    I N S T A L L A T I O N I N S T R U C T I O N S H I GH - E F F I C I E N C Y CO N D E N S I N G U N I TS F E A T U R IN G E A R T H - F R I E N D L Y R - 41 0 A R E F R I G E R A NT RSG - 6 1 ⁄ 2 & 7 1 ⁄ 2 T ON 92-42665-14-01 SUPERSEDES 92-42665-14-00 W ARNING [ ] INDICATES METRIC CONVERSIONS e a r t h f r i e n d l y r e f r i g e r a n t ...

  • Heat Controller R-410A - page 2

    2 T ABLE OF CONTENTS I .S A F E T YI N F O R M A T I O N ...........................................3 I I . I N T R O D U C T I O N ..................................................4 I I I . C H E C K I N GP R O D U C TR E C E I V E D ...................................4 I V . E Q U I P M E N TP R O T E C T I O N .................................. ...

  • Heat Controller R-410A - page 3

    3 1.0 SAFETY INFORMA TION ! W ARN ING TH IS U NI T MUS T BE P ER MA NEN TL Y GR OUN DE D. A G ROU ND L UG I S PROVIDED NEAR THE CONTACTOR FOR A GROUND WIRE. FAILURE TO D O SO C A N CA U SE A F I RE O R E LE C TR I CA L S HO C K RE S UL T IN G I N PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH. ! W ARN ING AFTER COMPLETION OF WIRING CHECK ALL ELEC ...

  • Heat Controller R-410A - page 4

    4 II. INTRODUCTION This booklet contains the installation and operating instructions for your self-contained air conditioner. There are a few pre cautions that should be taken to de rive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or danger- ous conditions. Read this booklet and any instructions packag ...

  • Heat Controller R-410A - page 5

    5 V . WHY USE AN AIR COOLED SPLIT SYSTEM? • With an air cooled system, you have no water or sewer connections to make, and no troublesome and costly water treatment problems. • Since the condensing unit is located outside the building, and the low profile air han- dling unit can be installed in the drop ceiling or in the conditioned space, you ...

  • Heat Controller R-410A - page 6

    6 VI. ST ANDARD UNIT FEA TURES — 6 1 ⁄ 2 AND 7 1 ⁄ 2 CABINET — Galvanized steel with a durable powder coat paint finish. The cabinet front and sides are formed into a one piece unitized design with stamped louvers to provide protection for the condenser coils. SERVICE ACCESS — Control box with separation between line and control voltages, ...

  • Heat Controller R-410A - page 7

    TABLE 2 P HYSICAL AND ELECTRICAL DATA TABLE (RSG) 7 Condensing Unit 078 090 Operating Weight (lbs.) [kg] 264 [119.8] 287 [130.2] Shipping Weight (lbs.) [kg] 283 [128.9] 306 [138.8] COMPRESSOR: Quantity 11 Type Scroll RPM 3500 CONDENSER FANS: Quantity 11 CFM [L/s] 4700 [2218] 4700 [2218] Diameter (in.) [mm] 24 [610] 24 [610] Motor Horsepower (ea.) [ ...

  • Heat Controller R-410A - page 8

    8 C. ORDER P ARTS When reporting shortages or damaged parts, or when ordering repair parts, give the c omplete unit model and serial numbers which are stamped on the Unit Rating Plate. D. ST ANDARD ITEMS The condensing unit consists of a completely assembled package which includes a com- p ressor, a condenser coil, fan, fan motors, outdoor control ...

  • Heat Controller R-410A - page 9

    TABLE 3 REFRIGERANT PIPING DATA Equivalent Length (ft.) [m] of straight type “L” tubing for non-ferrous valves and fittings (brazed). Tube Size, O.D. 9 VIII. REFRIGERANT PIPING DA T A CONDE NSING UNI TS ARE SHI PPED WITH A N ITROGE N HOLDING C HARGE. EVACU ATE CONDE NSING UN IT BEFORE C HARGIN G WITH REFR IGERAN T. FIGURE 4 ROOFTOP INSTALLATION ...

  • Heat Controller R-410A - page 10

    10 ! W ARN ING DO NOT U SE OX YGEN T O PUR GE LIN ES OR P RES SURE S YSTE M FOR L E A K T E S T . O X Y G E N R E A C T S V I O L E N T L Y W I T H O I L , W H I C H C A N CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH. FIGURE 5 L IQUID LINE PRESSURE DROP PER 100 FEET EQUIVALENT LENGTH (TYPE L COPPER TUBING) NOTES: 1. When evaporat ...

  • Heat Controller R-410A - page 11

    11 7. Insulate the liquid line whenever the heat pick-up or transfer can affect the sub-cool- ing. 8. Care should be taken to avoid transmission of noise or vibration to building structure. NOTES: 1. The minimum velocity line (700 fpm) is recommended for cooling only units with verti- cal or horizontal run refrigerant lines. 2. For suction pressure ...

