  • Bryant 574B - page 1

    SINGLE-PACKAGED GAS HEATING/ELECTRIC COOLING UNITS Model 574B Sizes 024-060 2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 574B.24.1 Single-Packaged Rooftop Products with Energy-Saving Fea- tures and Puron® refrigerant. • Direct Spark Ignition • Low Sound Levels • Up to 81% AFUE • 13 SEER • Variable Speed Blower Standard • F ...

  • Bryant 574B - page 2

    — 2 — Corporate thermostats include the Time Guard ® II anti-short cycle protection circuitry. If a non-corporate thermostat without anti-short cycle protection is used the Time Guard II field in- stalled anti-short cycle kit is recommended. Refrigerant system is designed to provide dependability. Liquid filter dryers are used to promote clean ...

  • Bryant 574B - page 3

    — 3 — ARI* CAPACITIES COOLING CAPACITIES AND EFFICIENCIES UNIT 574B NOMINAL T ONS ST ANDARD CFM NET COOLING CAP A CITIES (Btuh) EER @A‡ SEER† SOUND RA TINGS** (dB) 024040 2 800 24,000 11.0 13.0 72 030040 036060 2-1/2 036060 036090 3 1150 36,000 11.0 13.0 72 042060 042090 3-1/2 11.0 048090 048115 048130 4 1450 45,000 11.0 13.0 78 060090 0601 ...

  • Bryant 574B - page 4

    — 4 — ARI* CAPACITIES (cont) HEATING CAPACITIES AND EFFICIENCIES LEGEND AFUE — Annual Fuel Utilization Efficiency NOTE: Before purchasing this appliance, read important energy cost and efficiency information available from your retailer. OUTDOOR SOUND: OCT A VE B AND D A T A — DECIBELS (Lw(A)) UNIT 574B HEA TING INPUT (Btuh) OUTPUT CAP A CI ...

  • Bryant 574B - page 5

    — 5 — PHYSICAL DATA † Required filter sizes sho wn are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air- flo w or the heating airflow v elocity of 300 ft/min for thro waw ay type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in ...

  • Bryant 574B - page 6

    — 6 — PHYSICAL DATA (cont) † Required filter sizes shown are based on the lar ger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air - flo w or the heating airflow v elocity of 300 ft/min for thro waw ay type or 450 ft/min for high-capacity type. Air filter pressure drop for non-standard filters must not exceed ...

  • Bryant 574B - page 7

    — 7 — OPTIONS AND ACCESSORIES Factory-installed options Coil options include Tin-Plated* indoor hairpins, copper/copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fin construction. See model number nomenclature for coil options. *Tin-Plated indoor coils are built with special hairpi ...

  • Bryant 574B - page 8

    — 8 — FIL TER ACCESS DOOR (HORIZONT AL APPLICA TION ONL Y .) DO NOT REMO VE FROM DO WNFLOW DISCHARGE. REPLACEMENT P ANEL HOLE FOR ECONOMIZER WIRING HARDNESS DOOR LA TCH ANGLE HINGED FIL TER ACCESS DOOR INST ALL FIL TER ACCESS DOOR STICKER ALUMINUM FIL TER RAINHOOD 17 13/32 (442mm) 16 1/4 ” (413mm) 11 13/32 ” (290mm) A99315 Filter Rack A9931 ...

  • Bryant 574B - page 9

    — 9 — BASE UNIT DIMENSIONS — 574B024-036 REQ ’ D CLEARANCES FOR OPERA TION AND SERVICING. in. (mm) Evaporator coil access side .................. 3 6 (914) P ower entry side (except for NEC requirements) ......... 3 6 (914) Unit top .......................... 4 8 (1219) Side opposite ducts ..................... 3 6 (914) Duct panel ........ ...

  • Bryant 574B - page 10

    — 10 — REQUIRED CLEARANCE FOR OPERA TION AND SERVICING in. [mm] EV AP . COIL ACCESS SIDE..............................................................36.00 [914.0] POWER ENTR Y SIDE ......................................................................36.00 [914.0] (EXCEPT FOR NEC REQUIREMENTS) UNIT T OP ........................................ ...

  • Bryant 574B - page 11

    — 11 — ACCESSORY DIMENSIONS C00076 Gasket around outer edge Insulated deck pan Gasket around duct S/A R/A HV A C unit base *Gasketing outer flange Flashing field supplied Roofing material field supplied Cant strip field supplied *Provided with roofcurb Roof Duct work field supplied Insulation (field supplied) Roofcurb* Wood nailer* Gasketing in ...

  • Bryant 574B - page 12

    — 12 — SELECTION PROCEDURE (WITH E XAMPLE) I DETERMINE COOLING AND HEATING REQUIREMENTS AT DESIGN CONDITIONS: Given: Required Cooling Capacity (TC)....................... 34,500 Btuh Sensible Heat Capacity (SHC)......................... 26,000 Btuh Required Heating Capacity............................... 60,000 Btuh Condenser Entering Air Tempe ...

  • Bryant 574B - page 13

    — 13 — PERFORMANCE DATA STANDARD INDOOR ECM MOTOR COOLING CAPACITIES 574B024 COOLING PERFORMANCE T ABLE T emp (F) Outdoor Air Entering Condenser Evaporator Air — CFM / BF 800/0.026 900/0.032 1000/0.04 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 24.0 24.5 26.5 29.1 24.6 25.1 27.1 29.8 25.1 25.5 27.4 30.4 21.9 ...

