Manual MGE UPS Systems 100

30 pages 0.72 mb
Download

Go to site of 30

Summary
  • MGE UPS Systems 100 - page 1

    34003602EN/AB - Page 1 Installation manual PowerServices TM T elPac www .mgeups.com MGE UPS SYSTEMS T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T - Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T - ...

  • MGE UPS Systems 100 - page 2

    Page 2 - 34003602EN/AB ...

  • MGE UPS Systems 100 - page 3

    34003602EN/AB - Page 3 Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. PowerServices TelPac has been designed with the utmost care. It comes in 2 versions: card (ref. 66096) or external (ref. 66097 or 66098). The card version can be installed by the customer or by an MGE UPS SYSTEMS After Sales ...

  • MGE UPS Systems 100 - page 4

    Page 4 - 34003602EN/AB Foreword EMC compatibility The PowerServices TelPac card and external versions comply with the following standards, on condition that they are installed and used in compliance with their intended use and manufacturer’s instructions: ◗ Safety standards for IT equipment: EN 60950/A11 (1998). ◗ EMC: EN 61000-6-2 (1999), EN ...

  • MGE UPS Systems 100 - page 5

    34003602EN/AB - Page 5 Foreword Modem compatibility and supported countries The modem integrated in the PowerServices TelPac card is compatible with European standard CTR21 (01.98) in accordance with Council Decision 98/482/EC. Australia Austria Belgium Brazil Bulgaria Canada China Czechoslovakia Denmark Finland France Germany Greece Hong Kong Hung ...

  • MGE UPS Systems 100 - page 6

    Page 6 - 34003602EN/AB Information and advice. Visual indication. Action. Important instructions that must always be followed. Pictogram symbols UPS : U ninterruptible P ower S ystem. The conventions used to represent indicator lights in the illustrations are as follows: Indicator off. Indicator on. Flashing Indicator. Foreword ...

  • MGE UPS Systems 100 - page 7

    34003602EN/AB - Page 7 1. Presentation 1.1 Unpacking and checking the contents .......................................................................................................... 9 1.2 Overview ..................................................................................................................................................... ...

  • MGE UPS Systems 100 - page 8

    Page 8 - 34003602EN/AB Contents 3. Maintenance 3.1 Cable diagrams ............................................................................................................................................... 30 Serial cable diagrams (ref. 34003618) ................................................................................................... ...

  • MGE UPS Systems 100 - page 9

    34003602EN/AB - Page 9 1. Presentation 1.1 Unpacking and checking the contents Content of the card version A: PowerServices TelPac communication card. B: cover plate specifically designed for Galaxy PW UPS s . C: 5m telephone cable equipped with RJ11 plugs. D: 2.5m serial communication cable used for configuration and maintenance operations. E: 3 w ...

  • MGE UPS Systems 100 - page 10

    Page 10 - 34003602EN/AB Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T - 4 x Digital inputs DC 5V 1. Presentation 1.2 Overview Power supply connector (external unit). Dip-switch to configure the RS485 link. Extension port to connect the 4 additional contact inputs. Shielding configuration jumper. RS232 serial port for con ...

  • MGE UPS Systems 100 - page 11

    34003602EN/AB - Page 11 1. Presentation 1.3 Functions PowerServices TelPac enables connection of one or more products to the MGE UPS SYSTEMS Teleservice centre via an analogue telephone line. Several MGE UPS SYSTEMS products can be connected via a JBUS / RS485 connection. Connection of other equipment not supplied by MGE UPS SYSTEMS is possible via ...

  • MGE UPS Systems 100 - page 12

    Page 12 - 34003602EN/AB 1. Presentation 1.4 T echnical data sheet Functions RS232 Port RS485 Port Modem Contact inputs Power supply (external version) Characteristics/Default values ◗ 9600 ◗ 8 ◗ 1 ◗ None ◗ 1200, 8, 1 ◗ None ◗ 2 wires ◗ Master ◗ With ◗ Without ◗ 0.08 - 0.6 mm 2 (28/20 AWG) ◗ V.34/33.6 kbps ◗ Error correctio ...