  • Heat Controller R-410A - page 12

    12 FIGURE 8 COIL ABOVE CONDENSING UNIT FIGURE 7 COIL BELOW CONDENSING UNIT 16' to 50' 51' to 100' 101' to 150' EQUIVALENT LENGTH TO EVAPORATOR (FEET) 0' to 15' LIQUID LINE O.D. SIZES (INCHES) RECOMMENDED VAPOR AND LIQUID LINE SIZES FOR VARIOUS LENGTHS OF RUN VAPOR LINE O.D. SIZES (INCHES) 078 1 ⁄ 2 1 ⁄ 2 ...

  • Heat Controller R-410A - page 13

    13 VIX. WIRING NOTE: Field wi ring must comply wi th the National Ele ctric Code (CEC in C anada) and any local ordi nance that may app ly. X. ELECTRICAL POWER It is i mpo rtan t tha t pro per el ect ric al pow er is a vai labl e at th e uni t. Vol tag e mus t not va ry mor e tha n 10% of t hat s tam ped on t he ra tin g pla te. (S ee El ect rica l ...

  • Heat Controller R-410A - page 14

    14 XVI. R-410A REFRIGERANT A. TOOLS REQUIRED FOR INST ALLING & SERVICING R-410A MODELS M anifold Sets: -Up to 800 PSIG High Side -Up to 250 PSIG Low Side -550 PSIG Low Side Retard Manifold Hoses: -Service Pressure Rating of 800 PSIG Recovery Cylinders: - 400 PSIG Pressure Rating -Dept. of Transportation 4BA400 or 4BW400 B. SPECIFICA TION OF R-4 ...

  • Heat Controller R-410A - page 15

    D. REPLACEMENT UNITS To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized. Test ...

  • Heat Controller R-410A - page 16

    T ABLE 5 16 (1) Wire length equals twice the run distance. FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS SOLID COPPER WIRE - AWG 3.0 16 14 12 10 10 10 2.5 16 14 12 12 10 10 2.0 18 16 14 12 12 10 50 100 150 200 250 300 Length of Run - Feet (1) Thermostat Load - Amps N OTE: The condensing unit is shipped with a holding charge of dry nitrogen which ...

  • Heat Controller R-410A - page 17

    17 15. Note weight of refrigerant tank. 16. When system has stabilized, check superheat at the suction line service valve. The actual line temperature should be 15° to 25°F higher than the saturation temperature corresponding to the suction pressure. If superheat is measured at evaporator, the actual line temperature should be 15° to 20° higher ...

  • Heat Controller R-410A - page 18

    18 B. LIQUID PRESSURE CONTROL Outdoor fan motor speed control designed to regulate condenser head pressure at low ambients by varying the air volume through the condenser. Has been tested and is avail- able through the parts department. C. LIQUID LINE SOLENOID V AL VE LIQUID LINE SOLENOID VALVE (24V) — Recommended for all split system applica- ti ...

  • Heat Controller R-410A - page 19

    19 RSG078 SYSTEM CHARGE CHAR T 6 1 ⁄ 2 T ON CONDENSER Pressure at Liquid Service P ort (psig) Pressure at Suction Service P ort (psig) 6-1/2 T ON CONDENSING UNIT 60HZ. REFRIGERANT R-410A 92-102644-01-01 CA UTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERA TURE SHOULD BE A T COMFORT CONDITIONS FOR MOST ACCURA TE RESUL TS. INSTRUCTIONS: 1. ...

  • Heat Controller R-410A - page 20

    20 Pressure at Liquid Service P ort (psig) Pressure at Suction Service P ort (psig) Outdoor Ambient (F° DB) 7-1/2 T ON CONDENSING UNIT 60HZ. R EFRIGERANT R-410A 92-102644-03-01 CA UTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERATURE SHOULD BE AT COMFORT CONDITIONS FOR MOST ACCURA TE RESUL TS. INSTRUCTIONS: 1. CONNECT PRESSURE GUAGES TO SU ...

  • Heat Controller R-410A - page 21

    21 B. MAINTENANCE AND OPERA TION 1. All access panels must be in place when unit is in operation. 2. For maximum efficiency, the condenser coil must be kept clean. Periodic inspections, depending on local conditions are recommended. If it is necessary to clean the con- denser coil, use a common garden hose. 3. Never operate the unit without filters ...

  • Heat Controller R-410A - page 22

    22 W ARNING ! DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in control box ...

  • Heat Controller R-410A - page 23

    23 ...

  • Heat Controller R-410A - page 24

    24 CM 1208 ...

Produzent Heat Controller Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Heat Controller R-410A erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Heat Controller
- Bedienungsanleitungen R-410A
- Produktkarten Heat Controller
- Informationsbroschüren
- oder Energieetiketten Heat Controller R-410A
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Heat Controller R-410A.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Heat Controller R-410A, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Heat Controller R-410A. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Heat Controller R-410A ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Heat Controller R-410A, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Heat Controller R-410A hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Heat Controller R-410A verständlich ist.

Eine gänzliche Bedienungsanleitung von Heat Controller sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Heat Controller R-410A bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Heat Controller R-410A befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Heat Controller R-410A, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Heat Controller R-410A - die uns die ersten Schritte während der Nutzung von Heat Controller R-410A erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Heat Controller R-410A hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Heat Controller R-410A im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Heat Controller R-410A?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Heat Controller R-410A nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Heat Controller R-410A hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)