Bryant DELUXE 11 SEER R-410Aの取扱説明書

28ページ 1.64 mb
ダウンロード

ページに移動 of 28

Summary
  • Bryant DELUXE 11 SEER R-410A - page 1

    Form No. PDS 591B.18.1 DELUXE 11 SEER AIR CONDITIONER WITH PURON ® (R-410A) 591B (60 Hz) Sizes 018 thru 060 Br yant’ s Quantum Plus 591B with Puron® provides features which cannot be matched by any other family of equipment. The 591B is a Quantum Plus air conditioning system utilizing Br y- ant’ s unique Puron refr igerant. The en vironmental ...

  • Bryant DELUXE 11 SEER R-410A - page 2

    —2— DIMENSIONS AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW. 2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOL ...

  • Bryant DELUXE 11 SEER R-410A - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS * For tube sets g reater than 50 ft, consult Application Guideline and Ser vice Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. CHECK-FLO-RA TER ® PISTON * Piston listed is f or any approv ed non-capillar y tube coil combination. Piston is shipped with outdoor unit and must be installed i ...

  • Bryant DELUXE 11 SEER R-410A - page 4

    — 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE-SERIES 018-A 024-A 030-A 036-A Operating W eight (Lb) 168 178 188 198 ELECTRICAL Unit V olts — Hertz — Phase 208/230-60-1 Operating V oltage Range* 187-253 Compressor — Rated Load Amps 10.3 13.5 15.4 17.9 Lock ed Rotor Amps 51.0 61.0 73.0 100.0 Condenser F an Motor — Full Load Amps 0. ...

  • Bryant DELUXE 11 SEER R-410A - page 5

    — 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will oper ate satisf actorily . Oper ation outside these limits may result in unit f ailure. † If wire is applied at ambient g reater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab ...

  • Bryant DELUXE 11 SEER R-410A - page 6

    — 6 — A CCESSOR Y USA GE GUIDELINE * For tubing line sets g reater than 50 ft, refer to Application Guideline and Service Manual — Air Conditioning and Heat Pumps Using Puron ® Refrigerant. † Only when low-pressure s witch is used. ‡ Required for lo w-ambient controller (full modulation feature) and MotorMaster ® Control only . A CCESSO ...

  • Bryant DELUXE 11 SEER R-410A - page 7

    — 7 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) Continued 10. Low-Ambient Pressure Switc h A long life pressure s witch which is mounted to outdoor unit service valve . It is designed to cycle the outdoor f an motor in order to maintain head pressure within normal operating limits (approximately 200 psig to 365 psig). The contr ...

  • Bryant DELUXE 11 SEER R-410A - page 8

    — 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 018-A CC5A/CD5AA024* 17,400 NONE 10.5 11.0 11.0 9.95 CC5A/CD5AA018 17,000 NONE 10.5 11.0 11.0 9.75 CC5A/CD5A W024 17,400 NONE 10. ...

  • Bryant DELUXE 11 SEER R-410A - page 9

    — 9 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 024-A CE3AA024 23,400 TDR 11.5 — 11.5 10.40 CE3AA030 23,800 TDR 11.5 — 11.5 10.60 CK5A/CK5BW024 23,400 TDR 11.5 — ...

  • Bryant DELUXE 11 SEER R-410A - page 10

    — 10 — COMBINA TION RA TINGS Continued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A CC5A/CD5AA042* 35,400 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA036 35,000 NONE 10.5 11.0 11.0 9.70 CC5A/CD5AA042 35,40 ...

  • Bryant DELUXE 11 SEER R-410A - page 11

    — 11 — COMBINA TION RA TINGS Continued UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 036-A COILS + 355MA V060080 V ARIABLE SPEED FURNA CE CC5A/CD5AA042 35,400 TDR 11.5 — 11.5 10.35 CC5A/CD5A W036 35,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 12

    — 12 — UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 042-A CE3AA042 40,000 TDR 11.5 — 11.5 10.30 CE3AA048 40,500 TDR 11.5 — 11.5 10.35 CK5A/CK5BA042 40,000 TDR 11.5 — 11.5 10.40 CK5A/CK5BT042 40,000 TDR 11.5 — 11.5 10 ...

