    SIMA TIC 505 High Speed Counter and Encoder Module User Manual Order Number: PPX:505–81 13–2 Manual Assembly Number: 2586546–0019 Second Edition ...

  • Siemens SIMATIC 505 - page 2

    01/21/92 Copyright 1992 by Siemens Industrial Automation, Inc. All Rights Reserved — Printed in USA Reproduction, transmission or use of this document or contents is not permitted without express consent of Siemens Industrial Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or design, are re ...

  • Siemens SIMATIC 505 - page 3

     Contents iii Contents Chapter 1 Overview 1.1 Features 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Inputs 1–4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 Outputs 1–5 . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 4

    iv Contents Chapter 4 T roubleshooting 4.1 Checking the Operation of the Module 4-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 5 Applications 5.1 Sprayer Example 5-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 Description 5-2 . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 5

     Contents v List of Figur es 1-1 High Speed Counter Module 1-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Output 1-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 High Speed Counter LEDs 1-6 . . . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 6

    vi Contents List of T ables 1-1 Deter mining Count in Pulse Counter Mode 1-7 . . . . . . . . . . . . . . . . . . . . . . . . . B-1 Environmental Specifications B-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2 Electrical Specifications B-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 7

     Overview 1-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Chapter 1 Overview 1.1 Features 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Inputs 1-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 8

     1-2 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.1 Features The Series 505  High Speed Counter (HSC) module (PPX:505-7002) provides two independent high-speed counter channels. Each channel has the following features.  Four counter modes:  Pulse counter  Quadrature counter modes: 1X, 2X, ...

  • Siemens SIMATIC 505 - page 9

     Overview 1-3 Series 505 High Speed Counter and Encoder Module User ’ s Manual Base Plane Connector Printed Circuit Board Front Bezel Bezel Screw LEDs T erminal Block Bezel Screw Figure 1-1 High Speed Counter Module ...

  • Siemens SIMATIC 505 - page 10

     1-4 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.2 Inputs The HSC module has two independent channels. Each channel has four inputs.  Reset  Inhibit  T wo counter inputs Each input may be used as either sinking or sourcing (with external 5–24 VDC power supply). The input signals are connec ...

  • Siemens SIMATIC 505 - page 11

     Overview 1-5 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.3 Outputs Each channel has two open collector outputs capable of driving TTL level signals or sinking up to 0.4 Amps of current (at 40 _ C) from an external 24 VDC source and load. Y Output Output Return Output Circuit 0 P1 P2 65,535 Y1 Y2 Counter V alue Figure 1- ...

  • Siemens SIMATIC 505 - page 12

     1-6 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.4 LED Indicators Each channel contains four LED indicators which provide a visual indication of the channel’ s status as shown in Figure 1-3. Figure 1-3 High Speed Counter LEDs A T urns on when there is current flow through the A input. B T urns on w ...

  • Siemens SIMATIC 505 - page 13

     Overview 1-7 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.5 Counting Modes 1.5.1 Pulse Counter Each channel has two inputs, A and B. In the pulse counter mode, counting Mode occurs on the rising or falling edge of the incoming pulses. The relationship of the states of these two inputs determines the direction of the coun ...

  • Siemens SIMATIC 505 - page 14

    Overview 1-8 Series 505 High Speed Counter and Encoder Module User ’ s Manual Counting Modes (continued) 1.5.2 Quadrature Mode For quadrature mode, each channel counts according to rising and/or  falling edges. T ypical devices for quadrature inputs are optical encoders. Different quadrature modes are selected based on the ...

  • Siemens SIMATIC 505 - page 15

     Overview 1-9 Series 505 High Speed Counter and Encoder Module User ’ s Manual 1.5.4 2X Quadratur e If input A leads input B, the module counts up on both the rising and falling edges of input A. If input B leads input A, the module counts down on the rising and falling edges of input A. Figure 1-6 illustrates the relationship between inputs A ...

