Manual de instrucciones Heat Controller R-410A

24 de páginas 0.75 mb
Descargar

Pasar a la página of 24

Summary
  • Heat Controller R-410A - page 1

    I N S T A L L A T I O N I N S T R U C T I O N S H I GH - E F F I C I E N C Y CO N D E N S I N G U N I TS F E A T U R IN G E A R T H - F R I E N D L Y R - 41 0 A R E F R I G E R A NT RSG - 6 1 ⁄ 2 & 7 1 ⁄ 2 T ON 92-42665-14-01 SUPERSEDES 92-42665-14-00 W ARNING [ ] INDICATES METRIC CONVERSIONS e a r t h f r i e n d l y r e f r i g e r a n t ...

  • Heat Controller R-410A - page 2

    2 T ABLE OF CONTENTS I .S A F E T YI N F O R M A T I O N ...........................................3 I I . I N T R O D U C T I O N ..................................................4 I I I . C H E C K I N GP R O D U C TR E C E I V E D ...................................4 I V . E Q U I P M E N TP R O T E C T I O N .................................. ...

  • Heat Controller R-410A - page 3

    3 1.0 SAFETY INFORMA TION ! W ARN ING TH IS U NI T MUS T BE P ER MA NEN TL Y GR OUN DE D. A G ROU ND L UG I S PROVIDED NEAR THE CONTACTOR FOR A GROUND WIRE. FAILURE TO D O SO C A N CA U SE A F I RE O R E LE C TR I CA L S HO C K RE S UL T IN G I N PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH. ! W ARN ING AFTER COMPLETION OF WIRING CHECK ALL ELEC ...

  • Heat Controller R-410A - page 4

    4 II. INTRODUCTION This booklet contains the installation and operating instructions for your self-contained air conditioner. There are a few pre cautions that should be taken to de rive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or danger- ous conditions. Read this booklet and any instructions packag ...

  • Heat Controller R-410A - page 5

    5 V . WHY USE AN AIR COOLED SPLIT SYSTEM? • With an air cooled system, you have no water or sewer connections to make, and no troublesome and costly water treatment problems. • Since the condensing unit is located outside the building, and the low profile air han- dling unit can be installed in the drop ceiling or in the conditioned space, you ...

  • Heat Controller R-410A - page 6

    6 VI. ST ANDARD UNIT FEA TURES — 6 1 ⁄ 2 AND 7 1 ⁄ 2 CABINET — Galvanized steel with a durable powder coat paint finish. The cabinet front and sides are formed into a one piece unitized design with stamped louvers to provide protection for the condenser coils. SERVICE ACCESS — Control box with separation between line and control voltages, ...

  • Heat Controller R-410A - page 7

    TABLE 2 P HYSICAL AND ELECTRICAL DATA TABLE (RSG) 7 Condensing Unit 078 090 Operating Weight (lbs.) [kg] 264 [119.8] 287 [130.2] Shipping Weight (lbs.) [kg] 283 [128.9] 306 [138.8] COMPRESSOR: Quantity 11 Type Scroll RPM 3500 CONDENSER FANS: Quantity 11 CFM [L/s] 4700 [2218] 4700 [2218] Diameter (in.) [mm] 24 [610] 24 [610] Motor Horsepower (ea.) [ ...

  • Heat Controller R-410A - page 8

    8 C. ORDER P ARTS When reporting shortages or damaged parts, or when ordering repair parts, give the c omplete unit model and serial numbers which are stamped on the Unit Rating Plate. D. ST ANDARD ITEMS The condensing unit consists of a completely assembled package which includes a com- p ressor, a condenser coil, fan, fan motors, outdoor control ...

  • Heat Controller R-410A - page 9

    TABLE 3 REFRIGERANT PIPING DATA Equivalent Length (ft.) [m] of straight type “L” tubing for non-ferrous valves and fittings (brazed). Tube Size, O.D. 9 VIII. REFRIGERANT PIPING DA T A CONDE NSING UNI TS ARE SHI PPED WITH A N ITROGE N HOLDING C HARGE. EVACU ATE CONDE NSING UN IT BEFORE C HARGIN G WITH REFR IGERAN T. FIGURE 4 ROOFTOP INSTALLATION ...

  • Heat Controller R-410A - page 10

    10 ! W ARN ING DO NOT U SE OX YGEN T O PUR GE LIN ES OR P RES SURE S YSTE M FOR L E A K T E S T . O X Y G E N R E A C T S V I O L E N T L Y W I T H O I L , W H I C H C A N CAUSE AN EXPLOSION RESULTING IN SEVERE PERSONAL INJURY OR DEATH. FIGURE 5 L IQUID LINE PRESSURE DROP PER 100 FEET EQUIVALENT LENGTH (TYPE L COPPER TUBING) NOTES: 1. When evaporat ...

  • Heat Controller R-410A - page 11

    11 7. Insulate the liquid line whenever the heat pick-up or transfer can affect the sub-cool- ing. 8. Care should be taken to avoid transmission of noise or vibration to building structure. NOTES: 1. The minimum velocity line (700 fpm) is recommended for cooling only units with verti- cal or horizontal run refrigerant lines. 2. For suction pressure ...

  • Heat Controller R-410A - page 12

    12 FIGURE 8 COIL ABOVE CONDENSING UNIT FIGURE 7 COIL BELOW CONDENSING UNIT 16' to 50' 51' to 100' 101' to 150' EQUIVALENT LENGTH TO EVAPORATOR (FEET) 0' to 15' LIQUID LINE O.D. SIZES (INCHES) RECOMMENDED VAPOR AND LIQUID LINE SIZES FOR VARIOUS LENGTHS OF RUN VAPOR LINE O.D. SIZES (INCHES) 078 1 ⁄ 2 1 ⁄ 2 ...

