controls or manifold. WARNING: Never purge a li ...

  • Bryant GAMA 331JAV - page 8

    Install accessible manual shutoff valve upstream of furnace gas controls and within 72 in. of furnace. A 1/8-in. NPT plugged tapping is provided on gas value for test gage connection. Installation of additional 1/8-in. NPT plugged tapping, accessible for test gage connection, installed immediately upstream of gas supply connection to furnace and do ...

  • Bryant GAMA 331JAV - page 9

    A terminal block (EAC-1 [hot] and EAC-2 [neutral]) is provided for EAC connection. (See Fig. 10.) The terminals are energized with 115v, 1-amp maximum during blower motor operation. 2. Humidifier (HUM) Screw terminals (HUM-1 and C OM ) are provided for 24-v humidifier connection. The terminals are energized with 24v, 0.5-amp maximum when the gas va ...

  • Bryant GAMA 331JAV - page 10

    The gas service pressure must not exceed 0.5 psig (14-in. wc), and be no less than 0.16 psig (4.5-in. wc). Thermostat wire connections at R and W/W1 are the minimum required for gas heating operation. W2 must be connected for 2-stage heating thermostats. C OM , Y/Y2, and G are required for cooling, heat pumps, and some clock thermostats. These must ...

  • Bryant GAMA 331JAV - page 11

    → Fig. 14—Unit Wiring Diagram A97508 LEGEND ALS1 AUXILIARY LI MIT SWITCH , OVERTEMP. MANUAL R ESET, SPST (N.C.) ALS2 AUXILIARY LI MIT SWITCH , OVERTEMP. AUTO RES ET, SPST ( N.C.) BHI / LOR BLOWER MOTOR SPEED CHANGE RELAY , SPDT BHT / CLR BLOWER MOTOR SPEED CHANGE RELAY , SPDT BLWM BLOWER MOTOR, 4 or 5 -S PEED, PERMANEN T-SPLIT-CA PACITOR BLWR B ...

  • Bryant GAMA 331JAV - page 12

    a. Inducer prepurge period—As inducer motor IDM comes up to low speed or high speed, the low-heat pressure switch contacts LPS (or LPS and HPS) close to begin a 15-sec prepurge period. b. Ignitor warm-up—At the end of prepurge period, hot surface ignitor HSI is energized for a 17-sec ignitor warm-up period. c. Trial-for-ignition sequence—When ...

  • Bryant GAMA 331JAV - page 13

    (3.) When thermostat is satisfied, R to G-and-Y cir- cuits are opened. The outdoor unit stops, and furnace blower motor BLWM continues operating on high-cool speed for an additional 90 sec. b. Two-Speed Cooling Outdoor Unit (See Fig. 12 for thermostat connections.) (1.) The thermostat closes R to G-and-Y1 circuits for low cooling or closes R to G-a ...

  • Bryant GAMA 331JAV - page 14

    b. When installed with a heat pump, furnace control CPU automatically holds blower off time to 22 sec during HSI ignitor on period. After 17 sec of HSI ignitor on period, a trial-for-ignition sequence occurs as described above for gas heating. After flame is proved and without blower on delay, blower motor BLWM then operates on high-gas-heat speed ...

  • Bryant GAMA 331JAV - page 15

    g. Turn high-heat adjusting screw (5/64 hex Allen wrench) counterclockwise (out) to decrease input rate or clock- wise (in) to increase rate. NOTE: DO NOT set high-heat manifold pressure less than 3.2-in. wc or more than 3.8-in. wc for natural gas. If manifold pressure is outside this range, change main burner orifices. h. When correct input is obt ...

  • Bryant GAMA 331JAV - page 16

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifold Pressure ...

  • Bryant GAMA 331JAV - page 17

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifol ...

  • Bryant GAMA 331JAV - page 18

    TABLE 9—MODEL 331JAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT Continued (TABULATED DATA BASED ON 21,000 BTUH HIGH HEAT/13,500 BTUH LOW HEAT PER BURNER, DERATED 4% FOR EACH 1000 FT ABOVE SEA LEVEL) ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.58 0.60 0.62 0.64 0.66 Orifice No. Manifol ...

  • Bryant GAMA 331JAV - page 19

    a. Place duct thermometers in return and supply ducts as near furnace as possible. Be sure thermometers do not see heat exchangers so that radiant heat will not affect thermometer readings. This is particularly important with straight-run ducts. b. When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to d ...

  • Bryant GAMA 331JAV - page 20

    17. The thermostat anticipator should NOT be in this circuit while measuring current. If thermostat has no subbase, thermostat MUST be disconnected from R and W/W1 wires during current measurement. Return SW-2 to final desired location after completing reading. See thermostat manufacturer’s instructions for adjusting heat anticipator and for vary ...

  • Bryant GAMA 331JAV - page 21

    —21— ...

  • Bryant GAMA 331JAV - page 22

    —22— ...

  • Bryant GAMA 331JAV - page 23

    A94328 SER VICE TRAINING P ackaged Service T raining prog rams are an e xcellent wa y to increase your knowledge of the equipment discussed in this man ual, including: • Unit F amiliarization • Maintenance • Installation Ov er view • Oper ating Sequence A large selection of product, theor y , and skills prog rams is av ailable , using popul ...

  • Bryant GAMA 331JAV - page 24

    © 2008 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 —24— Printed in U.S.A. 331j602 Catalog No. 5333-100 ...

メーカー Bryant カテゴリー Furnace

Bryant GAMA 331JAVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- GAMA 331JAVの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant GAMA 331JAVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant GAMA 331JAVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant GAMA 331JAVの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant GAMA 331JAVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant GAMA 331JAVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant GAMA 331JAVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant GAMA 331JAVを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant GAMA 331JAVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant GAMA 331JAVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant GAMA 331JAVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant GAMA 331JAVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant GAMA 331JAVデバイスの基本機能を使うにあたってのヒント。 Bryant GAMA 331JAVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant GAMA 331JAVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant GAMA 331JAVのメーカー/サービスへの連絡先に関する情報。

Bryant GAMA 331JAVについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant GAMA 331JAVの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant GAMA 331JAVで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)