  • Siemens SIMATIC 505 - page 16

    Overview 1-10 Series 505 High Speed Counter and Encoder Module User ’ s Manual Counting Modes (continued) 1.5.5 4X Quadratur e If input A leads input B, the module counts up on rising and falling edges of both input A and input B. If input B leads input A, the module counts down on the rising and falling edges of input A and input B. Figure 1-7 s ...

  • Siemens SIMATIC 505 - page 17

     Installation 2-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Chapter 2 Installation 2.1 Before Installing the Module 2–2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.1 Visual Inspection 2-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.2 ...

  • Siemens SIMATIC 505 - page 18

    2-2 Installation Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.1 Before Installing the Module 2.1.1 Visual Inspection If there is any visible damage to the module, contact your Siemens Industrial Automation, Inc. distributor for replacement. 2.1.2 Additional Refer to the manuals listed below for instructions on installing, Re ...

  • Siemens SIMATIC 505 - page 19

     Installation 2-3 Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.1.4 General W iring The count, inhibit, and unfiltered reset inputs are high-speed inputs which Considerations may respond to noise present on the lines. T o avoid problems, follow these guidelines when installing the HSC module. D Use the shortest possible wi ...

  • Siemens SIMATIC 505 - page 20

    2-4 Installation Series 505 High Speed Counter and Encoder Module User ’ s Manual Before Installing the Module (continued) 2.1.5 Hierar chy of Figure 2-1 provides a simple flowchart of the installation process. Installation Insert the Module Connect W ires Set Jumper Configuration on Module Power Up Log into Controller Figure 2-1 Hierar chy of In ...

  • Siemens SIMATIC 505 - page 21

     Installation 2-5 Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.2 Selecting Counter Operation 2.2.1 Selecting The HSC module has two channels. Y ou can configure each channel Counter Mode to operate in any of four counter modes. Prior to installing the module into the I/O backplane, configure the module by setting the jump ...

  • Siemens SIMATIC 505 - page 22

    2-6 Installation Series 505 High Speed Counter and Encoder Module User ’ s Manual Selecting Counter Operation (continued) 2.2.2 Selecting the Some applications require faster response on the reset input line than Reset Filter the standard 3.75-ms filter allows. For faster response, select the optional 0.95-ms filter . (The 0.9-ms filter is more s ...

  • Siemens SIMATIC 505 - page 23

    Installation 2-7 Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.3 Inserting the Module in the I/O Base The HSC is a single-wide module. Insert it into any available slot on any Series 505 I/O base. Do not touch the printed circuit board while inserting the module. This could cause electrostatic damage to the components on the ...

  • Siemens SIMATIC 505 - page 24

    2-8 Installation Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.4 Wiring the Module 2.4.1 Wiring the W iring the module consists of wiring the the input and output signals. Te r minal Block See Figure 2-4 and Figure 2-5 for general guidelines. All connections are made at the module terminal block. See Figure 2-5. Output return ...

  • Siemens SIMATIC 505 - page 25

     Installation 2-9 Series 505 High Speed Counter and Encoder Module User ’ s Manual Ch1 A+ Ch1 B+ Ch1 RST+ Ch1 INH+ 5–24 VDC Ch2 A+ Ch2 B+ Ch2 RST+ Ch2 INH+ 5–24 VDC Sourcing Driver Ch2 INH– Ch2 RST– Ch2 B– Ch2 A– Ch2 Y2 Ch2 Y1 + – Ch1 Y2 Ch1 Y1 + – Sinking 5–24 VDC Ch1 A– Ch1 B– Ch1 RST– Ch1 INH– Driver Encoder 5–24 ...

  • Siemens SIMATIC 505 - page 26

    2-10 Installation Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.5 Logging the Module into the Controller 2.5.1 Updating the I/O After inserting the module into the base, update the I/O configuration Configuration in the controller . The module does not automatically onfigure itself. Definition A VPU or other programming devic ...

  • Siemens SIMATIC 505 - page 27

     Installation 2-11 Series 505 High Speed Counter and Encoder Module User ’ s Manual 2.5.3 Viewing the I/O Use SHOW to view the I/O Configuration Chart. If the HSC is Configuration installed in slot 1, for channel 1, base 00, the I/O chart will appear Chart as displayed in Figure 2-7. I/O CONFIGURA TION CHART FOR : CHANNEL 1, BASE 00 Slot 1 I/O ...

