    CATALOG NO. 6100.61E Effective: 02-01-05 Replaces: 03-01-03 Part No. 240790 INST ALLA TION AND OPERA TING INSTRUCTIONS Models 105B Brass VERSA ABOVE GROUND POOL and SP A HEA TER WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death. — WHAT TO DO ...

  • Raypak Versa 105B - page 2

    ...

  • Raypak Versa 105B - page 3

    Contents 4 PART ONE - Owner's Operating Instructions 4 SECTION 1 / START-UP PROCEDURES 4 Before Start-Up 5 Lighting Instructions & Shut-Off Procedures (manually lighted pilot MV) 6 Operating Instructions & Shut-Off Procedures (automatically lighted pilot IID) 7 After Start-Up 7 SECTION 2 / CAUTION 7 SECTION 3 / MAINTENANCE & CARE P ...

  • Raypak Versa 105B - page 4

    P ART ONE - OWNER'S OPERA TING INSTRUCTIONS BEFORE START-UP BURNERS Clean main burners and air louvers of dust, lint and debris. Keep heater area clear and free from com- bustibles, flammable liquids and chemicals. Do not obstruct the flow of combustion and ventilating air. 4 WATER First thing, insure that system is filled with water and have ...

  • Raypak Versa 105B - page 5

    1. STOP! Read the safety information above. 2. Set the thermostat on the lowest setting. 3. Turn On/Off switch to the "Off" position. 4. Remove heater door panel. 5. Push in gas control knob slightly and turn clock- wise to "Off". NOTE: Knob cannot be turned from "Pilot" to "Off" unless knob is pushed in slig ...

  • Raypak Versa 105B - page 6

    TO TURN OFF GAS TO APPLIANCE 1. STOP! Read the safety information above. 2. Set the thermostat to the lowest setting. 3. Turn off all electric power to the appliance. 4. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. 5. Remove heater door panel. 6. Turn gas control kno ...

  • Raypak Versa 105B - page 7

    AFTER START-UP Feel the inlet and outlet pipes. Outlet pipe should be only slightly warmer than the inlet. It should not be hot. WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. VISUAL INSPECTION With the heater on, remove the door and make a visual check of the pilot and ...

  • Raypak Versa 105B - page 8

    COLD WEATHER OPERATION MODERATE CLIMATE: Heater operation can continue during short term cold spells. When temperatures are below freezing, flow (continuous pump operation) must be maintained. CAUTION: Do not use the heater to maintain water temperatures just above freezing or for freeze protec- tion. When heaters are used during freezing weather c ...

  • Raypak Versa 105B - page 9

    P ART 2 - INST ALLA TION / SERVICE INSTRUCTIONS SECTION 1 RECEIVING EQUIPMENT On receipt of your equipment it is suggested that you visually check for external damage to the carton. If the carton is damaged, a note should be made on the Bill of Lading when signing for equipment. Remove the heater from the carton and if it is damaged, report the dam ...

  • Raypak Versa 105B - page 10

    CLEARANCES ALL HEATERS For clearances from combustible surfaces, see chart below. Clearances from Combustible construction. Indoor Installation: Top* (Drafthood) - 30"; Vent - 6"; Back - 5"; Right Side - 6"; Left Side - 6"; Floor - 0. Outdoor Installation: Top* (Stackless Top) - unobstructed; Back - 5"; Sides - 6" ...

  • Raypak Versa 105B - page 11

    HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY) In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater is not in direct wind current. In areas of daily high winds, it may be necessary to replace the outdoor stackless top with a stack adapter in ...

  • Raypak Versa 105B - page 12

    VENTING CONNECTIONS VENT TERMINAL (Outdoor) STACKLESS TOP STEP 1: Remove the (4) screws which fasten jacket top to heater. STEP 2: Lower outdoor top onto unit lining up slots in outdoor top with screw holes in jacket top. STEP 3: Reinstall (4) screws to secure jacket top and outdoor top to unit. VENT TERMINAL (Outdoor) OUTDOOR STACK STEP 1 Line up ...

  • Raypak Versa 105B - page 13

    VENT PIPING WARNING: Indoor boilers require a draft hood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisoning. Vent piping the same size or larger than the draft hood outlet is recommended, however, when the total vent height is at least ten (10) ...

  • Raypak Versa 105B - page 14

    GAS SUPPLY CONNECTIONS Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve located outside the heater jacket. All gas piping should be tested after installation in accordance with local codes. CAUTION: The heater and its manual shut off valve must be disconnected from the gas supply during any pressure ...

  • Raypak Versa 105B - page 15

    PLUMBING FOR WATER CONNECTIONS LOCATION The VERSA heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows: 1. The inlet side of the filter is plumbed directly to the discharge side of the filter pum ...

  • Raypak Versa 105B - page 16

    EXTERNAL AUXILIARY BYPASS VALVE (Where required) An auxiliary bypass valve should be used when flow rates exceed 115 GPM (usually a high performance pump size larger than 2 HP will exceed this flow rate). This valve is required to complement the function of the automatic bypass valve, particularly when starting the heater in winter or early spring ...

