    Form No. PDS 552A.18.3 DELUXE 12 SEER AIR CONDITIONER WITH PURON ® REFRIGERANT 552A (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 552A with Puron® refr igerant provides f eatures which cannot be matched by any other family of equip- ment. The 552A is a Quantum Plus air conditioning system uti- lizing Br yant’ s unique Puron refr igerant. ...

  • Bryant 552A - page 2

    — 2 — DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN CO ...

  • Bryant 552A - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft and/or 20 ft vertical differential, consult Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is for any appro ved non-capillary tube coil combina- tion. Piston is shipped with ou ...

  • Bryant 552A - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-F 024-F/G 030-F 036-F/G Operating W eight (Lb) 168 209 209 212 ELECTRICAL Unit V olts — Her tz — Phase 208/230 — 60 — 1 Operating V oltage Range* 187 — 253 Compressor — Rated Load Amps 10.3 13.5/12.8 14.7 16.7/15.4 Lock ed Rotor Amps 51.0 61.0/60.0 72.5 87.5/83.0 Conden ...

  • Bryant 552A - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actor ily . Operation outside these limits ma y resu lt in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed ca ...

  • Bryant 552A - page 6

    — 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft and/or 20 ft ver tical differential, ref er to Application Guideline and Ser vice Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and ...

  • Bryant 552A - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Contin ued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The cont ...

  • Bryant 552A - page 8

    — 8 — COMBINATION RATINGS UNIT SIZE-SERIES INDOOR UNIT TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV ‡ 018-F *CK5A/CK5BA024 17,500 NONE — 12.00 12.00 10.80 CC5A/CD5AA018 17,200 NONE — 11.50 11.50 10.45 CC5A/CD5AA024 17,500 NONE — 12.00 12.00 10.70 ...

  • Bryant 552A - page 9

    — 9 — 024-F CK5A/CK5BW030 23,200 TDR 13.00 — 13.00 11.20 CK5P A024 23,000 TDR&TXV 12.50 —— 11.10 CK5P A030 23,200 TDR&TXV 13.00 —— 11.20 CK5PW024 23,000 TDR&TXV 12.50 —— 11.10 CK5PW030 23,200 TDR&TXV 13.00 —— 11.20 COILS + 355MA V042040 V ARIABLE-SPEED FURNACE CC5A/CD5A W030 23,200 TDR 13.00 — 13.00 11.05 CK5 ...

  • Bryant 552A - page 10

    — 10 — 024-G CE3AA030 22,600 TDR 13.00 — 13.00 11.80 CK3BA024 22,200 TDR 13.00 — 13.00 11.85 CK3BA030 22,600 TDR 13.00 — 13.00 11.90 CK5A/CK5BA024 22,200 TDR 13.00 — 13.00 11.70 CK5A/CK5BA030 22,600 TDR 13.00 — 13.00 11.80 CK5A/CK5BW024 22,200 TDR 13.00 — 13.00 11.75 CK5A/CK5BW030 22,600 TDR 13.00 — 13.00 11.85 CK5P A024 22,200 TD ...

  • Bryant 552A - page 11

    — 11 — 024-G CK5A/CK5BW030 22,600 TDR 13.00 — 13.00 11.80 CK5PW024 22,200 TDR&TXV 13.00 —— 11.65 CK5PW030 22,600 TDR&TXV 13.00 —— 11.75 COILS + 315(A,J)A V060120 V ARIABLE-SPEED FURNA CE CE3AA024 22,200 TDR 13.00 — 13.00 11.45 CE3AA030 22,600 TDR 13.00 — 13.00 11.70 030-F *CK5A/CK5BA036 29,000 NONE — 12.00 12.00 10.65 CC ...

  • Bryant 552A - page 12

    — 12 — 030-F CK5PW036 29,000 TDR&TXV 13.00 —— 11.60 COILS + 355MA V042060 V ARIABLE-SPEED FURNACE CC5A/CD5AA036 29,000 TDR 13.00 — 13.00 11.25 CC5A/CD5A W030 28,000 TDR 12.50 — 12.50 10.80 CK3BA030 28,000 TDR 12.50 — 12.50 10.85 CK3BA036 29,000 TDR 13.00 — 13.00 11.30 CK5A/CK5BA036 29,000 TDR 13.00 — 13.00 11.30 CK5A/CK5BW030 ...

  • Bryant 552A - page 13

    — 13 — 036-F , G CK5A/CK5BT036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 CK5PE042 34,600 TDR&TXV 12.50 —— 11.25 CK5PT036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 315(A,J)A V048090 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 TDR 12.50 — 12.50 11.30 CC5A/CD5AA042 34,600 TDR 13.00 — 13.00 1 ...

  • Bryant 552A - page 14

    — 14 — 036-F , G CK3BA042 34,600 TDR 12.50 — 12.50 11.20 CK5A/CK5BA036 34,600 TDR 12.50 — 12.50 11.15 CK5P A036 34,600 TDR&TXV 12.50 —— 11.15 COILS + 355MA V042080 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 34,600 TDR 12.50 — 12.50 11.25 CC5A/CD5A W036 34,600 TDR 12.50 — 12.50 11.20 CK3BA042 34,600 TDR 12.50 — 12.50 11.25 CK5A/CK5B ...

