    Johnson Controls Unitary Produ cts 1031452-UIM-B-0513 R-22 OUTDOOR SPLIT -SYSTEM AIR CONDITIONING SHIPPED WITH NITROGEN CHARGE ONL Y MODELS: 13 SEER - GC GD 1.5 TO 5 T ONS INSTALLATION MANUAL ® LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SAFETY . . . . . . . . . . . . . . . ...

  • Johnson Controls 13 SEER - GCGD - page 2

    1031452-UIM-B-0513 2 Johnson Controls Unitary Products LIMIT A TIONS The unit should be installed in accordance with all National, S tate and Local Safety Codes and the limitations listed below: 1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed. 2. The outdoor unit must not be installed with any duct work i ...

  • Johnson Controls 13 SEER - GCGD - page 3

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 3 LIQUID LINE FIL TER-DRIER The air conditioning unit’s copper spun filter/dryer is located on the liq - uid line. PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied r efrigerant grade (ACR) co pper tubing that is internally c ...

  • Johnson Controls 13 SEER - GCGD - page 4

    1031452-UIM-B-0513 4 Johnson Controls Unitary Products Connect the refrigerant lines u sing the following proced ure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port. 2. Braze the liquid line to the liqui d valve at th ...

  • Johnson Controls 13 SEER - GCGD - page 5

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 5 SECTION V : TXV INST ALLA TIONS The following are the basic steps fo r inst allation. For detailed instruc- tions, refer to the Installation Instructions accompanying the TXV kit. Install TXV kit as follows: 1. Relieve the holding charge by pulling off the rubber cap plug on the suction manifo ...

  • Johnson Controls 13 SEER - GCGD - page 6

    1031452-UIM-B-0513 6 Johnson Controls Unitary Products SUPERHEA T CHARGING METHOD - PIST ON INDOOR 1. Operate system until temperatures and pressures stabilize (mini- mum of 10 minutes). 2. Measure and record indoor wet bulb (WB) temperature using a sling psychrometer and the outdoor dry bulb (DB) temperature using a thermometer . 3. Measure and re ...

  • Johnson Controls 13 SEER - GCGD - page 7

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 7 FIELD CONNECTIONS CONTR OL WIRING 1. Route low voltage wiring into bottom of control box as shown in Figure 6. Make low voltage wiring conne ctions inside the low volt- age box per Figures 7 - 1 1. 2. The complete connection diagram and schematic wiring label is located on the inside surface o ...

  • Johnson Controls 13 SEER - GCGD - page 8

    1031452-UIM-B-0513 8 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V oltage System Wiring” document available online at www . upgnet.com in the Product Catalog Section. FIGURE 8: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1A Single Stage Air Conditioner – PSC Air Han ...

  • Johnson Controls 13 SEER - GCGD - page 9

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 9 FIGURE 9: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1B Single Stage Air Conditioner – PSC Air Handler C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER MA SHP AHP ID MODELS SINGLE STAGE AIR CONDIT I O N ER Other Part Nu mbers: SAP = Legacy 265902 = ...

  • Johnson Controls 13 SEER - GCGD - page 10

    1031452-UIM-B-0513 10 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single S tage AC with PSC Furnace AC 5A Single Stage Air Conditioner – Single Stage PSC Furnace G*9F G*(8/9)S F*(8/9) S PS(8/9) GF(8/9) G8C L*8S C 24 – Volt Comm on R 24 – Volt Hot W Full Stage Heat Y / Y2 Second or Full Stage Compressor SINGLE STAGE PSC FUR ...

  • Johnson Controls 13 SEER - GCGD - page 11

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 11 FIGURE 1 1: Thermostat Chart - Single S tage AC with PSC Furnace AC 5B Single Stage Air Conditioner – Single Stage PSC Furnace C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER SINGLE STAGE AIR CONDIT I O N ER Y Full Stage Compressor G Fan *BP11C50124 *BN11C01124 *D ...

  • Johnson Controls 13 SEER - GCGD - page 12

    1031452-UIM-B-0513 12 Johnson Controls Unitary Products SECTION IX: INSTRUCTING THE O WNER Assist owner with processing warr anty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. I nstruct the owner or the opera- tor how to start, stop and adjust temperature sett ...

  • Johnson Controls 13 SEER - GCGD - page 13

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 13 SECTION X: WIRING DIAGRAM FIGURE 12: Wiring Diagram ...

  • Johnson Controls 13 SEER - GCGD - page 14

    1031452-UIM-B-0513 14 Johnson Controls Unitary Products NOTES ...

  • Johnson Controls 13 SEER - GCGD - page 15

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 15 SECTION XI: ST ART UP SHEET Air Conditioning and Heating Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Name Address City State or Province Zip or Postal Code Indoor Unit Model # Indoor Unit Serial # Indoor Coil Model # Indoor Coil Serial # Upflow Downf ...

  • Johnson Controls 13 SEER - GCGD - page 16

    Subject to change without not ice. Published in U.S.A. 1031452-UIM-B-0513 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 1031452-UIM-A-0413 Y ork Internat ional Corp. 5005 Y ork Driv e Norman, OK 73069 Supply static after indoor coil (in w.c.") Return Static (in w.c.") before filter Total External Static Pres ...

Produzent Johnson Controls Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Johnson Controls 13 SEER - GCGD erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Johnson Controls
- Bedienungsanleitungen 13 SEER - GCGD
- Produktkarten Johnson Controls
- Informationsbroschüren
- oder Energieetiketten Johnson Controls 13 SEER - GCGD
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Johnson Controls 13 SEER - GCGD.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Johnson Controls 13 SEER - GCGD, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Johnson Controls 13 SEER - GCGD. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Johnson Controls 13 SEER - GCGD ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Johnson Controls 13 SEER - GCGD, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Johnson Controls 13 SEER - GCGD hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Johnson Controls 13 SEER - GCGD verständlich ist.

Eine gänzliche Bedienungsanleitung von Johnson Controls sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Johnson Controls 13 SEER - GCGD bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Johnson Controls 13 SEER - GCGD befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Johnson Controls 13 SEER - GCGD, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Johnson Controls 13 SEER - GCGD - die uns die ersten Schritte während der Nutzung von Johnson Controls 13 SEER - GCGD erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Johnson Controls 13 SEER - GCGD hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Johnson Controls 13 SEER - GCGD im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Johnson Controls 13 SEER - GCGD?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Johnson Controls 13 SEER - GCGD nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Johnson Controls 13 SEER - GCGD hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)