    PN: 34000281 R1 SNMP-NET UPS SNMP Card (Web-Based monitoring SNMP Card) User ’ s Manual ...

  • Minute Man SNMP-NET - page 2

    SNMP-NET 2 T able of Content s Chapter 1 In troduction .................................................................................................... 3 Features ....................................................................................................................... ........3 System App licatio n ................................ ...

  • Minute Man SNMP-NET - page 3

    SNMP-NET 3 Chapter 1 Introduction Features • Network connection through RJ45 connector Allows connection of the UPS directly to t he Ethernet network through a RJ45 connector without using RS232 ports on the computer and without loading any i ndividual UPS management software on the network server. • Network UPS management Allows remote managem ...

  • Minute Man SNMP-NET - page 4

    SNMP-NET 4 Figure 1-1 System Application Diagram Figure 1-2 SNMP-NET Card UPS SNM P- NET SNMP Card NMS St a ti on or We b B r o w s e r Shutdown S/W Shutdown S/W Shutdown S/W Operati ng Syst em 1 Pow er Line Ethernet Operati ng Syst em 2 Op erating Syst em N. Ethernet Connection Reset Button Console / ENV Connection Di p Switches ...

  • Minute Man SNMP-NET - page 5

    SNMP-NET 5 Chapter 2 Installation Note: The SNMP-NET cards are designed to be Ho t Swappable, but there is a remote chance that when Hot-Swapping the SNMP-NET card that the UPS will shut down. MINUTEMAN recommends following steps 1 through 8 when inst al ling the SNMP-NET card , but to hot-swap, skip to step number 3 and omit steps 6, 7. 1. T urn o ...

  • Minute Man SNMP-NET - page 6

    SNMP-NET 6 Configuring the SNMP-NET by EzSetting 1. Prepare a workst ation (Microsoft Windows 9x, Me, NT4.0, 2000, 2003, XP or later). 2. Make sure both the DIP-s witches of SNMP-NET are set to OFF position (default: normal mode) to enable network transmission. 3. Make sure the workstation and SNMP-NET device are in the same LAN. 4. Put the CD (pro ...

  • Minute Man SNMP-NET - page 7

    SNMP-NET 7 8. Click on the Configuration button and setup t he essential network parameters. (See 2-3) Figure 2-3 Configure the system p arameters. Configuring the SNMP-NET through the COM Port 1. Prepare a workst ation (Microsoft Windows 9x, Me, NT4.0, 2000, 2003, XP or later). 2. Use the RJ45 to DB9 serial cable (provi ded) to connect between the ...

  • Minute Man SNMP-NET - page 8

    SNMP-NET 8 Configuring the SNMP-NET through Telnet 1. Connect the SNMP-NET SNMP card to the network. 2. Prepare a workst ation (Microsoft Window , Ma x OSX or Linux), which is connected to the same LAN. 3. Set both of the DIP-switches of the SNMP-NET to OFF position (normal mode). 4. From the Windows workstatio n open a DOS Prompt and type “telne ...

  • Minute Man SNMP-NET - page 9

    SNMP-NET 9 User Manager +========================+ User Manager +========================+ A d m i n i s t r a t o r [1]. Account: admin [2]. Password: ******** [3]. Limitation: Only in This LAN Device Manager [4]. Account: device [5]. Password: ******** [6]. Limitation: Only in This LAN Read Only User [7]. Account: user [8]. Password: ******** [9] ...

  • Minute Man SNMP-NET - page 10

    SNMP-NET 10 No. Function Description Default 1. IP Address The SNMP-NET IP address. 192.168.001.100 2. Subnet Mask The sub-net mask setting. 255.255.255.000 3. Gateway IP The network default gateway . 192.168.001.254 4. DNS IP Domain Name Server IP address 192.168.001.001 5. BOOTP/DHCP Client Enable/Dis able BOOTP/DHCP protocol Enable 6. HTTP Serve ...

  • Minute Man SNMP-NET - page 11

    SNMP-NET 11 SNMP Trap If you want to use a PC and perform the SNMP m anager ‘trap’ function in order to manage the UPS through SNMP-NET, the IP address of the PC must be added to the SNMP Trap list. The Event Level field is used to decide what kind of power events should be sent to the target address. There are 3 levels of power events: In form ...

  • Minute Man SNMP-NET - page 12

    SNMP-NET 12 Wake On LAN SNMP-NET supports the packet to wakeup workstations in 2 conditions: power restore or system startup with a time delay. +========================+ | W a k e O n L A N | +========================+ Index MAC Address Delay T rigger Conditions [1] 00-0c-08-34-4d-57 001 (Power Restore)(System S tartup) [2] 00-00-00-00-00-00 000 [ ...

  • Minute Man SNMP-NET - page 13

    SNMP-NET 13 Chapter 4 Managing SNMP-NET Running the Web Browser (Internet Explorer) 1. Make sure that you have a TCP/IP network already installed. 2. If there is no DHCP network service on the network, contact your network administrator to get an IP address for you workstation that has the same network’ s address as the SNMP-NET IP address. The d ...