  • Siemens SIMATIC 505 - page 28

     Programming 3-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Chapter 3 Programming 3.1 Controller Input W ords 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.1.1 WX1 (Status W ord) 3-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 29

    Programming 3-2 Series 505 High Speed Counter and Encoder Module User ’ s Manual 3.1 Controller Input W ords The HSC module is configured as three word inputs (WX) and five word outputs (WY). It occupies eight words of the controller ’ s word image register . 3.1.1 WX1 (Status W ord) W ord 1 (WX) is the module’ s status word. Eight bits provi ...

  • Siemens SIMATIC 505 - page 30

     Programming 3-3 Series 505 High Speed Counter and Encoder Module User ’ s Manual Inhibit Status. Each channel has an Inhibit Status bit in the status word. If the channel’ s Inhibit field input is active or if its Inhibit Command bit is 1 (see Setup W ord, Section 3.1.3), this bit will be 1 and the counter will not count. Otherwise, this bi ...

  • Siemens SIMATIC 505 - page 31

    Programming 3-4 Series 505 High Speed Counter and Encoder Module User ’ s Manual Controller Input W ords (continued) Reset Command. Both channels have a Reset Command bit. A transition from 0 (off) to 1 (on) of the Reset Command acts as a one-shot (providing a momentary reset of the channel), setting the count to 0. Even though the bit remains 1, ...

  • Siemens SIMATIC 505 - page 32

     T roubleshooting 4-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Chapter 4 T roubleshooting Re-seat board Check jumper position and condition of jumper (metal insert intact) Symptom Probable Cause Corrective Action Input LED is not on and Output LED is not on Signal wire noise Module not configured in controller I/O confi ...

  • Siemens SIMATIC 505 - page 33

    4-2 T roubleshooting Series 505 High Speed Counter and Encoder Module User ’ s Manual 4.1 Checking the Operation of the Module To check the operation of the module, follow these steps.  Module outputs will turn on during this procedure. 1. Using a programming device, force all presets to 0. 2. Reset both counters through the reset ...

  • Siemens SIMATIC 505 - page 34

     Applications 5-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Chapter 5 Applications 5.1 Sprayer Example 5- 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.1.1 Description 5- 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Siemens SIMATIC 505 - page 35

    Applications 5-2 Series 505 High Speed Counter and Encoder Module User ’ s Manual 5.1 Sprayer Example 5.1.1 Description A reversible DC motor drives a paint sprayer up and down a vertical assembly . A quadrature encoder on the drive shaft senses the direction and relative position of the sprayer . Channel 1 of the HSC will be used to enable the s ...

  • Siemens SIMATIC 505 - page 36

     Applications 5-3 Series 505 High Speed Counter and Encoder Module User ’ s Manual 5.1.2 Solution Connect encoder signals A and B to inputs A and B of the HSC. See Figure 5–2. Limit switch 1 (sprayer home) drives channel 1 Reset. Channel 1 outputs 1 and 2 are wire ORed and drive the sprayer enable. Select 1X Quadrature mode for channel 1, se ...

  • Siemens SIMATIC 505 - page 37

    Applications 5-4 Series 505 High Speed Counter and Encoder Module User ’ s Manual Sprayer Example (continued) LDC1 A: N= WY4 0 BITS1 A: N= WY4 4 BITS2 A: N= WY4 2 C12 C1 MOVW1 A: N= V200 2 BITC23 A: N= WY4 2 C15 C14 B: WY5 CLEAR CHANNEL 1 SETUP WORD SETUP CHANNEL 1 OUTPUT 2 T O GO LOW AT PRESET SELECT COUNT INHIBIT ON CHANNEL 1 INHIBIT CHANNEL 1 ...