  • Raypak Versa 105B - page 17

    ELECTRICAL WIRING NOTE: If it is necessary to replace any of the original wiring, it must be replaced with 105 °C wire or its equivalent, except all black wire must be replaced with 150 °C wire or its equivalent. MILLIVOLT SYSTEM The Millivolt System Residential Heater is equipped with a self-generating electrical system in which the electric cur ...

  • Raypak Versa 105B - page 18

    18 WIRING DIAGRAM MILLIVOLT UNITS Fig. #2353 WIRING DIAGRAM KEY Fig. # 8096 PINK CONNECTOR BLUE CONNECTOR * * If required by local code, install at this location. ...

  • Raypak Versa 105B - page 19

    WIRING DIAGRAM I.I.D. UNITS IGNITION DEVICE - HONEYWELL Fig. # 9250 19 ...

  • Raypak Versa 105B - page 20

    WIRING DIAGRAM IID UNITS IGNITION DEVICE - ROBERTSHAW Fig. # 9251 20 ...

  • Raypak Versa 105B - page 21

    SECTION 4 / SERVICING INSTRUCTIONS GENERAL LOCATION OF CONTROLS 21 CONTROLS/ADJUSTMENTS/ REPLACEMENTS TEMPERATURE CONTROLS The water temperature is controlled by the heater thermostat on the upper front panel of the heater. The control center contains an On/Off toggle switch and a thermostat. The switch functions as a means for turning the heater o ...

  • Raypak Versa 105B - page 22

    PRESSURE SWITCH ADJUSTMENT: 1. With pump and heater on, turn adjustment knob ( clockwise) until a click is heard from the gas valve. 2. Turn adjustment knob (counter clockwise) 1/4 turn. 3. Turn pump off and on several times. Heater should shut off immediately. If it does not, repeat steps above until proper adjustment is made. Adjustment Knob Fig. ...

  • Raypak Versa 105B - page 23

    BURNER DRAWER REMOVAL 1. Shut off main electrical power switch to heater. 2. Shut off gas upstream of heater. 3. Remove front door. 4. Disconnect gas line from gas valve. 5. Remove (2) screws that mount burner tray to unit. 6. Disconnect wires that terminate at gas valve. 7. Slide out burner tray. 8. Reverse above procedure to reinstall. GAS VALVE ...

  • Raypak Versa 105B - page 24

    TUBE CLEANING PROCEDURE Establish a regular inspection schedule, frequency depending on local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16" in thickness. The heater may be cleaned from the return header side, without breaking pipe connections. It is prefer- able, however, to remove ...

  • Raypak Versa 105B - page 25

    25 CONTROL IMMERSION WELL REPLACEMENT 1. Shut water off to heater and drain heat exchanger. 2. Remove jacket top panel. 3. Remove old control well with bushing and sleeve, with 7/8" wrench or socket. 4. Slip "o" ring gasket over control well and install in header. "O" Ring Gasket Well Assembly Fig. #8101.0 UNITHERM GOVERNOR ...

  • Raypak Versa 105B - page 26

    SECTION 5 / TROUBLE SHOOTING GUIDE IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not quali ...

  • Raypak Versa 105B - page 27

    If pilot burner remains lit. Jump across pressure switch terminals If main burner does not fire, remove jumper Check for adequate water flow from filter Replace pressure switch Jump across thermostat If main burner fires, remove jumper If main burner does NOT fire... Jump across each high limit and remove jumper Replace thermostat Replace high limi ...

  • Raypak Versa 105B - page 28

    ELECTRICAL (ELECTRONIC IGNITION IID) WARNING HIGH VOLTAGE For qualified Technicians ONLY NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater. Intermittent Pilot System TROUBLESHOOTING HONEYWELL S8600 NOTE: Before troubleshooting, familiarize yourself with t ...

  • Raypak Versa 105B - page 29

    SECTION 6/REPLACEMENT PARTS LIST NOTE: To supply the correct part it is important that you state the model number, serial number and type of gas when applicable. Any part returned for replacement under standard company warranties must be properly tagged with RAYPAK return parts tag, completely filled in with the heater serial number, model number, ...

  • Raypak Versa 105B - page 30

    30 ...

  • Raypak Versa 105B - page 31

    31 ...

  • Raypak Versa 105B - page 32

    32 ...

Manufacturer Raypak Category Swimming Pool Heater

Documents that we receive from a manufacturer of a Raypak Versa 105B can be divided into several groups. They are, among others:
- Raypak technical drawings
- Versa 105B manuals
- Raypak product data sheets
- information booklets
- or energy labels Raypak Versa 105B
All of them are important, but the most important information from the point of view of use of the device are in the user manual Raypak Versa 105B.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Raypak Versa 105B, service manual, brief instructions and user manuals Raypak Versa 105B. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Raypak Versa 105B.

Similar manuals

A complete manual for the device Raypak Versa 105B, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Raypak Versa 105B by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Raypak Versa 105B.

A complete Raypak manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Raypak Versa 105B - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Raypak Versa 105B, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Raypak Versa 105B, that we can find in the current document
3. Tips how to use the basic functions of the device Raypak Versa 105B - which should help us in our first steps of using Raypak Versa 105B
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Raypak Versa 105B
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Raypak Versa 105B in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Raypak Versa 105B?

Use the form below

If you did not solve your problem by using a manual Raypak Versa 105B, ask a question using the form below. If a user had a similar problem with Raypak Versa 105B it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)