    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 1 FM 4/08 Configuring the EZ-ZONE ® RUI/Gateway 1. This White Paper is not m eant to be an exhaustive step-by-st ep discussion in configuring the RUI/Gateway, ...

  • Watlow Electric RUI/Gateway - page 2

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 2 FM 4/08 3. Some notables regarding the graphic above. In the steps that follow we are going to focus on four of the prompt s shown: a. Modbus ® Enable ( Mb;E ...

  • Watlow Electric RUI/Gateway - page 3

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 3 FM 4/08 9. Provide a name for the channel. 10. In this example the device driv er selected will be “Modbus Ethernet”. ...

  • Watlow Electric RUI/Gateway - page 4

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 4 FM 4/08 11. Select the appropriate hardware (network adapter) used on the network. 12. Next, select the appropriat e write optimization method. ...

  • Watlow Electric RUI/Gateway - page 5

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 5 FM 4/08 13. The next selection allows for multiple master s on the network. When mult iple masters exist on a network talking (reading & writ ing) to the ...

  • Watlow Electric RUI/Gateway - page 6

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 6 FM 4/08 15. Once the channel configuration is complete it is now time to configure a device (RUI/Gateway). 16. Select the Modbus ® driver. ...

  • Watlow Electric RUI/Gateway - page 7

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 7 FM 4/08 17. Recall that in steps 1-3 it was said that there ar e other configuration st eps that need to be addressed that are not covered in this paper. As a ...

  • Watlow Electric RUI/Gateway - page 8

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 8 FM 4/08 19. If communications fail between KEPServer EX and RUI/Gateway stop polling device. 20. Generate unique input / output (I /O) tags for the RUI/Gatewa ...

  • Watlow Electric RUI/Gateway - page 9

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 9 FM 4/08 21. Use the defaults for port number and IP protocol. 22. Use the defaults as shown. ...

  • Watlow Electric RUI/Gateway - page 10

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 10 FM 4/08 23. The graphic below sh ows the default Modbus ® word order which also represents the default Modbus ® word order for the RUI/Gateway (Low/High). ...

  • Watlow Electric RUI/Gateway - page 11

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 11 FM 4/08 25. KEPServerEX allows for impor ted tags via a text file. 26. Any tag returning an except ion error will no longer be polle d. ...

  • Watlow Electric RUI/Gateway - page 12

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 12 FM 4/08 27. This concludes the device (RUI/Gateway) configuration. 28. Tag creation. In step 5 some prompts were shown indicating fu rther explanation would ...

  • Watlow Electric RUI/Gateway - page 13

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 13 FM 4/08 each: PV1 of PM1 = 400361 (offset = 0) PV1 of PM2 = 405361 (offset = 5000) PV1 of PM3 = 410361 (offset = 10000) PV1 of PM4 = 415361 (offset = 15000) ...

  • Watlow Electric RUI/Gateway - page 14

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 14 FM 4/08 30. To create similar tags for PV2 - PV4 simply click on the duplicate ic on (circle) and change the fields accordingly (squares). 31. Once each of t ...

  • Watlow Electric RUI/Gateway - page 15

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 15 FM 4/08 said, look closely at the addresses given in defining the CLSP for each of the four PM controls. 33. In the screen shot above we now see a series of ...

  • Watlow Electric RUI/Gateway - page 16

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 16 FM 4/08 34. To better understand the follo wing discussion and examples download and read the section entitled “User Programmable Memory Blocks” found in ...

  • Watlow Electric RUI/Gateway - page 17

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 17 FM 4/08 36. In the screen shot that follows one can see t he factory defaults for the Assembly Definition Addresses (block of 80 words) as they are bei ng re ...

  • Watlow Electric RUI/Gateway - page 18

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 18 FM 4/08 38. Changing an element in the assembly is EZ. A new tag was created as shown below. Notice the address identified as well as the data type. ...

  • Watlow Electric RUI/Gateway - page 19

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 19 FM 4/08 39. The address shown above represents pointer 12 as shown in the EZ-ZONE ® PM Communications user manual under the s ub-heading of “User Programm ...

  • Watlow Electric RUI/Gateway - page 20

    RUI/Gateway & Modbus ® TCP Configuration & Programming Exampl e Using KEPServerEX 4.0 Watlow 1241 Bundy Blvd Winona, MN 55987 Telephone: 507-494-5656 © 2008 Watlow Electric Mfg Co 20 FM 4/08 42. Lastly, in the screen shot below, notice that the 12 th pointer has indeed been changed to Idle Set Point (circle) and the tag created to reflect ...

メーカー Watlow Electric カテゴリー Network Card

Watlow Electric RUI/Gatewayのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- RUI/Gatewayの取扱説明書
- Watlow Electricの製品カード
- パンフレット
- またはWatlow Electric RUI/Gatewayの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Watlow Electric RUI/Gatewayの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Watlow Electric RUI/Gatewayの取り付け説明書、サービスマニュアル、簡易説明書、またはWatlow Electric RUI/Gatewayのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Watlow Electric RUI/Gatewayの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Watlow Electric RUI/Gatewayデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがWatlow Electric RUI/Gatewayを使用するのを助ける技術的文書のことです。説明書は通常、全てのWatlow Electric RUI/Gatewayユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Watlow Electricの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Watlow Electric RUI/Gatewayの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははWatlow Electric RUI/Gatewayの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Watlow Electric RUI/Gatewayに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Watlow Electric RUI/Gatewayデバイスの基本機能を使うにあたってのヒント。 Watlow Electric RUI/Gatewayのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Watlow Electric RUI/Gatewayに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるWatlow Electric RUI/Gatewayのメーカー/サービスへの連絡先に関する情報。

Watlow Electric RUI/Gatewayについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもWatlow Electric RUI/Gatewayの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがWatlow Electric RUI/Gatewayで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)