    Form No. PDS 533A.24.1 AIR CONDITIONER with Puron ® 533A (60 Hz) Sizes 024 thru 060 Model 533A Energy-Efficient Air Conditioners incor porate innov ative technology to pro vide quiet, reliable cooling per- f ormance. Built into these units are the f eatures most desired by homeo wners today including SEER r atings of at least 12.0 when combined w ...

  • Bryant 533A - page 2

    —2— DIMENSIONS A  SQ AIR IN AIR IN 3 / 8 -IN. DIA TIEDOWN KNOCK OUTS (2) PLACES H G F E L K J AIR IN M N AIR DISCHARGE AIR IN AIR DISCHARGE NO TES: 1. ALLOW 30" CLEARANCE  TO SER VICE SIDE OF UNIT , 48" ABO VE UNIT , 6& ...

  • Bryant 533A - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Residential Split System Application Guideline and Service Manual. CHECK-FLO-RA TER® PISTON * Piston listed is f or any approv ed non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. CHARGING SUBCOO ...

  • Bryant 533A - page 4

    —4— SPECIFICA TIONS See notes on page 6. UNIT SIZE-SERIES 024-A 030-A/A 036-A/A Operating W eight (Lb) 143 138 156 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1/208/230—60—3 208/230—60—1/208/230—60—3 Operating V oltage Range* 187—253 187—253/197—253 187—253/197—253 Compressor— Rated Load Amps 1 ...

  • Bryant 533A - page 5

    —5— SPECIFICA TIONS Continued UNIT SIZE-SERIES 042-A/A 048-A/A 060-A/A Operating W eight (Lb) 197 203 238 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1/208/230—60—3 Operating V oltage Range* 187—253/197—253 Compressor—Rated Load Amps 18.6/13.5 20.5/14.7 27.6/18.1 Lock ed Rotor Amps 105.0/77.0 109.0/91.0 158.0/137.0 Condenser ...

  • Bryant 533A - page 6

    —6— A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Residential Split-System Long-Line Application Guideline and Service Manual. † Only when low-pressure s witch is used. ‡ Required for Lo w-Ambient Controller (full modulation feature) and MotorMaster® Control only . A CCESSOR Y DESCRIPTION AND USA GE (Lis ...

  • Bryant 533A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. Liquid-Line Solenoid V alve (LSV) An electrically operated shutoff valv e to be installed at the outdoor or indoor unit (depending on tubing confi guration) and which stops and starts refrigerant liquid flow in response to compressor oper ation. Maintains a column of ...

  • Bryant 533A - page 8

    —8— COMBINA TION RA TINGS See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 024-A CK5A/CK5BA030* 23,000 NONE — 12.00 12.00 10.05 CC5A/CD5AA024 23,000 NONE — 11.70 11.70 9.90 CC5A/CD5AA030 23,000 NONE — 12.0 ...

  • Bryant 533A - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 030-A COILS + 333(B,J)A V036060 V ARIABLE SPEED FURNA CE CC5A/CD5AA030 27,800 TDR 12.50 — 12.50 10.80 CC5A/CD5AA036 29,000 T ...

  • Bryant 533A - page 10

    —10— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 036-A COILS + 333(B,J)A V048080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 34,600 TDR 13.00 — 13.00 11.15 CC5A/CD5A W036 34,600 ...

  • Bryant 533A - page 11

    —11— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 042-A FV4ANF005 40,500 NONE 13.20 — 13.20 11.45 FX4ANF042 38,500 NONE 11.70 — 11.70 10.25 FX4ANF048 39,500 NONE 12.00 — ...

  • Bryant 533A - page 12

    —12— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 048-A FG3AAA060 45,000 NONE — 11.70 11.70 10.30 FK4CNB006 46,000 TDR&TXV 13.20 — — 11.45 FK4CNF005 45,000 TDR&T ...

  • Bryant 533A - page 13

    —13— * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degr adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a fur nace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ Based on computer simulati ...

  • Bryant 533A - page 14

    —14— DET AILED COOLING CAP A CITIES* See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** T o ...

  • Bryant 533A - page 15

    —15— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 19

    —19— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele v ation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur . † T otal and sensible capacities are net capacities . ...

  • Bryant 533A - page 20

    —20— CONDENSER ONL Y RA TINGS* See notes on page 21. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 533AN024-A 30 TCG 23.3 22.1 20.8 19.6 18.3 17.0 15.7 14.4 SDT 76.9 86.8 96.6 107. 117. 127. 136. 146. KW 1.20 1.37 1.55 1.76 1.98 2.22 2.48 2.74 35 TCG 25.6 24.3 22.9 21.5 20.2 18.7 17.3 15.9 SDT 78.1 87.9 97.7 108. 1 ...

  • Bryant 533A - page 21

    —21— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal P ower (Kw) SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh). SST °F CONDENSER ENTERING AIR TEMPERA TUR ...

  • Bryant 533A - page 22

    —22— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xternal static pressure av ailab le is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without low-ambient oper ation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4 ...

  • Bryant 533A - page 23

    —23— ...

  • Bryant 533A - page 24

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: NEW © 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 —2 4— PRINTED IN U.S.A. Catalog No. 5253-300 2-00 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-cooled, split-sy ...

Производитель Bryant Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Bryant 533A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 533A
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 533A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 533A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 533A, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 533A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 533A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 533A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 533A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 533A.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 533A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 533A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 533A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 533A - которые должны облегчить нам первые шаги во время использования Bryant 533A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 533A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 533A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 533A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 533A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 533A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)