  • Siemens SIMATIC 505 - page 38

     Applications 5-5 Series 505 High Speed Counter and Encoder Module User ’ s Manual 5.2 Flow Rate Example 5.2.1 Description A flow meter outputs 200 pulses per gallon. The program requires calculation of flow rate in gallons per minute (GPM). 5.2.2 Solution Configure the HSC as WX9–WX1 1, WY12–WY16. Attach channel 1 to the flow meter . The ...

  • Siemens SIMATIC 505 - page 39

    Applications 5-6 Series 505 High Speed Counter and Encoder Module User ’ s Manual 5.3 T ank Filling Example 5.3.1 Description The HSC module measures the volume of liquid and control the filling valve. (See Figure 5-6.) A flow meter , generating 200 pulses per gallon, is connected to the HSC channel 2, input A. Output 2 controls the filling valve ...

  • Siemens SIMATIC 505 - page 40

     Applications 5-7 Series 505 High Speed Counter and Encoder Module User ’ s Manual C141 BITC1 A: WY4 N = 5 C140 X128 C140 C140 C256 C140 IS USED T O INITIA TE/TERMINA TE FILLING C1 C140 C1 : RESET HSC, LOAD INIT AL PRESETS Y20 LDC4 A: WY4 N = 0 MOVW1 A: V200 N = 2 B: WY7 BITS1 A: WY4 N = 5 C141 : CLEAR RESET BIT C1 Y20 C1 Y20 Y20 C140 : ENABLE ...

  • Siemens SIMATIC 505 - page 41

    Applications 5-8 Series 505 High Speed Counter and Encoder Module User ’ s Manual T ank Filling Example (continued) C51 C8 C51 C8 : AFTER 90,000 PULSES, SUBTRACT THE OVERCOUNTS FROM 10,000 AND LOAD THE REMAINING COUNT INT O PRESET 2. CTR2 P = 9 MOVW2 A: V201 N = 1 B: WY7 SUB2 C51 C8 Y20 C61 SUB1 C61 C51 : ACCUMULA TE THE OVERCOUNTS A: WX3 B: V200 ...

  • Siemens SIMATIC 505 - page 42

     T erminal Block W orksheet A-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Appendix A T er minal Block W orksheet ...

  • Siemens SIMATIC 505 - page 43

     Specifications B-1 Series 505 High Speed Counter and Encoder Module User ’ s Manual Appendix B Specifications B.1 Environmental Specifications B-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B.2 Electrical Specifications B-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B ...

  • Siemens SIMATIC 505 - page 44

    Specifications B-2 Series 505 High Speed Counter and Encoder Module User ’ s Manual B.1 Environmental Specifications T able B-1 Environmental Specifications Operating T emperature 0 _ to 60 _ C (32 _ to 140 _ F) Storage T emperature –40 _ to 70 _ C (–40 _ to 158 _ F) Relative Humidity 5% to 95% noncondensing Pollution Degree 2, IEC 664, 664A ...

  • Siemens SIMATIC 505 - page 45

     Specifications B-3 Series 505 High Speed Counter and Encoder Module User ’ s Manual B.2 Electrical Specifications T able B-2 Electrical Specifications Count Inputs Frequency (maximum) Duty Count Mode Quadrature Mode Cycle Freq. Freq. (w/ 15  max. phase error) 10% 10 Khz 4 Khz 20% 25 Khz 8 Khz 25% 30 Khz 10 Khz 30% 35 Khz 12 Khz 40% 50 Khz ...

  • Siemens SIMATIC 505 - page 46

    Specifications B-4 Series 505 High Speed Counter and Encoder Module User ’ s Manual Electrical Specifications (continued)  Count inputs are constant current type inputs. Reset and Inhibit Inputs: On voltage: to 28 VDC, Class 2 supply Current on: 2 to 40 mA Of f voltage: –1.5 to 1.5 VDC Current of f: 0 to 0.75 mA Reset delay ti ...

