  • Bryant 561C - page 1

    Form No. PDS 561C.18.6 ELECTRIC AIR CONDITIONER 561C (60 Hz) Sizes 018 thru 060 Model 561C Energy-Efficient Air Conditioners incor porate inno- vativ e technology to provide reliab le summer cooling perfor- mance. Built into these units are the f eatures most desired by homeowners toda y including SEER ratings of up to 11.5 when used with componen ...

  • Bryant 561C - page 2

    —2— DIMENSIONS—561C A97017 AIR IN NOTES: 1. Allow 30 in. clearance to service side of unit, 48 in. above unit, 6 in. on one side, 12 in.  on remaining side, and 24 in. between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55 ° F, max. 125 ° F. 3. Series designation is the 14th position of t ...

  • Bryant 561C - page 3

    —3— CHECK-FLO-RA TER® PIST ON CHART * Piston listed is f or any approv ed coil non-capillar y tube combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil. RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. SOUND PO WER ...

  • Bryant 561C - page 4

    —4— SPECIFICA TIONS See notes on page 7. UNIT SIZE-SERIES 561C018-A, D 561C024-A, D 561C030-A, D 561C030-A Operating W eight (Lb) 113/115 115/117 124/133 124 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 Operating V oltage Range* 197—253 187—253 Compressor— Rated Load Amps 9.6/9.0 10.7/11.6 14.2/14.8 9.4 Lock ed ...

  • Bryant 561C - page 5

    —5— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C036-A, B, E 561C036-B, D 561C036-B 561C042-A, B 561C042-B, C 561C042-B Operating W eight (Lb) 129/138/138 129/133 133 138/142 142 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 460—60—3 208-230—60—1 208/230—60—3 460—60—3 Operating V ...

  • Bryant 561C - page 6

    —6— SPECIFICA TIONS Continued See notes on page 7. UNIT SIZE-SERIES 561C048-A, B 561C048-B, C 561C060-A, B 561C060-B, E Operating W eight (Lb) 192/198 233/218 ELECTRICAL Unit V olts—Hertz—Phase 208-230—60—1 208/230—60—3 460—60—3 208-230—60—1 208/230—60—3 460—60—3 Operating V oltage Range* 197—253 187—253 414—50 ...

  • Bryant 561C - page 7

    —7— * P er missible limits of the v oltage range at which unit will operate satisf actor ily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30°C (86°F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cable (NM), trade name R OMEX, shall be t ...

  • Bryant 561C - page 8

    —8— A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 9. High-Pressure Switch Auto reset SPST s witch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to l ...

  • Bryant 561C - page 9

    —9— COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 018-A, D CC5A/CD5AA018* 17,200 NONE — 10.00 10.00 9.20 CC5A/CD5AA024 17,600 NONE 10.00 10.50 10.50 9.45 CC5A/CD5A W024 17,600 N ...

  • Bryant 561C - page 10

    —10— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 030-A, D CD5A/CD5AA030* 28,000 NONE 10.00 10.10 10.10 9.10 CC5A/CD5AA036 29,000 NONE 10.00 10.10 10.10 9.30 CC5A/CD5A ...

  • Bryant 561C - page 11

    —11— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK3BA036 33,800 NONE 10.00 10.20 10.20 9.20 CK3BA042 33,800 NONE 10.00 10.20 10.20 9.20 CK5A/CK5BA036 ...

  • Bryant 561C - page 12

    —12— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 036-A, B, D , E CK5A/CK5BA042 33,400 TDR 10.80 — 10.80 10.00 CK5A/CK5BT042 33,400 TDR 10.80 — 10.80 10.00 CK5A/CK5 ...

  • Bryant 561C - page 13

    —13— COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL T OT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST AND ARD RA TING BR Y ANT GAS FURNA CE OR A CCESSOR Y TDR† A CCESSOR Y TXV‡ EERA 042-A, B, C COILS + 355MA V060100 V ARIABLE-SPEED FURNACE CC5A/CD5AA042 40,000 TDR 10.50 — 10.50 9.45 CC5A/CD5AC048 ...

  • Bryant 561C - page 14

    —14— COMBINA TION RA TINGS Continued * T ested Combination. † In most cases, only 1 method should be used to achie v e TDR function. Using more than 1 method in a system ma y cause degradation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. All Br yant furnaces are equipped with TDR exc ...

  • Bryant 561C - page 15

    —15— DET AILED COOLING CAP A CITIES* See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys K ...

  • Bryant 561C - page 16

    —16— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 17

    —17— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 18

    —18— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 19

    —19— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 20

    —20— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 21

    —21— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 22

    —22— DETAILED COOLING CAPACITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ota ...

  • Bryant 561C - page 23

    —23— DET AILED COOLING CAP A CITIES* Continued See notes on page 24. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES °F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T otal Sys KW** Capacity MBtuh† T ...

  • Bryant 561C - page 24

    —24— DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity ma y occur . † T otal and sensible capacities are net capacities . B ...

  • Bryant 561C - page 25

    —25— CONDENSER ONL Y RA TINGS* See notes on page 26. SST °F CONDENSER ENTERING AIR TEMPERA TURES °F 55 65 75 85 95 105 115 125 561C018-A, D 30 TCG 17.6 16.2 14.7 13.4 12.0 10.7 9.52 8.35 KW 1.37 1.49 1.58 1.66 1.73 1.77 1.80 1.82 SDT 75.6 86.1 96.4 106.0 116.0 126.0 136.0 146.0 35 TCG 19.6 18.1 16.6 15.1 13.6 12.3 10.9 9.68 KW 1.40 1.52 1.63 ...

  • Bryant 561C - page 26

    —26— CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table . KW — T otal Po wer (Kw) SDT — Saturated T emperature Leaving Compressor (°F) SST — Saturated T emperature Entering Compressor (°F) TCG — Gross Cooling Capacity (1000 Btuh) SST °F CONDENSER ENTERING AIR TEMPERA TURE ...

  • Bryant 561C - page 27

    —27— SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w-ambient operation accessor y is 55°F (12.8°C). 3. Maximum outdoor operating air temperature is 125°F (51.7°C). 4. For reli ...

  • Bryant 561C - page 28

    —2 8— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels PDS 561C.18.5 © 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5256-108 11-99 GUIDE SPECIFICA TIONS GENERAL System Description Outdoor-mounted, air-coo ...

Fabricante Bryant Categoría Air Conditioner

Los documentos del dispositivo Bryant 561C que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones 561C
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant 561C
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant 561C.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant 561C, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant 561C. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant 561C.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant 561C, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant 561C. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant 561C.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant 561C - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant 561C, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant 561C que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant 561C - que deben facilitarnos los primeros pasos durante el uso de Bryant 561C
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant 561C
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bryant 561C en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bryant 561C?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bryant 561C, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bryant 561C probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)