    Cancels: II 619C-24-3 II 619C-24-4 4/15/06 CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1 INST ALLA TION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17 I. Step 1 — Complete Pre-Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 II. Step ...

  • Bryant 619CNQ - page 2

    —2— T able 1 — System Matches *Units must be field reconfigured f or 1 1 / 2 ton (18,000 Btuh) operation. See Bef ore Installation section on page 3 for details. NO T E: Numbers in ( ) indicate quantities when there is more than one fan coil unit in the system. Ensure unit operation within the application guidelines shown in T able 2. When in ...

  • Bryant 619CNQ - page 3

    —3— T able 3A — Physical Data, Unde r Ceiling Cooling Onl y Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on this page for details . †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch. I. STEP 1 — COMPLETE PRE-INST ALLA TION CHECKS A. Unpack Unit Store fan coil ...

  • Bryant 619CNQ - page 4

    —4— T able 3B — Physical Data, Under Ceiling Heat Pump Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on page 3 for details. †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch. 3. Remove inlet grilles from in door unit by sliding for- ward. Reinstall prior to unit ...

  • Bryant 619CNQ - page 5

    —5— Fig. 3 — Base Unit Dimensions UNIT SIZE WEIGHT (lb) A B E F G Cooling Only Heat Pump ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm 024 108 110 4- 2 15 / 16 1294 3-10 1169 4- 1 5 / 8 1260 — — 1- 9 5 / 8 549 036 117 119 4-10 13 / 16 1493 4- 5 7 / 8 1368 4- 9 1 / 2 1459 — — 2- 1 1 / 2 648 048 149 151 5-11 9 / 16 1817 5- 6 5 / 8 1 ...

  • Bryant 619CNQ - page 6

    —6— 5. Run refrigerant piping as directly as possible and avoid any unnecessary turns or ben ds . 6. Condensate piping can be dir ected through the inside wall to an approved drain or straight o utside. NO TE: The piping hole for condensate line must slope at a minimum pitch of 1 / 4 in. per foot to ensure proper drainage . If proper pitch cann ...

  • Bryant 619CNQ - page 7

    —7— F . T o Install Thermostat: If there is at least 3 / 8 in. of space between the back of indoor unit and wall: 1. Route thermostat wires (fi eld-supplied) through slot in right side or rear panel of indoor unit (F ig. 3). 2. Route wires over refr igerant and drain piping as shown in Fig . 12. IMPORT ANT : Do not route wires under the piping ...

  • Bryant 619CNQ - page 8

    —8— 3. Insulate and caulk wall openings to reduce air infil- tration and refrigerant pipe vibrations on structure. 4. Evacuate piping, if necessary . If either refrigerant piping or the indoor coil is exposed to atmospheric conditions , it must be ev acua ted to 1000 microns to eliminate contamination and moisture in the system. V . STEP 5 — ...

  • Bryant 619CNQ - page 9

    —9— HEX-HEAD BOLT MOUNTING SLOT Fig. 10 — Mounting Ha nging Brackets Fig. 11 — Hangin g Fan Co il Unit *F actor y-supplied. Fig. 12 — Routing Wires Over Piping NO TE: T eflon Seal must face to ward the outdoor heat pump unit. Fig. 13 — AccuRater Meteri ng Device at Service V alve (Bypass T ype Components), Heat Pump Systems Only a40-625 ...

  • Bryant 619CNQ - page 10

    —10— VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS Be sure field wiring complies with local building codes and NEC , and unit voltage is within limits shown in T ab le 5. Contact local power company for correction of improper line voltage. NO TE: Use copper wire only betw een disconnect switch(es) and unit. NO TE: Instal l branch circuit disconnec ...

  • Bryant 619CNQ - page 11

    —11— Fig. 14 — Component Location (T ypical Ceiling-Suspended System) LEGEND *Standard. †Accessory item. **Field supplied. ††Insulate for heat pump application. NO T ES: 1. All piping must f ollow standard refr igerant piping techniques. 2. All wiring must comply with the applicable local and national codes . 3. Liquid line need not be ...

  • Bryant 619CNQ - page 12

    —12— VII. STEP 7 — INST ALL THERMOST A T These systems use a 3-speed thermostat. The thermostat monitors the system operatio n and controls the operating mode. T o change settings or re fer to the thermostat Operat- ing Instructions. Mount thermostat to a wall in the occupied space using 2 field-supplied screws . Locate th e thermostat in an ...

  • Bryant 619CNQ - page 13

    —13— LEGEND ASM — Air Sweep Motor ASR — Air Sw ee p Rela y EQUIP GND — Equipment Ground FL — Fuse Link FPT — F reeze Protection Ther mostat HP — Heat Pump HR — Heater Relay HTR — Heater HTT — Heater T emp. Thermostat IFM — Indoor-F an Motor NEC — National Electrical Code PL — Plug TB — T er minal Board TRAN — T ransf ...

