Manuale per l’uso Bryant DELUXE 11 SEER R-410A

28 pagine 1.64 mb
Scarica

Vai alla pagina of 28

Summary
  • Bryant DELUXE 11 SEER R-410A - page 1

    Form No. PDS 591B.18.1 DELUXE 11 SEER AIR CONDITIONER WITH PURON ® (R-410A) 591B (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Br y- ant’ s unique Puron refr igerant. The en vironmental ...

  • Bryant DELUXE 11 SEER R-410A - page 2

    —2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOL ...

  • Bryant DELUXE 11 SEER R-410A - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Application Guideline and Ser vice Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is f or any approv ed non-capillar y tube coil combination. Piston is shipped with outdoor unit and must be installed i ...

  • Bryant DELUXE 11 SEER R-410A - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating W eight (Lb) 168 178 188 198 ELECTRICAL Unit V olts — Hertz — Phase 208/230-60-1 Operating V oltage Range* 187-253 Compressor — Rated Load Amps 10.3 13.5 15.4 17.9 Lock ed Rotor Amps 51.0 61.0 73.0 100.0 Condenser F an Motor — Full Load Amps 0. ...

  • Bryant DELUXE 11 SEER R-410A - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actorily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab ...

  • Bryant DELUXE 11 SEER R-410A - page 6

    — 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Application Guideline and Service Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and MotorMaster ® Control only . A CCESSO ...

  • Bryant DELUXE 11 SEER R-410A - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The contr ...

  • Bryant DELUXE 11 SEER R-410A - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.5 11.0 11.0 9.95 CC5A/CD5AA018 17,000 NONE 10.5 11.0 11.0 9.75 CC5A/CD5A W024 17,400 NONE 10. ...

  • Bryant DELUXE 11 SEER R-410A - page 9

    — 9 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.5 — 11.5 10.40 CE3AA030 23,800 TDR 11.5 — 11.5 10.60 CK5A/CK5BW024 23,400 TDR 11.5 — ...

  • Bryant DELUXE 11 SEER R-410A - page 10

    — 10 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A CC5A/CD5AA042* 35,400 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA036 35,000 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA042 35,40 ...

  • Bryant DELUXE 11 SEER R-410A - page 11

    — 11 — COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A COILS + 355MA V060080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 35,400 TDR 11.5 — 11.5 10.35 CC5A/CD5A W036 35,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 12

    — 12 — UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 042-A CE3AA042 40,000 TDR 11.5 — 11.5 10.30 CE3AA048 40,500 TDR 11.5 — 11.5 10.35 CK5A/CK5BA042 40,000 TDR 11.5 — 11.5 10.40 CK5A/CK5BT042 40,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 13

    — 13 — See notes on page 14. . UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 048-A CE3AA060 47,000 TDR 11.5 — 11.5 10.65 CK3BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BT060 47, ...

  • Bryant DELUXE 11 SEER R-410A - page 14

    — 14 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degradation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ Based on computer simulati ...

  • Bryant DELUXE 11 SEER R-410A - page 15

    — 15 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 16

    — 16 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 17

    — 17 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 18

    — 18 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 19

    — 19 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 20

    — 20 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 21

    — 21 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 22

    — 22 — DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities. B ...

  • Bryant DELUXE 11 SEER R-410A - page 23

    — 23 — CONDENSER ONL Y RA TINGS* See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.90 73.70 0.77 15.00 83.10 0.92 14.20 92.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.40 120.80 1.71 10.40 130.20 1.95 9.30 139.50 2.20 35 TCG SDT KW 17.50 75.30 0.79 16.60 84.60 0.94 ...

  • Bryant DELUXE 11 SEER R-410A - page 24

    — 24 — CONDENSER ONL Y RA TINGS* Continued See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.70 77.00 1.99 30.90 86.20 2.23 29.10 95.40 2.49 27.30 104.60 2.77 25.40 113.80 3.09 23.50 122.90 3.43 21.50 132.00 3.79 19.40 140.90 4.19 35 TCG SDT KW 36.00 78.70 2.01 34.00 ...

  • Bryant DELUXE 11 SEER R-410A - page 25

    — 25 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temper ature without lo w-ambient oper ation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor oper ating air temper ature is 125 ° F ...

  • Bryant DELUXE 11 SEER R-410A - page 26

    — 26 — MA TCHED SYSTEM A98599 ...

  • Bryant DELUXE 11 SEER R-410A - page 27

    — 27 — ...

  • Bryant DELUXE 11 SEER R-410A - page 28

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No. 5259-100 9-01 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-cooled, split-s ...

Fabbricante Bryant Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoBryant DELUXE 11 SEER R-410A possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso DELUXE 11 SEER R-410A
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant DELUXE 11 SEER R-410A
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant DELUXE 11 SEER R-410A.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant DELUXE 11 SEER R-410A, manuali di manutenzione, brevi manuali o manuali utente Bryant DELUXE 11 SEER R-410A. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant DELUXE 11 SEER R-410A.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant DELUXE 11 SEER R-410A, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant DELUXE 11 SEER R-410A dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant DELUXE 11 SEER R-410A.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant DELUXE 11 SEER R-410A - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant DELUXE 11 SEER R-410A, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant DELUXE 11 SEER R-410A che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant DELUXE 11 SEER R-410A - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant DELUXE 11 SEER R-410A
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant DELUXE 11 SEER R-410A
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant DELUXE 11 SEER R-410A in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant DELUXE 11 SEER R-410A?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant DELUXE 11 SEER R-410A con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant DELUXE 11 SEER R-410A è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)