  • Heat Controller R-410A - page 13

    13 VIX. WIRING NOTE: Field wi ring must comply wi th the National Ele ctric Code (CEC in C anada) and any local ordi nance that may app ly. X. ELECTRICAL POWER It is i mpo rtan t tha t pro per el ect ric al pow er is a vai labl e at th e uni t. Vol tag e mus t not va ry mor e tha n 10% of t hat s tam ped on t he ra tin g pla te. (S ee El ect rica l ...

  • Heat Controller R-410A - page 14

    14 XVI. R-410A REFRIGERANT A. TOOLS REQUIRED FOR INST ALLING & SERVICING R-410A MODELS M anifold Sets: -Up to 800 PSIG High Side -Up to 250 PSIG Low Side -550 PSIG Low Side Retard Manifold Hoses: -Service Pressure Rating of 800 PSIG Recovery Cylinders: - 400 PSIG Pressure Rating -Dept. of Transportation 4BA400 or 4BW400 B. SPECIFICA TION OF R-4 ...

  • Heat Controller R-410A - page 15

    D. REPLACEMENT UNITS To prevent failure of a new condensing unit, the existing evaporator tubing system must be correctly sized and cleaned or replaced. Care must be exercised that the expansion device is not plugged. For new and replacement units, a liquid line filter drier should be installed and refrigerant tubing should be properly sized. Test ...

  • Heat Controller R-410A - page 16

    T ABLE 5 16 (1) Wire length equals twice the run distance. FIELD WIRE SIZE FOR 24 VOLT THERMOSTAT CIRCUITS SOLID COPPER WIRE - AWG 3.0 16 14 12 10 10 10 2.5 16 14 12 12 10 10 2.0 18 16 14 12 12 10 50 100 150 200 250 300 Length of Run - Feet (1) Thermostat Load - Amps N OTE: The condensing unit is shipped with a holding charge of dry nitrogen which ...

  • Heat Controller R-410A - page 17

    17 15. Note weight of refrigerant tank. 16. When system has stabilized, check superheat at the suction line service valve. The actual line temperature should be 15° to 25°F higher than the saturation temperature corresponding to the suction pressure. If superheat is measured at evaporator, the actual line temperature should be 15° to 20° higher ...

  • Heat Controller R-410A - page 18

    18 B. LIQUID PRESSURE CONTROL Outdoor fan motor speed control designed to regulate condenser head pressure at low ambients by varying the air volume through the condenser. Has been tested and is avail- able through the parts department. C. LIQUID LINE SOLENOID V AL VE LIQUID LINE SOLENOID VALVE (24V) — Recommended for all split system applica- ti ...

  • Heat Controller R-410A - page 19

    19 RSG078 SYSTEM CHARGE CHAR T 6 1 ⁄ 2 T ON CONDENSER Pressure at Liquid Service P ort (psig) Pressure at Suction Service P ort (psig) 6-1/2 T ON CONDENSING UNIT 60HZ. REFRIGERANT R-410A 92-102644-01-01 CA UTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERA TURE SHOULD BE A T COMFORT CONDITIONS FOR MOST ACCURA TE RESUL TS. INSTRUCTIONS: 1. ...

  • Heat Controller R-410A - page 20

    20 Pressure at Liquid Service P ort (psig) Pressure at Suction Service P ort (psig) Outdoor Ambient (F° DB) 7-1/2 T ON CONDENSING UNIT 60HZ. R EFRIGERANT R-410A 92-102644-03-01 CA UTION: BEFORE FINAL REFRIGERANT CHECK, INDOOR AIR TEMPERATURE SHOULD BE AT COMFORT CONDITIONS FOR MOST ACCURA TE RESUL TS. INSTRUCTIONS: 1. CONNECT PRESSURE GUAGES TO SU ...

  • Heat Controller R-410A - page 21

    21 B. MAINTENANCE AND OPERA TION 1. All access panels must be in place when unit is in operation. 2. For maximum efficiency, the condenser coil must be kept clean. Periodic inspections, depending on local conditions are recommended. If it is necessary to clean the con- denser coil, use a common garden hose. 3. Never operate the unit without filters ...

  • Heat Controller R-410A - page 22

    22 W ARNING ! DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run • Power off or loose electrical connection • Check for correct voltage at compressor contactor in control box ...

  • Heat Controller R-410A - page 23

    23 ...

  • Heat Controller R-410A - page 24

    24 CM 1208 ...

Fabricante Heat Controller Categoría Air Conditioner

Los documentos del dispositivo Heat Controller R-410A que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Heat Controller
- manuales de instrucciones R-410A
- hojas de producto Heat Controller
- folletos informativos
- o etiquetas energéticas Heat Controller R-410A
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Heat Controller R-410A.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Heat Controller R-410A, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Heat Controller R-410A. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Heat Controller R-410A.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Heat Controller R-410A, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Heat Controller R-410A. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Heat Controller R-410A.

El manual de instrucciones completo de Heat Controller debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Heat Controller R-410A - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Heat Controller R-410A, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Heat Controller R-410A que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Heat Controller R-410A - que deben facilitarnos los primeros pasos durante el uso de Heat Controller R-410A
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Heat Controller R-410A
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Heat Controller R-410A en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Heat Controller R-410A?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Heat Controller R-410A, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Heat Controller R-410A probablemente compartirá una forma de solucionarlo.