    NOTE: Read the entire instruction manual before performing any service or maintenance. This symbol → indicates a change since the last issue. These procedures are for size 44,000 through 154,000 Btuh input units. Index Page SAFETY CONSIDERATIONS ..................................................1-2 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCED ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 2

    WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSS ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 3

    1. Downflow/Horizontal Each furnace requires 2 filters which are installed in the return-air duct. (See Fig. 4 and 5.) To remove filters for cleaning or replacement, proceed as follows: a. Disconnect electrical power before removing blower access door. b. Remove screw from front of door and remove blower access door. c. Reach up behind top plate, t ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 4

    9. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel: a. Mark blower wheel location on shaft before disassembly to ensure proper reassembly. b. Loosen setscrew holding blower wheel on motor shaft. NOTE: Mark blower mounting arms, motor, and blower housing ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 5

    WARNING: Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warn- ing could result in electrical shock, personal injury, or death. NOTE: If thermostat terminals are jumpered before blower ac- cess door ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 6

    (8.) Reinstall cell inlet plates and burner assembly. Care must be exercised to center burners in cell openings. 11. Clean flame sensor with fine steelwool. 12. Remove old sealant from center panel and collector box flange and apply new sealant to collector box flange and reinstall on center panel, making sure all 8 screws are secure. NOTE: A relea ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 7

    c. Remove control access door. d. BRIEFLY remove either wire from the main limit switch until LED goes out, then reconnect it. NOTE: If wire to main limit is disconnected longer than 4 sec, main blower starts, and retrieval request is ignored. 2. When above items have been completed, the following will occur: a. LED flashes a status code 4 times. R ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 8

    Fig. 11—Furnace Control A99255 HUMIDIFIER TERMINAL (24-V AC 0.5 AMP MAX) LED OPERA TION & DIAGNOSTIC LIGHT HARNESS CONNECT OR 24-V TRANSFORMER SEC-2 SP ARE-1 SP ARE-2 EAC-1 EAC-ELECTR ONIC AIR CLEANER TERMINALS (115-V AC 1.0 AMP MAX) EAC-2 115-V AC (L2) NEUTRAL CONNECTION 24-V THERMOST A T TERMINALS BLOWER SPEED SELECTION TERMINALS INDUCER MO ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 9

    → Fig. 12—Furnace Wiring Diagram A00304 PCB BLOWER OFF DELAY SELECTION CHART 90 SEC 135 SEC 180 SEC 225 SEC GVR H I/L O RELA Y SEC-1 SEC-2 PL1 3 2 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DELAY G R Y W C HUM HSI R I DR BLWR BLOWER SPEED SELECT FU1 COOL HEA T L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC -3A FUSE SP A RE-2 SP ARE-1 EAC-1 EAC-2 C 1 ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 10

    Fig. 13—Service Label A96263 SERVICE 11 NO PREVIOUS CODE - Stored sta tus codes are er ased when power (115 V or 24V) to control is interrupted or 48 hours after ea ch fault is cl eared. 12 BLOWER ON AFTER POWER UP ( 115V or 24V) - Blower ru ns for 90 seconds, if unit is power ed up duri ng a call for hea t (R-W closed). 13 LI MIT OR FLAM E ROLL- ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 11

    —11— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 12

    Is circuit breaker closed? Close door switch and go to start. Is red LED status light on? Is door switch closed? Is red LED status light blinking rapidly without a pause? Is there 1 15v going to switch? Replace door switch. Replace control center . Replace transformer . Is red LED status light blinking ON/OFF slowly with a combination of short and ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 13

    11 NO PREVIOUS F AUL T - Faults are erased after 48 hrs or whenever power (1 15v or 24v) is interrupted. Run system through a heating or cooling cycle to check system. 12 BLO WER ON AFTER PO WER UP (115V OR 24V) - Normal operation. Blower will run for 90 sec when furnace power is interrupted during a call for heat, R-W closed. 13 LIMIT OR FLAME ROL ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 14

    —14— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 15

    —15— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 16

    A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based f ...

Fabricante Bryant Categoría Furnace

Los documentos del dispositivo Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - que deben facilitarnos los primeros pasos durante el uso de Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)