    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 1 FM 4/08 Configuring the EZ-ZONE ® RUI/Gateway 1. This White Paper is not m eant to be an exhaustive step-by-st ep discussion in configuring the RUI/Gateway, ...

  • Watlow Electric RUI/Gateway - page 2

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 2 FM 4/08 3. Some notables regarding the graphic above. In the steps that follow we are going to focus on four of the prompt s shown: a. Modbus ® Enable ( Mb;E ...

  • Watlow Electric RUI/Gateway - page 3

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 3 FM 4/08 9. Provide a name for the channel. 10. In this example the device driv er selected will be “Modbus Ethernet”. ...

  • Watlow Electric RUI/Gateway - page 4

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 4 FM 4/08 11. Select the appropriate hardware (network adapter) used on the network. 12. Next, select the appropriat e write optimization method. ...

  • Watlow Electric RUI/Gateway - page 5

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 5 FM 4/08 13. The next selection allows for multiple master s on the network. When mult iple masters exist on a network talking (reading & writ ing) to the ...

  • Watlow Electric RUI/Gateway - page 6

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 6 FM 4/08 15. Once the channel configuration is complete it is now time to configure a device (RUI/Gateway). 16. Select the Modbus ® driver. ...

  • Watlow Electric RUI/Gateway - page 7

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 7 FM 4/08 17. Recall that in steps 1-3 it was said that there ar e other configuration st eps that need to be addressed that are not covered in this paper. As a ...

  • Watlow Electric RUI/Gateway - page 8

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 8 FM 4/08 19. If communications fail between KEPServer EX and RUI/Gateway stop polling device. 20. Generate unique input / output (I /O) tags for the RUI/Gatewa ...

  • Watlow Electric RUI/Gateway - page 9

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 9 FM 4/08 21. Use the defaults for port number and IP protocol. 22. Use the defaults as shown. ...

  • Watlow Electric RUI/Gateway - page 10

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 10 FM 4/08 23. The graphic below sh ows the default Modbus ® word order which also represents the default Modbus ® word order for the RUI/Gateway (Low/High). ...

  • Watlow Electric RUI/Gateway - page 11

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 11 FM 4/08 25. KEPServerEX allows for impor ted tags via a text file. 26. Any tag returning an except ion error will no longer be polle d. ...

  • Watlow Electric RUI/Gateway - page 12

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 12 FM 4/08 27. This concludes the device (RUI/Gateway) configuration. 28. Tag creation. In step 5 some prompts were shown indicating fu rther explanation would ...

  • Watlow Electric RUI/Gateway - page 13

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 13 FM 4/08 each: PV1 of PM1 = 400361 (offset = 0) PV1 of PM2 = 405361 (offset = 5000) PV1 of PM3 = 410361 (offset = 10000) PV1 of PM4 = 415361 (offset = 15000) ...

  • Watlow Electric RUI/Gateway - page 14

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 14 FM 4/08 30. To create similar tags for PV2 - PV4 simply click on the duplicate ic on (circle) and change the fields accordingly (squares). 31. Once each of t ...

  • Watlow Electric RUI/Gateway - page 15

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 15 FM 4/08 said, look closely at the addresses given in defining the CLSP for each of the four PM controls. 33. In the screen shot above we now see a series of ...

  • Watlow Electric RUI/Gateway - page 16

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 16 FM 4/08 34. To better understand the follo wing discussion and examples download and read the section entitled “User Programmable Memory Blocks” found in ...

  • Watlow Electric RUI/Gateway - page 17

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 17 FM 4/08 36. In the screen shot that follows one can see t he factory defaults for the Assembly Definition Addresses (block of 80 words) as they are bei ng re ...

  • Watlow Electric RUI/Gateway - page 18

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 18 FM 4/08 38. Changing an element in the assembly is EZ. A new tag was created as shown below. Notice the address identified as well as the data type. ...

  • Watlow Electric RUI/Gateway - page 19

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 19 FM 4/08 39. The address shown above represents pointer 12 as shown in the EZ-ZONE ® PM Communications user manual under the s ub-heading of “User Programm ...

  • Watlow Electric RUI/Gateway - page 20

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 20 FM 4/08 42. Lastly, in the screen shot below, notice that the 12 th pointer has indeed been changed to Idle Set Point (circle) and the tag created to reflect ...

Produzent Watlow Electric Kategorie Network Card

Dokumente, die wir vom Produzenten des Geräts Watlow Electric RUI/Gateway erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Watlow Electric
- Bedienungsanleitungen RUI/Gateway
- Produktkarten Watlow Electric
- Informationsbroschüren
- oder Energieetiketten Watlow Electric RUI/Gateway
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Watlow Electric RUI/Gateway.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Watlow Electric RUI/Gateway, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Watlow Electric RUI/Gateway. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Watlow Electric RUI/Gateway ansehen.

Die komplette Bedienungsanleitung des Geräts Watlow Electric RUI/Gateway, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Watlow Electric RUI/Gateway hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Watlow Electric RUI/Gateway verständlich ist.

Eine gänzliche Bedienungsanleitung von Watlow Electric sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Watlow Electric RUI/Gateway bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Watlow Electric RUI/Gateway befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Watlow Electric RUI/Gateway, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Watlow Electric RUI/Gateway - die uns die ersten Schritte während der Nutzung von Watlow Electric RUI/Gateway erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Watlow Electric RUI/Gateway hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Watlow Electric RUI/Gateway im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Watlow Electric RUI/Gateway?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Watlow Electric RUI/Gateway nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Watlow Electric RUI/Gateway hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)