    Form No. PDS 533A.24.1 AIR CONDITIONER with Puron ® 533A (60 Hz) Sizes 024 thru 060 Model 533A Energy-Efficient Air Conditioners incor porate innov ative technology to pro vide quiet, reliable cooling per- f ormance. Built into these units are the f eatures most desired by homeo wners today including SEER r atings of at least 12.0 when combined w ...

  • Bryant 533A - page 2

    —2— DIMENSIONS A  SQ AIR IN AIR IN 3 / 8 -IN. DIA TIEDOWN KNOCK OUTS (2) PLACES H G F E L K J AIR IN M N AIR DISCHARGE AIR IN AIR DISCHARGE NO TES: 1. ALLOW 30" CLEARANCE  TO SER VICE SIDE OF UNIT , 48" ABO VE UNIT , 6& ...

  • Bryant 533A - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Residential Split System Application Guideline and Service Manual. CHECK-FLO-RA TER® PISTON * Piston listed is f or any approv ed non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. CHARGING SUBCOO ...

  • Bryant 533A - page 4

    —4— SPECIFICA TIONS See notes on page 6. UNIT SIZE-SERIES 024-A 030-A/A 036-A/A Operating W eight (Lb) 143 138 156 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1 208/230—60—1/208/230—60—3 208/230—60—1/208/230—60—3 Operating V oltage Range* 187—253 187—253/197—253 187—253/197—253 Compressor— Rated Load Amps 1 ...

  • Bryant 533A - page 5

    —5— SPECIFICA TIONS Continued UNIT SIZE-SERIES 042-A/A 048-A/A 060-A/A Operating W eight (Lb) 197 203 238 ELECTRICAL Unit V olts—Hertz—Phase 208/230—60—1/208/230—60—3 Operating V oltage Range* 187—253/197—253 Compressor—Rated Load Amps 18.6/13.5 20.5/14.7 27.6/18.1 Lock ed Rotor Amps 105.0/77.0 109.0/91.0 158.0/137.0 Condenser ...

  • Bryant 533A - page 6

    —6— A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Residential Split-System Long-Line Application Guideline and Service Manual. † Only when low-pressure s witch is used. ‡ Required for Lo w-Ambient Controller (full modulation feature) and MotorMaster® Control only . A CCESSOR Y DESCRIPTION AND USA GE (Lis ...

  • Bryant 533A - page 7

    —7— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. Liquid-Line Solenoid V alve (LSV) An electrically operated shutoff valv e to be installed at the outdoor or indoor unit (depending on tubing confi guration) and which stops and starts refrigerant liquid flow in response to compressor oper ation. Maintains a column of ...

  • Bryant 533A - page 8

    —8— COMBINA TION RA TINGS See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 024-A CK5A/CK5BA030* 23,000 NONE — 12.00 12.00 10.05 CC5A/CD5AA024 23,000 NONE — 11.70 11.70 9.90 CC5A/CD5AA030 23,000 NONE — 12.0 ...

  • Bryant 533A - page 9

    —9— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 030-A COILS + 333(B,J)A V036060 V ARIABLE SPEED FURNA CE CC5A/CD5AA030 27,800 TDR 12.50 — 12.50 10.80 CC5A/CD5AA036 29,000 T ...

  • Bryant 533A - page 10

    —10— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 036-A COILS + 333(B,J)A V048080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 34,600 TDR 13.00 — 13.00 11.15 CC5A/CD5A W036 34,600 ...

  • Bryant 533A - page 11

    —11— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 042-A FV4ANF005 40,500 NONE 13.20 — 13.20 11.45 FX4ANF042 38,500 NONE 11.70 — 11.70 10.25 FX4ANF048 39,500 NONE 12.00 — ...

  • Bryant 533A - page 12

    —12— COMBINA TION RA TINGS Continued See notes on page 13. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR† Accessory TXV‡ 048-A FG3AAA060 45,000 NONE — 11.70 11.70 10.30 FK4CNB006 46,000 TDR&TXV 13.20 — — 11.45 FK4CNF005 45,000 TDR&T ...

  • Bryant 533A - page 13

    —13— * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degr adation in perf ormance. Use either the accessory Time-Dela y Rela y KAA TD0101TDR or a fur nace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ Based on computer simulati ...

  • Bryant 533A - page 14

    —14— DET AILED COOLING CAP A CITIES* See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** T o ...

  • Bryant 533A - page 15

    —15— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued See notes on page 19. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sys Kw** Capacity MBtuh† T otal Sy ...

  • Bryant 533A - page 19

    —19— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele v ation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur . † T otal and sensible capacities are net capacities . ...

  • Bryant 533A - page 20

    —20— CONDENSER ONL Y RA TINGS* See notes on page 21. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 533AN024-A 30 TCG 23.3 22.1 20.8 19.6 18.3 17.0 15.7 14.4 SDT 76.9 86.8 96.6 107. 117. 127. 136. 146. KW 1.20 1.37 1.55 1.76 1.98 2.22 2.48 2.74 35 TCG 25.6 24.3 22.9 21.5 20.2 18.7 17.3 15.9 SDT 78.1 87.9 97.7 108. 1 ...

  • Bryant 533A - page 21

    —21— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal P ower (Kw) SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh). SST °F CONDENSER ENTERING AIR TEMPERA TUR ...

  • Bryant 533A - page 22

    —22— SYSTEM DESIGN SUMMAR Y 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xternal static pressure av ailab le is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without low-ambient oper ation accessory is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4 ...

  • Bryant 533A - page 23

    —23— ...

  • Bryant 533A - page 24

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: NEW © 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 —2 4— PRINTED IN U.S.A. Catalog No. 5253-300 2-00 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-cooled, split-sy ...

Fabricant Bryant Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilBryant 533A peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bryant
- manuels d’utilisations 533A
- fiches produit Bryant
- dépliants
- ou étiquettes-énergie Bryant 533A
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bryant 533A.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bryant 533A, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bryant 533A. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bryant 533A.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bryant 533A, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bryant 533A par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bryant 533A.

Le manuel d’utilisation complet Bryant, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bryant 533A - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bryant 533A, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBryant 533A qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bryant 533A - qui devraient nous aider dans les premières étapes lors de l'utilisation Bryant 533A
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bryant 533A
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bryant 533A dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bryant 533A?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bryant 533A, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bryant 533A il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)