  • Bryant 619CNQ - page 14

    —14— AUTO COOL HEA T COOL HEA T AUTO FLA T THERMOST A T (FLA TST A T) COOLING ONL Y HEA T & COOL (53DFS250-FS-BR Y) SLIMLINE THERMOST A T HEA T PUMP COOLING ONL Y HEA T & COO L (53DFS250-SL-BR Y) 5-1-1 PROGRAMMABLE THERMOST A T COOLING ONL Y HEA T & COOL (53DFST2-NP-BR Y) Fig. 18 — Thermostats a40-1384 a40-1385 a40-1386 ...

  • Bryant 619CNQ - page 15

    —15— VIII. STEP 8 — MAKE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS The thermostat is wired betw een the indoor and outdoor units to make the s ystem complete. A. Check AccuRater Metering Device The correct Ac cuRater (bypass type) refrigerant con t rol is required for system capacity optimization. An AccuRater device (see Fig. 19) is suppl ...

  • Bryant 619CNQ - page 16

    —16— 5 38 A 619CNF ,CNQ 5 38 A 619CNF ,CNQ Fig. 20 — Cooling System Wiring Diagram a40-1636 ...

  • Bryant 619CNQ - page 17

    —17— 619CNQ 5 38 B 5 38 B 619CNQ Fig. 21 — Heat Pump Wiring Diagram a40-1637 ...

  • Bryant 619CNQ - page 18

    —18— ST ART -UP Make the following checks and complete the Start-Up Check- list on page CL-1 before sy stem start-up. Also refer to the condensing unit Installation, St art-Up and Service Instructions for system start-up instructions and refrigerant charging methods . 1. Check condensate drainage system: a. Remove grille and frame from the unit ...

  • Bryant 619CNQ - page 19

    —19— The DFB logic checks the 10-m inute defrost timer and the DFT . If the DFT opens in less than 10 minutes , the DFB switches the unit back to norm al heating operation. If the DFT remains closed, the DFB switches the unit back to heating operation after 10 minu tes. When the DFB changes back to heating mode , the RVR (reversing valve relay) ...

  • Bryant 619CNQ - page 20

    —20— III. CLEAN INDOOR UNIT BOTT OM P ANEL If the bottom panel of the unit becomes dirty or smudged, wipe the outside of the panel wi th a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth. IV . CLEAN INDOOR COIL T o clean the coil, remove ind oor unit bottom panel and vac- uum the coil fins, using care not to ...

  • Bryant 619CNQ - page 21

    —21— T able 7 — T roubleshooting *If fuse blo ws or circuit breaker trips again after firs t star t attempt, DO NOT attempt to start system again. Contact your local dealer f or assistance. †When outdoor temperature is approximately 55 F or bel ow , indoor coil frosting may occur when system is operated in cooling or maximum dehumidificatio ...

  • Bryant 619CNQ - page 22

    Copy right 2006 Bryant Heating & Cooling Systems Printed in U.S .A. CA T ALOG NO . 02-619C0001-II SER VICE TRAINING P ackaged Service Training programs are an excellent wa y to in crease your knowledge of the equip- ment discussed in this manual, includi ng: • Unit F amiliarization • Maintenance • Installation Overview • Operating Seque ...

  • Bryant 619CNQ - page 23

    CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR UNIT : MODEL NO. ___________________ INDOOR UNIT : MODEL NO . _____________________ SERIAL NO . ________________________________ ___ SERIAL NO . ________________________________ ___ ACCESSORIES: _________________________________________ _________________________________________ PISTONS: ...

  • Bryant 619CNQ - page 24

    Copy right 2006 Bryant Heating & Cooling Systems Printed in U .S.A. CL-2 6-06A CA T ALOG NO. 02-619C00 01-II CUT ALONG DO TTED LINE CUT ALONG DOTTED LINE ST ART -UP CHECKLIST (c ont) IV . ST ART -UP IF UNIT HAS A CRANKC ASE HEATER, HAS IT BEEN ON FOR 24 HOURS? ____________ MEASURE AND RECORD THE: AIR ENTERING OUTDOOR UNIT : ____________ F AIR E ...

Produzent Bryant Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Bryant 619CNQ erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bryant
- Bedienungsanleitungen 619CNQ
- Produktkarten Bryant
- Informationsbroschüren
- oder Energieetiketten Bryant 619CNQ
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bryant 619CNQ.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bryant 619CNQ, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bryant 619CNQ. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bryant 619CNQ ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bryant 619CNQ, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bryant 619CNQ hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bryant 619CNQ verständlich ist.

Eine gänzliche Bedienungsanleitung von Bryant sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bryant 619CNQ bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bryant 619CNQ befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bryant 619CNQ, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bryant 619CNQ - die uns die ersten Schritte während der Nutzung von Bryant 619CNQ erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bryant 619CNQ hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bryant 619CNQ im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bryant 619CNQ?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bryant 619CNQ nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bryant 619CNQ hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)