    TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-410A MODELS: TCGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .ahridirectory . org LISTED ISO 9001 C ...

  • York TCGD18 THRU 60 - page 2

    359315-YTG-B-0408 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Dat a MODEL TCGD18 S41S1(H) TCGD24 S41S1(H) TCGD30 S41S1(H) TCGD36 S41S1(H) TCGD42 S41S1(H) TCGD48 S41S1(H) TCGD60 S41S1 Unit Supply V oltage ...

  • York TCGD18 THRU 60 - page 3

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 3 Additional R-410A Ch arge / Orifice Size for V arious Matched Systems Outdoor Unit TCGD18 S41S1(H) TCGD24 S41S1(H) TCGD30 S41S1(H) TCGD36 S41S1(H) TCGD42 S41S1(H) TCGD48 S41S1(H) TCGD60 S41S1 Required Orifice or TXV 1,2 0.048 / 902 0.055 / 902 0.061 / 907 0.065 / 9 03 0.075 / 903 0.073 / 904 0. ...

  • York TCGD18 THRU 60 - page 4

    359315-YTG-B-0408 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for th e condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the abo ...

  • York TCGD18 THRU 60 - page 5

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 5 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SENS. 13 SEER AC WITH MA TCGD18S41S1(H) MA08B 17 FC/MC18B 600 17.5 12.9 13.00 1 1.00 TCGD24S41S1(H) MA08B 17 FC/MC36B 800 24.0 16.7 13 .00 1 1.00 MA08B 17 FC/MC35B ...

  • York TCGD18 THRU 60 - page 6

    359315-YTG-B-0408 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / F*FP TCGD18S41S1(H) AHP18 17 – 650 17.5 12.9 13.00 1 1.00 F4FP024 18 – 600 17.5 12.9 13.00 1 1.00 TCGD24S41S1(H) AHP30 17 – 795 24.0 16.8 13.00 1 1.00 F4FP036 21.5 – 800 24.0 16.7 13.00 1 1.00 TCGD30S41S1(H) AHP30 17 – 1015 29.0 21.0 13 ...

  • York TCGD18 THRU 60 - page 7

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SENS. TCGD18S41S1(H) 450 - 750 14,17 FC/MC/PC18 600 17.5 12.9 13.00 1 1.00 450 - 750 14 HC18 600 17.5 12.9 13.00 1 1. ...

  • York TCGD18 THRU 60 - page 8

    359315-YTG-B-0408 8 Johnson Controls Unitary Products COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 13 SEER AC WITH V ARIABLE SPEED FUR NACES 2 TCGD18S41S1(H) PV8*A12 FC/MC/PC1 8A 14 600 17.5 13.4 14.00 12.50 PV9*A12 FC/MC/PC1 8A 14 625 17 ...

  • York TCGD18 THRU 60 - page 9

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 9 TCGD36S41S1(H) PV8*C20 FC/MC/PC48C 21 1200 35.0 25.2 13.50 12.00 P(C,V)9*C16 FC/MC/PC48C 21 1 175 35.0 25.4 14 .00 12.00 P(C,V)9*C20 FC/MC/PC48C 21 1 195 35.0 25.2 14 .00 12.00 P(C,V)9*D20 FC/MC/PC48D 24 1220 35.0 25.4 14 .00 12.00 PV8*C16 HC42 21 1200 36.0 25.4 14.00 12.00 PV8*C20 HC42 21 1200 ...

  • York TCGD18 THRU 60 - page 10

    359315-YTG-B-0408 10 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Required when using TXV i ndoor coil. Also, provides increased starting torque for a reas with low voltage. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor . ROOM ...

  • York TCGD18 THRU 60 - page 11

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD18 THRU 60 - page 12

    359315-YTG-B-0408 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD18 THRU 60 - page 13

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 13 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD18 THRU 60 - page 14

    359315-YTG-B-0408 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD18 THRU 60 - page 15

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 15 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD18 THRU 60 - page 16

    359315-YTG-B-0408 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...

  • York TCGD18 THRU 60 - page 17

    359315-YTG-B-0408 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...

  • York TCGD18 THRU 60 - page 18

    Subject to change without notice. Printe d in U.S.A. 359315-YTG-B-0408 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 359315-YTG-A-0208 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 NOTES ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York TCGD18 THRU 60 can be divided into several groups. They are, among others:
- York technical drawings
- TCGD18 THRU 60 manuals
- York product data sheets
- information booklets
- or energy labels York TCGD18 THRU 60
All of them are important, but the most important information from the point of view of use of the device are in the user manual York TCGD18 THRU 60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York TCGD18 THRU 60, service manual, brief instructions and user manuals York TCGD18 THRU 60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York TCGD18 THRU 60.

Similar manuals

A complete manual for the device York TCGD18 THRU 60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York TCGD18 THRU 60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York TCGD18 THRU 60.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York TCGD18 THRU 60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York TCGD18 THRU 60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York TCGD18 THRU 60, that we can find in the current document
3. Tips how to use the basic functions of the device York TCGD18 THRU 60 - which should help us in our first steps of using York TCGD18 THRU 60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York TCGD18 THRU 60
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York TCGD18 THRU 60 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York TCGD18 THRU 60?

Use the form below

If you did not solve your problem by using a manual York TCGD18 THRU 60, ask a question using the form below. If a user had a similar problem with York TCGD18 THRU 60 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)