  • MGE UPS Systems 100 - page 13

    34003602EN/AB - Page 13 1. Presentation Green UPS indicator 10 Card version 1.5 Indicator lights External version Red CD indicator 9 Card version External version Self tests Card fault Waiting for UPS communication Exchanging data with UPS UPS communication fault Card fault Waiting for UPS communication Exchanging data with UPS Modem connected Mode ...

  • MGE UPS Systems 100 - page 14

    Page 14 - 34003602EN/AB 2. Installation 2.1 Procedure 1 - Install the PowerServices TelPac kit using the present manual. 2 - Fill in the information form. 3 - Send the form to your Teleservice centre (by Fax or Internet). 4 - Your centre will activate this service. 5 - You receive an acknowledgement of receipt. The information form must be sent bac ...

  • MGE UPS Systems 100 - page 15

    34003602EN/AB - Page 15 2. Installation 2.3 The various installation types Remote monitoring One UPS Several UPSs or products Installation type Single-unit Multi-unit UPS connected to the telephone line Galaxy PW Galaxy 3000 Pulsar/Comet EX treme /EX RT Galaxy Comet S31 Others Galaxy PW Galaxy 3000 Pulsar/Comet EX treme /EX RT Galaxy Comet S31 Othe ...

  • MGE UPS Systems 100 - page 16

    Page 16 - 34003602EN/AB 2. Installation 2.4 Recommendations To ensure continuous remote monitoring of your equipment, the unit must remain permanently connected to the telephone network once installed. Regular checks should be made to ensure that it is working properly via the indicator light on the front of the card or external unit (see section 1 ...

  • MGE UPS Systems 100 - page 17

    34003602EN/AB - Page 17 2. Installation Galaxy PW Galaxy 3000 Galaxy Pulsar / Comet EX treme Comet EX RT Comet EXtreme Comet S31 ! ! f a u l t ATTENTION : Onduleur sous Teleservice WARNING: UPS under Teleservice MGE UPS SYSTEMS Ne pas mettre hors tension sans avoir au préalable déconnecté la ligne téléphonique Do not switch off without first d ...

  • MGE UPS Systems 100 - page 18

    Page 18 - 34003602EN/AB 2. Installation 2.6 Setting up the RS485 link General For UPS s equipped with the PowerServices TelPac external version (see table section 2.3 "The various installation types"), communication between the UPS and the external unit is achieved via a RS485 link in 2-wire mode. The link works using the master-slave mod ...

  • MGE UPS Systems 100 - page 19

    34003602EN/AB - Page 19 2. Installation Impedance matching and bias settings If a specific adjustment is required on the RS485 link, see the settings on DIP switch SA1: Switch number 1 2 3 4 Function T+ to R+ connection T- to R- connection T+ 0V bias R+ R- impedance matching Switch number 5 6 7 8 Function R+ 0V bias T- +5V bias T+ T - impedance mat ...

  • MGE UPS Systems 100 - page 20

    Page 20 - 34003602EN/AB Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T - 2 1 3 2 1 3 2. Installation Configuring the shielding terminal When electrical measurements are to be made on the RS485 link, it is possible to configure the shielding terminal of terminal block 7 as a "0V" terminal. The holes above each te ...

  • MGE UPS Systems 100 - page 21

    34003602EN/AB - Page 21 2. Installation Configuring the RS485 card for Comet XM1 XM2 JOJO 6761294 ON OFF XM5 XM3 XM4 The settings proposed below comply with the recommended configuration (see section "Single-unit type installation"). They must be made before installing and commissioning the PowerServices TelPac external unit. The slave nu ...

  • MGE UPS Systems 100 - page 22

    Page 22 - 34003602EN/AB 2. Installation Configuring the RAUZ card for Galaxy The settings proposed below comply with the recommended configuration (see section "Single-unit type installation"). They must be made before installing and commissioning the PowerServices TelPac external unit. The serial link format and the slave number should b ...

  • MGE UPS Systems 100 - page 23

    34003602EN/AB - Page 23 Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T- < 4m Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T- U-Talk Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T- 2. Installation 2.7 Installing the PowerServices T elPac card N.B. : For Galaxy PW UPS ...