  • Bryant DELUXE 11 SEER R-410A - page 13

    — 13 — See notes on page 14. . UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F A CTOR Y- SUPPLIED ENHANCE- MENT SEER EER Standard Rating Bryant Gas Furnace or Accessory TDR † Accessory Puron TXV 048-A CE3AA060 47,000 TDR 11.5 — 11.5 10.65 CK3BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BA060 47,000 TDR 11.5 — 11.5 10.65 CK5A/CK5BT060 47, ...

  • Bryant DELUXE 11 SEER R-410A - page 14

    — 14 — * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system ma y cause degradation in perf or mance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a furnace equipped with TDR. Most Br yant furnaces are equipped with TDR. ‡ Based on computer simulati ...

  • Bryant DELUXE 11 SEER R-410A - page 15

    — 15 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 16

    — 16 — DET AILED COOLING CAP A CITIES* See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys ...

  • Bryant DELUXE 11 SEER R-410A - page 17

    — 17 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 18

    — 18 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 19

    — 19 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 20

    — 20 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 21

    — 21 — DET AILED COOLING CAP A CITIES* Continued See notes on page 22. EV AP AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † T otal Sys Kw** Capacity MBtuh † ...

  • Bryant DELUXE 11 SEER R-410A - page 22

    — 22 — DET AILED COOLING CAP A CITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length and/or indoor unit is located abov e outdoor unit, a slight variation in capacity may occur . † T otal and sensible capacities are net capacities. B ...

  • Bryant DELUXE 11 SEER R-410A - page 23

    — 23 — CONDENSER ONL Y RA TINGS* See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN018-A 30 TCG SDT KW 15.90 73.70 0.77 15.00 83.10 0.92 14.20 92.60 1.10 13.30 102.00 1.28 12.30 111.40 1.49 11.40 120.80 1.71 10.40 130.20 1.95 9.30 139.50 2.20 35 TCG SDT KW 17.50 75.30 0.79 16.60 84.60 0.94 ...

  • Bryant DELUXE 11 SEER R-410A - page 24

    — 24 — CONDENSER ONL Y RA TINGS* Continued See notes on page 25. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 125 591BN036-A 30 TCG SDT KW 32.70 77.00 1.99 30.90 86.20 2.23 29.10 95.40 2.49 27.30 104.60 2.77 25.40 113.80 3.09 23.50 122.90 3.43 21.50 132.00 3.79 19.40 140.90 4.19 35 TCG SDT KW 36.00 78.70 2.01 34.00 ...

  • Bryant DELUXE 11 SEER R-410A - page 25

    — 25 — SYSTEM DESIGN SUMMAR Y 1. Intended f or outdoor installation with free air inlet and outlet. Outdoor f an external static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor oper ating air temper ature without lo w-ambient oper ation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor oper ating air temper ature is 125 ° F ...

  • Bryant DELUXE 11 SEER R-410A - page 26

    — 26 — MA TCHED SYSTEM A98599 ...

  • Bryant DELUXE 11 SEER R-410A - page 27

    — 27 — ...

  • Bryant DELUXE 11 SEER R-410A - page 28

    SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 — 28 — PRINTED IN U.S.A. Catalog No. 5259-100 9-01 GUIDE SPECIFICATIONS GENERAL System Description Outdoor-mounted, air-cooled, split-s ...

メーカー Bryant カテゴリー Air Conditioner

Bryant DELUXE 11 SEER R-410Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- DELUXE 11 SEER R-410Aの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant DELUXE 11 SEER R-410Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant DELUXE 11 SEER R-410Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant DELUXE 11 SEER R-410Aの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant DELUXE 11 SEER R-410Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant DELUXE 11 SEER R-410Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant DELUXE 11 SEER R-410Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant DELUXE 11 SEER R-410Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant DELUXE 11 SEER R-410Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant DELUXE 11 SEER R-410Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant DELUXE 11 SEER R-410Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant DELUXE 11 SEER R-410Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant DELUXE 11 SEER R-410Aデバイスの基本機能を使うにあたってのヒント。 Bryant DELUXE 11 SEER R-410Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant DELUXE 11 SEER R-410Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant DELUXE 11 SEER R-410Aのメーカー/サービスへの連絡先に関する情報。

Bryant DELUXE 11 SEER R-410Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant DELUXE 11 SEER R-410Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant DELUXE 11 SEER R-410Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)