TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-410A MODELS: TCGD18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be fo und at w ww .ahridirectory . org LISTED ISO 9001 C ...
-
York TCGD18 THRU 60 - page 2
359315-YTG-B-0408 2 Johnson Controls Unitary Products All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Dat a MODEL TCGD18 S41S1(H) TCGD24 S41S1(H) TCGD30 S41S1(H) TCGD36 S41S1(H) TCGD42 S41S1(H) TCGD48 S41S1(H) TCGD60 S41S1 Unit Supply V oltage ...
-
York TCGD18 THRU 60 - page 3
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 3 Additional R-410A Ch arge / Orifice Size for V arious Matched Systems Outdoor Unit TCGD18 S41S1(H) TCGD24 S41S1(H) TCGD30 S41S1(H) TCGD36 S41S1(H) TCGD42 S41S1(H) TCGD48 S41S1(H) TCGD60 S41S1 Required Orifice or TXV 1,2 0.048 / 902 0.055 / 902 0.061 / 907 0.065 / 9 03 0.075 / 903 0.073 / 904 0. ...
-
York TCGD18 THRU 60 - page 4
359315-YTG-B-0408 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for th e condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the TXV or orifice and additional charge required for s pecific evaporator coil in t he system using the abo ...
-
York TCGD18 THRU 60 - page 5
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 5 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT A L SENS. 13 SEER AC WITH MA TCGD18S41S1(H) MA08B 17 FC/MC18B 600 17.5 12.9 13.00 1 1.00 TCGD24S41S1(H) MA08B 17 FC/MC36B 800 24.0 16.7 13 .00 1 1.00 MA08B 17 FC/MC35B ...
-
York TCGD18 THRU 60 - page 6
359315-YTG-B-0408 6 Johnson Controls Unitary Products — = Not applicable. 13 SEER AC WITH AHP / SHP / F*FP TCGD18S41S1(H) AHP18 17 – 650 17.5 12.9 13.00 1 1.00 F4FP024 18 – 600 17.5 12.9 13.00 1 1.00 TCGD24S41S1(H) AHP30 17 – 795 24.0 16.8 13.00 1 1.00 F4FP036 21.5 – 800 24.0 16.7 13.00 1 1.00 TCGD30S41S1(H) AHP30 17 – 1015 29.0 21.0 13 ...
-
York TCGD18 THRU 60 - page 7
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT A L SENS. TCGD18S41S1(H) 450 - 750 14,17 FC/MC/PC18 600 17.5 12.9 13.00 1 1.00 450 - 750 14 HC18 600 17.5 12.9 13.00 1 1. ...
-
York TCGD18 THRU 60 - page 8
359315-YTG-B-0408 8 Johnson Controls Unitary Products COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 13 SEER AC WITH V ARIABLE SPEED FUR NACES 2 TCGD18S41S1(H) PV8*A12 FC/MC/PC1 8A 14 600 17.5 13.4 14.00 12.50 PV9*A12 FC/MC/PC1 8A 14 625 17 ...
-
York TCGD18 THRU 60 - page 9
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 9 TCGD36S41S1(H) PV8*C20 FC/MC/PC48C 21 1200 35.0 25.2 13.50 12.00 P(C,V)9*C16 FC/MC/PC48C 21 1 175 35.0 25.4 14 .00 12.00 P(C,V)9*C20 FC/MC/PC48C 21 1 195 35.0 25.2 14 .00 12.00 P(C,V)9*D20 FC/MC/PC48D 24 1220 35.0 25.4 14 .00 12.00 PV8*C16 HC42 21 1200 36.0 25.4 14.00 12.00 PV8*C20 HC42 21 1200 ...
-
York TCGD18 THRU 60 - page 10
359315-YTG-B-0408 10 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Required when using TXV i ndoor coil. Also, provides increased starting torque for a reas with low voltage. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor . ROOM ...
-
York TCGD18 THRU 60 - page 11
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...
-
York TCGD18 THRU 60 - page 12
359315-YTG-B-0408 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...
-
York TCGD18 THRU 60 - page 13
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 13 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...
-
York TCGD18 THRU 60 - page 14
359315-YTG-B-0408 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...
-
York TCGD18 THRU 60 - page 15
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 15 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...
-
York TCGD18 THRU 60 - page 16
359315-YTG-B-0408 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree abo ve the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM ...
-
York TCGD18 THRU 60 - page 17
359315-YTG-B-0408 Johnson Controls Unitary Produ cts 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degr ee above the listed temperature and decreases by 1060 BTUH per 1 000 CFM p ...
-
York TCGD18 THRU 60 - page 18
Subject to change without notice. Printe d in U.S.A. 359315-YTG-B-0408 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 359315-YTG-A-0208 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 NOTES ...