  • Siemens SIMATIC 505 - page 47

     Specifications B-5 Series 505 High Speed Counter and Encoder Module User ’ s Manual Outputs User voltage: 28 VDC max. . . . . . . . . . . . . . . . . . . . . . . . . . V oltage drop: 1.8 VDC max. @ 400 mA . . . . . . . . . . . . . . . 1.0 VDC max. @ 25 mA Leakage current: 500  A max. . . . . . . . . . . . . . Peak current: 500 mA for 1 ms ...

  • Siemens SIMATIC 505 - page 48

    Specifications B-6 Series 505 High Speed Counter and Encoder Module User ’ s Manual B.3 Additional Compliances In addition, the system complies with applicable requirements of V erband Deutscher Elektrotechniker (VDE) 0160: Electrical Equipment Series 505 products have been developed with consideration of the draft standard for programmable contr ...

  • Siemens SIMATIC 505 - page 49

    Customer Registration We would like to know what you think about our user manuals so that we can serve you better . How would you rate the quality of our manuals? Excellent Good Fair Poor Accuracy Organization Clarity Completeness Overall design Size Index Would you be interested in giving us more detailed comments about our manuals? Y es! Please s ...

  • Siemens SIMATIC 505 - page 50

    BUSINESS REPL Y MAIL FIRST CLASS PERMIT NO.3 JOHNSON CITY , TN FOLD FOLD POST AGE WILL BE P AID BY ADDRESSEE NO POST AGE NECESSARY IF MAILED IN THE UNITED ST A TES SIEMENS INDUSTRIAL AUTOMA TION, INC. 3000 BILL GARLAND RD. P .O. BOX 1255 JOHNSON CITY TN 37605–1255 A TTN: T echnical Communications M/S 3519 ...

  • Siemens SIMATIC 505 - page 51

     Index-1 Index A Assistance, 2-2 C Configuration selecting, 2-10 updating, 2-10 Configuring jumpers, 2-5 User Options, 2-10 Count input, 1-4 Count rate, 1-2 Counter mode, 1-7 D Double-count quadrature, 1-9 E Electrical specifications, B-3 Environmental specifications, B-2 F Features, 1-2 H Handling the HSC, 2-2 I I/O address, 2-10 configuration ...

  • Siemens SIMATIC 505 - page 52

    Index-2 Q Quadrature Mode, quadruple count, 1-10 Quadrature mode double-count, 1-9 single-count, 1-8 Quadruple count, quadrature mode, 1-10 R References, 2-2 Reset, 1-2, 1-4 S Single-count quadrature, 1-8 Static electricity , 2-2 T T erminal block, 2-8 wiring diagram, 2-9 worksheet, 2-8 U Using status words, 3-2 W W iring, 2-3, 2-8 considerations, ...

  • Siemens SIMATIC 505 - page 53

    SIMA TIC is a registered trademark of Siemens AG. Series 505 and TISOFT are trademarks of Siemens Industrial Automation, Inc. T exas Instruments and TI are registered trademarks of T exas Instruments Incorporated. TI505, TI525, TI535, and TI545 are trademarks of T exas Instruments Incorporated. UL is a registered trademark of Underwriters Laborator ...

メーカー Siemens カテゴリー Pet Fence

Siemens SIMATIC 505のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- SIMATIC 505の取扱説明書
- Siemensの製品カード
- パンフレット
- またはSiemens SIMATIC 505の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Siemens SIMATIC 505の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Siemens SIMATIC 505の取り付け説明書、サービスマニュアル、簡易説明書、またはSiemens SIMATIC 505のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Siemens SIMATIC 505の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Siemens SIMATIC 505デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSiemens SIMATIC 505を使用するのを助ける技術的文書のことです。説明書は通常、全てのSiemens SIMATIC 505ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Siemensの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Siemens SIMATIC 505の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSiemens SIMATIC 505の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Siemens SIMATIC 505に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Siemens SIMATIC 505デバイスの基本機能を使うにあたってのヒント。 Siemens SIMATIC 505のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Siemens SIMATIC 505に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるSiemens SIMATIC 505のメーカー/サービスへの連絡先に関する情報。

Siemens SIMATIC 505についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもSiemens SIMATIC 505の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがSiemens SIMATIC 505で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)