  • Bryant 552A - page 15

    — 15 — 042-F CK5P A042 39,000 TDR&TXV 12.50 —— 10.85 CK5P A048 39,500 TDR&TXV 12.50 —— 10.95 CK5PE042 39,500 TDR&TXV 12.50 —— 10.90 CK5PT042 39,000 TDR&TXV 12.50 —— 10.85 CK5PT048 39,500 TDR&TXV 12.50 —— 10.95 COILS + 315(A,J)A V066110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA042 39,000 TDR 12.50 — 12.50 10.9 ...

  • Bryant 552A - page 16

    — 16 — 042-F CC5A/CD5A C048 39,000 TDR 12.50 — 12.50 10.65 CD5AA048 39,500 TDR 12.50 — 12.50 10.80 CK3BA042 39,000 TDR 12.50 — 12.50 10.75 CK3BA048 39,500 TDR 12.50 — 12.50 10.85 CK5A/CK5BA042 39,000 TDR 12.50 — 12.50 10.75 CK5A/CK5BA048 39,500 TDR 12.50 — 12.50 10.85 CK5P A042 39,000 TDR&TXV 12.50 —— 10.75 CK5P A048 39,500 ...

  • Bryant 552A - page 17

    — 17 — 048-F CK5P A048 44,500 TDR&TXV 12.00 —— 10.60 CK5PT048 44,500 TDR&TXV 12.00 —— 10.60 COILS + 315(A,J)A V066110 V ARIABLE-SPEED FURNA CE CC5A/CD5AA060 45,000 TDR 12.50 — 12.50 10.85 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.70 CC5A/CD5A W048 44,500 TDR 12.50 — 12.50 10.80 CD5AA048 44,500 TDR 12.00 — 12.00 10.80 CD ...

  • Bryant 552A - page 18

    — 18 — 048-F CK5PX060 46,000 TDR&TXV 12.00 —— 10.70 COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA060 44,500 TDR 12.00 — 12.00 10.55 CC5A/CD5A C048 44,000 TDR 12.00 — 12.00 10.40 CC5A/CD5A W060 45,500 TDR 12.50 — 12.50 10.85 CD5AA048 44,500 TDR 12.00 — 12.00 10.55 CK3BA048 44,500 TDR 12.00 — 12.00 10.60 CK3BA060 45,0 ...

  • Bryant 552A - page 19

    — 19 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ TXV must be Puron ® compa ...

  • Bryant 552A - page 20

    — 20 — DET AILED COOLING CAP A CITIES* See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys ...

  • Bryant 552A - page 21

    — 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 22

    — 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 23

    — 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 24

    — 24 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 25

    — 25 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 26

    — 26 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 27

    — 27 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 28

    — 28 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 29

    — 29 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 30

    — 30 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 31

    — 31 — DET AILED COOLING CAP A CITIES* Continued See notes on page 32. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † T otal Sys kW** Capacity MBtuh † ...

  • Bryant 552A - page 32

    — 32 — DET AILED COOLING CAP A CITIES* Continued NO TE: When the required data fall between the pub lished data, inter polation may be perf or med. Extrapolation is not an acceptable pr actice. * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/o ...

  • Bryant 552A - page 33

    — 33 — CONDENSER ONL Y RA TINGS* See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN018-F 30 TCG 16.0 15.1 14.3 13.4 12.4 11.5 10.5 9.50 SDT 67.7 77.4 87.0 96.7 106.4 116.1 125.8 135.2 KW 0.80 0.92 1.06 1.21 1.38 1.56 1.76 1.97 35 TCG 17.6 16.6 15.7 14.8 13.8 12.8 11.7 10.6 SDT 68.7 78.3 88. ...

  • Bryant 552A - page 34

    — 34 — CONDENSER ONL Y RA TINGS* Continued See notes on page 35. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 552AN030-F 30 TCG SDT KW 26.7 71.2 1.41 25.3 80.9 1.59 23.8 90.6 1.80 22.4 100. 2.04 21.0 110. 2.30 19.5 120. 2.59 18.0 129. 2.91 16.4 139. 3.26 35 TCG SDT KW 29.3 72.5 1.42 27.8 82.1 1.60 26.2 91.8 1.81 ...

  • Bryant 552A - page 35

    — 35 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure availab le is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temperature without low-ambient oper ation accessor y is 55 ° F (12.8 ° C). 3. Maximum outdoor oper ating air temperature is 125 ° F ...

  • Bryant 552A - page 36

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 552A.18.2 New: PDS 552A.18.3 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 36 — PRINTED IN U.S.A. Catalog No. 5255-206 10-03 GUIDE SPECIFICATIONS GENERAL System Description Outdoo ...

Производитель Bryant Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Bryant 552A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 552A
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 552A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 552A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 552A, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 552A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 552A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 552A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 552A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 552A.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 552A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 552A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 552A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 552A - которые должны облегчить нам первые шаги во время использования Bryant 552A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 552A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 552A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 552A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 552A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 552A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)