    Form No. PDS 591B.18.1 DELUXE 11 SEER AIR CONDITIONER WITH PURON ® (R-410A) 591B (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Br y- ant’ s unique Puron refr igerant. The en vironmental ...

  • Bryant DELUXE 11 SEER R-410A - page 2

    —2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOL ...

  • Bryant DELUXE 11 SEER R-410A - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Application Guideline and Ser vice Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is f or any approv ed non-capillar y tube coil combination. Piston is shipped with outdoor unit and must be installed i ...

  • Bryant DELUXE 11 SEER R-410A - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating W eight (Lb) 168 178 188 198 ELECTRICAL Unit V olts — Hertz — Phase 208/230-60-1 Operating V oltage Range* 187-253 Compressor — Rated Load Amps 10.3 13.5 15.4 17.9 Lock ed Rotor Amps 51.0 61.0 73.0 100.0 Condenser F an Motor — Full Load Amps 0. ...

  • Bryant DELUXE 11 SEER R-410A - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actorily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab ...

  • Bryant DELUXE 11 SEER R-410A - page 6

    — 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Application Guideline and Service Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and MotorMaster ® Control only . A CCESSO ...

  • Bryant DELUXE 11 SEER R-410A - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The contr ...

  • Bryant DELUXE 11 SEER R-410A - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.5 11.0 11.0 9.95 CC5A/CD5AA018 17,000 NONE 10.5 11.0 11.0 9.75 CC5A/CD5A W024 17,400 NONE 10. ...

  • Bryant DELUXE 11 SEER R-410A - page 9

    — 9 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.5 — 11.5 10.40 CE3AA030 23,800 TDR 11.5 — 11.5 10.60 CK5A/CK5BW024 23,400 TDR 11.5 — ...

  • Bryant DELUXE 11 SEER R-410A - page 10

    — 10 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A CC5A/CD5AA042* 35,400 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA036 35,000 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA042 35,40 ...

  • Bryant DELUXE 11 SEER R-410A - page 11

    — 11 — COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A COILS + 355MA V060080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 35,400 TDR 11.5 — 11.5 10.35 CC5A/CD5A W036 35,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 12

    — 12 — UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 042-A CE3AA042 40,000 TDR 11.5 — 11.5 10.30 CE3AA048 40,500 TDR 11.5 — 11.5 10.35 CK5A/CK5BA042 40,000 TDR 11.5 — 11.5 10.40 CK5A/CK5BT042 40,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 13

    — 13 — See notes on page 14. . UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 048-A CE3AA060 47,000 TDR 11.5 — 11.5 10.65 CK3BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BT060 47, ...

  • Bryant DELUXE 11 SEER R-410A - page 14

    — 14 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degradation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ Based on computer simulati ...

  • Bryant DELUXE 11 SEER R-410A - page 15

    — 15 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 16

    — 16 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 17

    — 17 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 18

    — 18 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 19

    — 19 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 20

    — 20 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 21

    — 21 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 22

    — 22 — DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities. B ...

  • Bryant DELUXE 11 SEER R-410A - page 23

    — 23 — CONDENSER ONL Y RA TINGS* See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.90 73.70 0.77 15.00 83.10 0.92 14.20 92.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.40 120.80 1.71 10.40 130.20 1.95 9.30 139.50 2.20 35 TCG SDT KW 17.50 75.30 0.79 16.60 84.60 0.94 ...

  • Bryant DELUXE 11 SEER R-410A - page 24

    — 24 — CONDENSER ONL Y RA TINGS* Continued See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.70 77.00 1.99 30.90 86.20 2.23 29.10 95.40 2.49 27.30 104.60 2.77 25.40 113.80 3.09 23.50 122.90 3.43 21.50 132.00 3.79 19.40 140.90 4.19 35 TCG SDT KW 36.00 78.70 2.01 34.00 ...

  • Bryant DELUXE 11 SEER R-410A - page 25

    — 25 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temper ature without lo w-ambient oper ation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor oper ating air temper ature is 125 ° F ...

  • Bryant DELUXE 11 SEER R-410A - page 26

    — 26 — MA TCHED SYSTEM A98599 ...

  • Bryant DELUXE 11 SEER R-410A - page 27

    — 27 — ...

  • Bryant DELUXE 11 SEER R-410A - page 28

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No. 5259-100 9-01 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-cooled, split-s ...

Fabricante Bryant Categoría Air Conditioner

Los documentos del dispositivo Bryant DELUXE 11 SEER R-410A que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones DELUXE 11 SEER R-410A
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant DELUXE 11 SEER R-410A
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant DELUXE 11 SEER R-410A.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant DELUXE 11 SEER R-410A, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant DELUXE 11 SEER R-410A. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant DELUXE 11 SEER R-410A.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant DELUXE 11 SEER R-410A, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant DELUXE 11 SEER R-410A. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant DELUXE 11 SEER R-410A.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant DELUXE 11 SEER R-410A - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant DELUXE 11 SEER R-410A, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant DELUXE 11 SEER R-410A que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant DELUXE 11 SEER R-410A - que deben facilitarnos los primeros pasos durante el uso de Bryant DELUXE 11 SEER R-410A
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant DELUXE 11 SEER R-410A
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bryant DELUXE 11 SEER R-410A en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bryant DELUXE 11 SEER R-410A?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bryant DELUXE 11 SEER R-410A, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bryant DELUXE 11 SEER R-410A probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)