    Cancels: II 619C-24-3 II 619C-24-4 4/15/06 CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1 INST ALLA TION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-17 I. Step 1 — Complete Pre-Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 II. Step ...

  • Bryant 619CNQ - page 2

    —2— T able 1 — System Matches *Units must be field reconfigured f or 1 1 / 2 ton (18,000 Btuh) operation. See Bef ore Installation section on page 3 for details. NO T E: Numbers in ( ) indicate quantities when there is more than one fan coil unit in the system. Ensure unit operation within the application guidelines shown in T able 2. When in ...

  • Bryant 619CNQ - page 3

    —3— T able 3A — Physical Data, Unde r Ceiling Cooling Onl y Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on this page for details . †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch. I. STEP 1 — COMPLETE PRE-INST ALLA TION CHECKS A. Unpack Unit Store fan coil ...

  • Bryant 619CNQ - page 4

    —4— T able 3B — Physical Data, Under Ceiling Heat Pump Units *Field reconfigured to 18,000 Btuh (1 1 / 2 tons). See Before Installation section on page 3 for details. †The valv e connect ion size is 7 / 8 inch. The recommended line size is 1 1 / 8 inch. 3. Remove inlet grilles from in door unit by sliding for- ward. Reinstall prior to unit ...

  • Bryant 619CNQ - page 5

    —5— Fig. 3 — Base Unit Dimensions UNIT SIZE WEIGHT (lb) A B E F G Cooling Only Heat Pump ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm 024 108 110 4- 2 15 / 16 1294 3-10 1169 4- 1 5 / 8 1260 — — 1- 9 5 / 8 549 036 117 119 4-10 13 / 16 1493 4- 5 7 / 8 1368 4- 9 1 / 2 1459 — — 2- 1 1 / 2 648 048 149 151 5-11 9 / 16 1817 5- 6 5 / 8 1 ...

  • Bryant 619CNQ - page 6

    —6— 5. Run refrigerant piping as directly as possible and avoid any unnecessary turns or ben ds . 6. Condensate piping can be dir ected through the inside wall to an approved drain or straight o utside. NO TE: The piping hole for condensate line must slope at a minimum pitch of 1 / 4 in. per foot to ensure proper drainage . If proper pitch cann ...

  • Bryant 619CNQ - page 7

    —7— F . T o Install Thermostat: If there is at least 3 / 8 in. of space between the back of indoor unit and wall: 1. Route thermostat wires (fi eld-supplied) through slot in right side or rear panel of indoor unit (F ig. 3). 2. Route wires over refr igerant and drain piping as shown in Fig . 12. IMPORT ANT : Do not route wires under the piping ...

  • Bryant 619CNQ - page 8

    —8— 3. Insulate and caulk wall openings to reduce air infil- tration and refrigerant pipe vibrations on structure. 4. Evacuate piping, if necessary . If either refrigerant piping or the indoor coil is exposed to atmospheric conditions , it must be ev acua ted to 1000 microns to eliminate contamination and moisture in the system. V . STEP 5 — ...

  • Bryant 619CNQ - page 9

    —9— HEX-HEAD BOLT MOUNTING SLOT Fig. 10 — Mounting Ha nging Brackets Fig. 11 — Hangin g Fan Co il Unit *F actor y-supplied. Fig. 12 — Routing Wires Over Piping NO TE: T eflon Seal must face to ward the outdoor heat pump unit. Fig. 13 — AccuRater Meteri ng Device at Service V alve (Bypass T ype Components), Heat Pump Systems Only a40-625 ...

  • Bryant 619CNQ - page 10

    —10— VI. STEP 6 — MAKE ELECTRICAL CONNECTIONS Be sure field wiring complies with local building codes and NEC , and unit voltage is within limits shown in T ab le 5. Contact local power company for correction of improper line voltage. NO TE: Use copper wire only betw een disconnect switch(es) and unit. NO TE: Instal l branch circuit disconnec ...

  • Bryant 619CNQ - page 11

    —11— Fig. 14 — Component Location (T ypical Ceiling-Suspended System) LEGEND *Standard. †Accessory item. **Field supplied. ††Insulate for heat pump application. NO T ES: 1. All piping must f ollow standard refr igerant piping techniques. 2. All wiring must comply with the applicable local and national codes . 3. Liquid line need not be ...

  • Bryant 619CNQ - page 12

    —12— VII. STEP 7 — INST ALL THERMOST A T These systems use a 3-speed thermostat. The thermostat monitors the system operatio n and controls the operating mode. T o change settings or re fer to the thermostat Operat- ing Instructions. Mount thermostat to a wall in the occupied space using 2 field-supplied screws . Locate th e thermostat in an ...

  • Bryant 619CNQ - page 13

    —13— LEGEND ASM — Air Sweep Motor ASR — Air Sw ee p Rela y EQUIP GND — Equipment Ground FL — Fuse Link FPT — F reeze Protection Ther mostat HP — Heat Pump HR — Heater Relay HTR — Heater HTT — Heater T emp. Thermostat IFM — Indoor-F an Motor NEC — National Electrical Code PL — Plug TB — T er minal Board TRAN — T ransf ...