  • Bryant 574B - page 14

    — 14 — PERFORMANCE DATA (cont) STANDARD INDOOR ECM MOTOR COOLING CAPACITIES (cont) See Legend and Notes on page 15. 574B036 COOLING PERFORMANCE T ABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1100/0.06 1225/0.07 1400/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 36.2 36.8 39.7 43.8 ...

  • Bryant 574B - page 15

    — 15 — PERFORMANCE DATA (cont) STANDARD INDOOR ECM MOTOR COOLING CAPACITIES (cont) 574B048 COOLING PERFORMANCE T ABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air — CFM/BF 1260/0.06 1400/0.06 1600/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52. ...

  • Bryant 574B - page 16

    — 16 — FIL TER SIZE CFM 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 20 X 20 X 1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 ————————— — — 20 X 24 X 1 —— — — 0.09 0.10 0.11 0.13 0.14 0.15 0.16 —————— — — 24 X 30 X 1 —— — — — — — 0.07 0.08 0.09 0 ...

  • Bryant 574B - page 17

    — 17 — 574B COOLING DRY COIL ECM AIRFLOW — SMALL CABINET 574B COOLING DRY COIL ECM AIRFLOW — LARGE CABINET 574B HEATING ECM AIRFLOW — SMALL CABINET 574B HEATING ECM AIRFLOW — LARGE CABINET UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0 – 0.39 0.4 – 0.69 0.7 – 1.0 0.0 – 0.39 0.4 – 0.69 ...

  • Bryant 574B - page 18

    — 18 — 574B ECM AIR FLOW VS. TEMPERATURE RISE CHART PERFORMANCE DATA (CONT) ECONOMIZER/1-IN. FIL TER PRESSURE DROP (in. wg) UNIT COOLING SIZE RA TED GAS INPUT RA TE (X 1000) AIRFLO W SETTING EAST SELECT ™ (SCFM) CALCULA TED TEMPERA TURE RISE MIN. TEMP RISE MAX TEMP RISE MAX DISCH. TEMP 574B 024 40 800 36.5 20 50 175 574B 030 40 800 36.5 20 50 ...

  • Bryant 574B - page 19

    — 19 — TYPICAL PIPING AND WIRING INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00022 C00023 ...

  • Bryant 574B - page 20

    — 20 — APPLICATION DATA Condensate trap — A 2-in. condensate trap must be fi eld supplied. Ductwork — Secure down fl ow discharge ductwork to roof curb . For horizontal discharge applications , attach ductwork to unit with fl anges. T o con vert a unit to down fl ow disc harge — Units are equipped with f actor y-installed inserts in t ...

  • Bryant 574B - page 21

    — 21 — C99024 ELECTRICAL DATA 574B (STANDARD) ELECTRICAL DATA UNIT SIZE 574B V -PH-Hz V O LTA G E RANGE COMPRESSOR OUTDOOR F AN M OTOR INDOOR F AN MO T OR PO WER SUPPL Y Min Max RLA LRA FLA FLA MCA MAX FUSE OR BKR 024 208/230 – 1 – 60 187 253 13.5 61.0 0.8 4.3 22.0/22.0 30/30 030 208/230 – 1 – 60 187 253 16.9 73.0 0.8 4.3 25.0/25.0 30/3 ...

  • Bryant 574B - page 22

    — 22 — TYPICAL WIRING SCHEMATIC — 208/230-1-60 SHOWN C01035 YEL BLK YEL BLU YEL YEL BLK BRN I BLK ...

  • Bryant 574B - page 23

    — 23 — TYPICAL WIRING SCHEMATIC — 208/230-3-60 SHOWN C99077 C03025 ...

  • Bryant 574B - page 24

    — 24 — OPERATING SEQUENCE Heating — On a call for heating, terminal “ W ” of the thermostat is energized, starting the induced-draft motor. When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This function is performed by the integrated gas control (IGC). The e ...

  • Bryant 574B - page 25

    — 25 — ...

  • Bryant 574B - page 26

    — 26 — ...

  • Bryant 574B - page 27

    — 27 — PACKAGED GAS HEATING/ELECTRIC COOLING UNITS CONSTANT VOLUME APPLICATION HVAC GUIDE SPECIFICATIONS SIZE RANGE: 2 TO 5 TONS, NOMINAL COOLING 40,000 TO 130,000 BTUH, NOMINAL HEATING INPUT BRYANT MODEL NUMBER: 574B PART 1 — GENERAL 1.01 SYSTEM DESCRIPTION Outdoor rooftop mounted, gas heating/electric cooling unit utilizing a scroll compres ...

  • Bryant 574B - page 28

    — 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: NEW Form PDS 574B.24.1 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5257-400 8-03 K. Electrical Requirements: All unit power wiring shall enter t ...

Производитель Bryant Категория Gas Heater

Документы, которые мы получаем от производителя устройства Bryant 574B мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 574B
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 574B
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 574B.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 574B, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 574B. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 574B.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 574B, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 574B пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 574B.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 574B - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 574B, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 574B, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 574B - которые должны облегчить нам первые шаги во время использования Bryant 574B
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 574B
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 574B в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 574B?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 574B, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 574B со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)