    NOTE: Read the entire instruction manual before performing any service or maintenance. This symbol → indicates a change since the last issue. These procedures are for size 44,000 through 154,000 Btuh input units. Index Page SAFETY CONSIDERATIONS ..................................................1-2 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCED ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 2

    WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User’s Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSS ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 3

    1. Downflow/Horizontal Each furnace requires 2 filters which are installed in the return-air duct. (See Fig. 4 and 5.) To remove filters for cleaning or replacement, proceed as follows: a. Disconnect electrical power before removing blower access door. b. Remove screw from front of door and remove blower access door. c. Reach up behind top plate, t ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 4

    9. If a greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel: a. Mark blower wheel location on shaft before disassembly to ensure proper reassembly. b. Loosen setscrew holding blower wheel on motor shaft. NOTE: Mark blower mounting arms, motor, and blower housing ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 5

    WARNING: Blower access door switch opens 115-v power to furnace control. No component operation can occur. Caution must be taken when manually closing this switch for service purposes. Failure to follow this warn- ing could result in electrical shock, personal injury, or death. NOTE: If thermostat terminals are jumpered before blower ac- cess door ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 6

    (8.) Reinstall cell inlet plates and burner assembly. Care must be exercised to center burners in cell openings. 11. Clean flame sensor with fine steelwool. 12. Remove old sealant from center panel and collector box flange and apply new sealant to collector box flange and reinstall on center panel, making sure all 8 screws are secure. NOTE: A relea ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 7

    c. Remove control access door. d. BRIEFLY remove either wire from the main limit switch until LED goes out, then reconnect it. NOTE: If wire to main limit is disconnected longer than 4 sec, main blower starts, and retrieval request is ignored. 2. When above items have been completed, the following will occur: a. LED flashes a status code 4 times. R ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 8

    Fig. 11—Furnace Control A99255 HUMIDIFIER TERMINAL (24-V AC 0.5 AMP MAX) LED OPERA TION & DIAGNOSTIC LIGHT HARNESS CONNECT OR 24-V TRANSFORMER SEC-2 SP ARE-1 SP ARE-2 EAC-1 EAC-ELECTR ONIC AIR CLEANER TERMINALS (115-V AC 1.0 AMP MAX) EAC-2 115-V AC (L2) NEUTRAL CONNECTION 24-V THERMOST A T TERMINALS BLOWER SPEED SELECTION TERMINALS INDUCER MO ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 9

    → Fig. 12—Furnace Wiring Diagram A00304 PCB BLOWER OFF DELAY SELECTION CHART 90 SEC 135 SEC 180 SEC 225 SEC GVR H I/L O RELA Y SEC-1 SEC-2 PL1 3 2 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DELAY G R Y W C HUM HSI R I DR BLWR BLOWER SPEED SELECT FU1 COOL HEA T L2 PL3 PL2 VAC 120 L1 PR1 1 2 1 2 3 PR2 24 VAC -3A FUSE SP A RE-2 SP ARE-1 EAC-1 EAC-2 C 1 ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 10

    Fig. 13—Service Label A96263 SERVICE 11 NO PREVIOUS CODE - Stored sta tus codes are er ased when power (115 V or 24V) to control is interrupted or 48 hours after ea ch fault is cl eared. 12 BLOWER ON AFTER POWER UP ( 115V or 24V) - Blower ru ns for 90 seconds, if unit is power ed up duri ng a call for hea t (R-W closed). 13 LI MIT OR FLAM E ROLL- ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 11

    —11— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 12

    Is circuit breaker closed? Close door switch and go to start. Is red LED status light on? Is door switch closed? Is red LED status light blinking rapidly without a pause? Is there 1 15v going to switch? Replace door switch. Replace control center . Replace transformer . Is red LED status light blinking ON/OFF slowly with a combination of short and ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 13

    11 NO PREVIOUS F AUL T - Faults are erased after 48 hrs or whenever power (1 15v or 24v) is interrupted. Run system through a heating or cooling cycle to check system. 12 BLO WER ON AFTER PO WER UP (115V OR 24V) - Normal operation. Blower will run for 90 sec when furnace power is interrupted during a call for heat, R-W closed. 13 LIMIT OR FLAME ROL ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 14

    —14— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 15

    —15— ...

  • Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - page 16

    A94328 SERVICE TRAINING Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based f ...

Fabbricante Bryant Categoria Furnace

I documenti che otteniamo dal fabbricante del dispositivoBryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, manuali di manutenzione, brevi manuali o manuali utente Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant GAS-FIRED INDUCED-COUSTION FURNACES 373LAV è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)