  • MGE UPS Systems 100 - page 24

    Page 24 - 34003602EN/AB < 4m < 1m 2. Installation 2.8 Installation of the PowerServices TelPac external unit for Comet UPSs For this installation it is necessary to de-energise the UPS . The various PowerServices TelPac components do not present an electrocution hazard for the installer. It is necessary to initially check: ◗ That the UPS is ...

  • MGE UPS Systems 100 - page 25

    34003602EN/AB - Page 25 300 mm < 1m < 4m 2. Installation Comet S31 15/20KVA Checking the indicator light (see section 1.5 "Indicator lights") ◗ Put the UPS back into operation. ◗ Check the status of the UPS green indicator light 10 : - on steady for 5s (status 1 in the table), - then regular flashing every second (status 3 in th ...

  • MGE UPS Systems 100 - page 26

    Page 26 - 34003602EN/AB XR11 1 2 4 XR11 2. Installation Installation, connections 1 - Open the doors giving access to the switch handles, 2 - Carry out the UPS shut-down procedure and remove the three protective panels, 3 - Check: ◗ that the UPS is equipped with at least one GTCZ communication card 17 and one RAUZ card 18 . ◗ that a protected a ...

  • MGE UPS Systems 100 - page 27

    34003602EN/AB - Page 27 < 3m 2. Installation 8 - Clean the planned location for the external unit using the cleaning kit provided (see figure). 9 - Remove the adhesive protection from under the external unit. 10 - Place the unit as shown. 11 - Press down hard for 10 seconds to fix the adhesive. 12 - Connect the power supply cord 20 to the back o ...

  • MGE UPS Systems 100 - page 28

    Page 28 - 34003602EN/AB A B 5V U-T alk Settings JBUS / RS485 PowerServices TelPac UPS CD Phone A 5V B R+ R- T+ T- < 10m 2. Installation 2.10 Connecting contact type inputs Contact type inputs enable the connection of equipment without RS485 / JBUS links or equipment that is unknown to PowerServices TelPac . By default, closing of a contact cause ...

  • MGE UPS Systems 100 - page 29

    34003602EN/AB - Page 29 2. Installation PowerServices TelPac external unit (2 inputs + 4 extensions) Four similar inputs C, D, E, F are available inside the external unit on terminal block XM13. To connect contacts to these four inputs, proceed as follows: ◗ Remove the cover (partly unscrew the screws and pivot the cover). ◗ Remove the card fro ...

  • MGE UPS Systems 100 - page 30

    Page 30 - 34003602EN/AB 3. Maintenance 3.1 Cable diagrams Serial cable (ref. 34003618) Modem cable (ref. 34003729) Comet link cable (ref. 34003747) red black brown brown red black DB9 female connector DB9/RJ9 cable (2.5 m) RJ9 male connector 4 1 DB9 female connector RJ9 male connector 2 3 4 5 6 7 8 4 3 2 1 9 1 RJ45 male connector RJ45/RJ1 1 cable ( ...

Manufacturer MGE UPS Systems Category Power Supply

Documents that we receive from a manufacturer of a MGE UPS Systems 100 can be divided into several groups. They are, among others:
- MGE UPS Systems technical drawings
- 100 manuals
- MGE UPS Systems product data sheets
- information booklets
- or energy labels MGE UPS Systems 100
All of them are important, but the most important information from the point of view of use of the device are in the user manual MGE UPS Systems 100.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals MGE UPS Systems 100, service manual, brief instructions and user manuals MGE UPS Systems 100. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product MGE UPS Systems 100.

A complete manual for the device MGE UPS Systems 100, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use MGE UPS Systems 100 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of MGE UPS Systems 100.

A complete MGE UPS Systems manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual MGE UPS Systems 100 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the MGE UPS Systems 100, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the MGE UPS Systems 100, that we can find in the current document
3. Tips how to use the basic functions of the device MGE UPS Systems 100 - which should help us in our first steps of using MGE UPS Systems 100
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with MGE UPS Systems 100
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of MGE UPS Systems 100 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning MGE UPS Systems 100?

Use the form below

If you did not solve your problem by using a manual MGE UPS Systems 100, ask a question using the form below. If a user had a similar problem with MGE UPS Systems 100 it is likely that he will want to share the way to solve it.

Copy the text from the picture