  • Bryant 619CNQ - page 14

    —14— AUTO COOL HEA T COOL HEA T AUTO FLA T THERMOST A T (FLA TST A T) COOLING ONL Y HEA T & COOL (53DFS250-FS-BR Y) SLIMLINE THERMOST A T HEA T PUMP COOLING ONL Y HEA T & COO L (53DFS250-SL-BR Y) 5-1-1 PROGRAMMABLE THERMOST A T COOLING ONL Y HEA T & COOL (53DFST2-NP-BR Y) Fig. 18 — Thermostats a40-1384 a40-1385 a40-1386 ...

  • Bryant 619CNQ - page 15

    —15— VIII. STEP 8 — MAKE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNITS The thermostat is wired betw een the indoor and outdoor units to make the s ystem complete. A. Check AccuRater Metering Device The correct Ac cuRater (bypass type) refrigerant con t rol is required for system capacity optimization. An AccuRater device (see Fig. 19) is suppl ...

  • Bryant 619CNQ - page 16

    —16— 5 38 A 619CNF ,CNQ 5 38 A 619CNF ,CNQ Fig. 20 — Cooling System Wiring Diagram a40-1636 ...

  • Bryant 619CNQ - page 17

    —17— 619CNQ 5 38 B 5 38 B 619CNQ Fig. 21 — Heat Pump Wiring Diagram a40-1637 ...

  • Bryant 619CNQ - page 18

    —18— ST ART -UP Make the following checks and complete the Start-Up Check- list on page CL-1 before sy stem start-up. Also refer to the condensing unit Installation, St art-Up and Service Instructions for system start-up instructions and refrigerant charging methods . 1. Check condensate drainage system: a. Remove grille and frame from the unit ...

  • Bryant 619CNQ - page 19

    —19— The DFB logic checks the 10-m inute defrost timer and the DFT . If the DFT opens in less than 10 minutes , the DFB switches the unit back to norm al heating operation. If the DFT remains closed, the DFB switches the unit back to heating operation after 10 minu tes. When the DFB changes back to heating mode , the RVR (reversing valve relay) ...

  • Bryant 619CNQ - page 20

    —20— III. CLEAN INDOOR UNIT BOTT OM P ANEL If the bottom panel of the unit becomes dirty or smudged, wipe the outside of the panel wi th a soft dry cloth. Use a mild liquid detergent and wipe off carefully with a dry cloth. IV . CLEAN INDOOR COIL T o clean the coil, remove ind oor unit bottom panel and vac- uum the coil fins, using care not to ...

  • Bryant 619CNQ - page 21

    —21— T able 7 — T roubleshooting *If fuse blo ws or circuit breaker trips again after firs t star t attempt, DO NOT attempt to start system again. Contact your local dealer f or assistance. †When outdoor temperature is approximately 55 F or bel ow , indoor coil frosting may occur when system is operated in cooling or maximum dehumidificatio ...

  • Bryant 619CNQ - page 22

    Copy right 2006 Bryant Heating & Cooling Systems Printed in U.S .A. CA T ALOG NO . 02-619C0001-II SER VICE TRAINING P ackaged Service Training programs are an excellent wa y to in crease your knowledge of the equip- ment discussed in this manual, includi ng: • Unit F amiliarization • Maintenance • Installation Overview • Operating Seque ...

  • Bryant 619CNQ - page 23

    CL-1 ST ART -UP CHECKLIST I. PRELIMINAR Y INFORMA TION OUTDOOR UNIT : MODEL NO. ___________________ INDOOR UNIT : MODEL NO . _____________________ SERIAL NO . ________________________________ ___ SERIAL NO . ________________________________ ___ ACCESSORIES: _________________________________________ _________________________________________ PISTONS: ...

  • Bryant 619CNQ - page 24

    Copy right 2006 Bryant Heating & Cooling Systems Printed in U .S.A. CL-2 6-06A CA T ALOG NO. 02-619C00 01-II CUT ALONG DO TTED LINE CUT ALONG DOTTED LINE ST ART -UP CHECKLIST (c ont) IV . ST ART -UP IF UNIT HAS A CRANKC ASE HEATER, HAS IT BEEN ON FOR 24 HOURS? ____________ MEASURE AND RECORD THE: AIR ENTERING OUTDOOR UNIT : ____________ F AIR E ...

Производитель Bryant Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Bryant 619CNQ мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания 619CNQ
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant 619CNQ
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant 619CNQ.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant 619CNQ, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant 619CNQ. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant 619CNQ.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant 619CNQ, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant 619CNQ пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant 619CNQ.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant 619CNQ - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant 619CNQ, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant 619CNQ, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant 619CNQ - которые должны облегчить нам первые шаги во время использования Bryant 619CNQ
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant 619CNQ
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant 619CNQ в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant 619CNQ?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant 619CNQ, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant 619CNQ со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)