  • Minute Man SNMP-NET - page 14

    SNMP-NET 14 UPS Shutdown during Power Crisis UPS only: SNMP-NET responds to two dif ferent kinds of U PS shutdown events (AC failed, Battery Low). Go to Configure in the UPS M anagement menu and Login as an Admi nistrator . Set the options in UPS Shutdown Action section then press the Submit button. UPS + Shut down Software (SNMP-NET Client): If yo ...

  • Minute Man SNMP-NET - page 15

    SNMP-NET 15 SNMP Access Control Setting SNMP-NET support s SNMP protocol. Y ou c an use an NMS to manage the UPS through the network. The IP address of the workst ation mu st be entered in the SN MP-NET write access table to prevent unauthorized users from conf iguring SNMP-NET via SNMP protocols. Power Fail/Restore Simulation T o make sure the net ...

  • Minute Man SNMP-NET - page 16

    SNMP-NET 16 Chapter 5 Shutdown Software There are two kinds of shutdown software to help you to protect servers from power crisis. One is SNMP-NET Client the other one is the SN MP-NET ShutdownAgent. Both programs have the ability to shutdown servers gracefully . The major difference is the SNMP-NET ShutdownAgent can only receive SNMP traps of powe ...

  • Minute Man SNMP-NET - page 17

    SNMP-NET 17 Chapter 6 Specification Technical Specification Network Connection RJ-45 jack connector Operating T emperature 0 ~ 40 ° C Operating Humidity 10 ~ 80 % Power Input 9~24V DC Power Consumption 1 W att Maximum Size 130 mm x 60 mm (L x W) Weight 58 g Dipswitch Definition No. SW1 SW2 Function Mode 1 ON ON Console Configuration Mode 2 ON OFF ...

  • Minute Man SNMP-NET - page 18

    SNMP-NET 18 Chapter 7 Appendix Troubleshooting 1. How can I provide a SNTP (Simple Netw ork T imer Protocol) server for SNMP-NET? Solution: There are two ways to provide a network T ime Server for SNMP-NET : 1) Install the SNMP-NET Client software you can find it on the CD. 2) Install the “Simple TCP/IP Services” of “Networking Services” fr ...

  • Minute Man SNMP-NET - page 19

    SNMP-NET 19 6. Unable to perform an SNMP get operation. Solution: Check the SNMP settings stored in t he SNMP-NET . The IP Address of the PC you are using must be entered in one of the SNMP Access Control NMS IP fields, with Read or Read/Write permission. The Co mmunity S tring on the PC and SNMP-NET must match. 7. Unable to perform an SNMP set ope ...

  • Minute Man SNMP-NET - page 20

    SNMP-NET 20 Glossary Agent Implemented SNMP applications in network el ement s (hosts). Agent s perform the network management’s functions as requested by t he network administrator from an NMS. Ethernet Local Area Network technology , can link up to 1,024 no des in a bus network. Ethernet provides raw data tran sfer in a rate of 10 megabits/sec. ...

  • Minute Man SNMP-NET - page 21

    SNMP-NET 21 Obtaining Technical Assistance For T echnical Support on the Web, please visit the Support section of our Web site or visit our online Discussion Forum at www .minutemanups.com In order to diagnose the problem you are having, our technicians need the following information from you. Inst allation Site: C o m p a n y N a m e : A d d r e s ...

  • Minute Man SNMP-NET - page 22

    SNMP-NET 22 LIMITED PRODUCT WARRANTY Para System s Inc. (Para Syst ems) wa rrants this equipment, when pro perly applied and operated within specifie d conditions, against faulty materials or workman ship for a peri od of three years from the dat e of original purchase by the end user. For equipm ent sites within the United States and Canada, this ...

Производитель Minute Man Категория Network card

Документы, которые мы получаем от производителя устройства Minute Man SNMP-NET мы можем разделить на несколько групп. Это в частности:
- технические чертежи Minute Man
- инструкции обслуживания SNMP-NET
- паспорта изделия Minute Man
- информационные брошюры
- энергетические этикетки Minute Man SNMP-NET
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Minute Man SNMP-NET.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Minute Man SNMP-NET, инструкции обслуживания, короткие инструкции или инструкции пользователя Minute Man SNMP-NET. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Minute Man SNMP-NET.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Minute Man SNMP-NET, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Minute Man SNMP-NET пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Minute Man SNMP-NET.

Полная инструкция обслуживания Minute Man, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Minute Man SNMP-NET - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Minute Man SNMP-NET, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Minute Man SNMP-NET, которое найдем в данном документе
3. Советы по использованию основных функций устройства Minute Man SNMP-NET - которые должны облегчить нам первые шаги во время использования Minute Man SNMP-NET
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Minute Man SNMP-NET
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Minute Man SNMP-NET в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Minute Man SNMP-NET?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Minute Man SNMP-NET, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Minute Man SNMP-NET со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)