Bryant 502Aの取扱説明書

16ページ 0.69 mb
ダウンロード

ページに移動 of 16

Summary
  • Bryant 502A - page 1

    F or m No . PD S 502A. 24.1 HORIZONT AL INDOOR SINGLE P A CKA GE COOLING UNITS Single P ac kage Coo ling Un its F eaturing: • compac t design • flexibili ty • eas y main tena nce • high qu ality and rel iability • quiet and effic ient scroll co mpressor techn olog y FEA TURES /BENEF ITS All in o ne pac kage — high coo ling efficie ncy , ...

  • Bryant 502A - page 2

    2 T ABLE OF CONTENTS Pa g e F eatures/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Model Nu mber Nome nclature . . . . . . . . . . . . . . . . . . . . . . . . . 2 ARI Capacit y Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ph ysical Data . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Bryant 502A - page 3

    3 PHYSICAL D A T A LEGEND *Shipping weights include base unit plus packaging. † If components are to be split, additional refrigerant will be needed. **Use T ype L copper only . NO TE: If components are to be split, the maxim um length of refrigerant tubing to be used is 50 equivalent ft, assuming components will be installed in same horizontal p ...

  • Bryant 502A - page 4

    4 FIELD-INST ALLED A CCESSORIES Thermo stat and Subbase — Attract i v e wall-mo unted 24-v access or y provi des pr eci se te mperat ure c ontr ol. Auto matic and Manu al changeo ver mo dels av ailab le. A thermostat s ubbase is av ailab le that works w ith Cycle-L OC ™ circuitr y . If a saf ety device tr ips, comp ress or lo cks out and subbas ...

  • Bryant 502A - page 5

    5 B ASE UNI T DIMENSION S DIMENSIONS (ft-in.) UNIT 502A ABCDE 024 2-5 2-1 5 / 8 1- 5 3 / 4 1-2 1-1 036 2-4 3 / 4 2-2 1- 5 3 / 4 1-2 1-1 048 2-5 2-3 1-11 5 / 8 1-8 7 / 8 1-7 7 / 8 060 2-4 3 / 4 2-2 3 / 4 1-11 5 / 8 1-8 7 / 8 1-7 7 / 8 Unit Compone nt Locations ...

  • Bryant 502A - page 6

    6 SELECTION PROCEDURE (with e xample) I DETERMINE COO LING REQUIREMENTS A T DESIGN CONDITIONS. Given: Gross C ooling Capacity Required (TC) . . . . . . . . . . . . . . . . . . . . . . . . . 39,00 0 Btuh Sensib le Heat Capaci ty (SHC) . . . . . . . . . . . . 30,50 0 Btuh T emperature of Air Entering Condenser . . . . . . . . . . . 95 F T emperature ...

  • Bryant 502A - page 7

    7 PERFORMANCE D A T A (cont) GROSS COOLING CAP A CITIES (cont) LEGEND NO TES: 1. Perf or m ance based on nomin al conden ser airflow l isted in physical da ta table on page 3 . 2. SHC is ba sed on 80 F db te mperature of air e nteri ng the co il. Below 80 F db, subtract (corr factor x cfm) from SHC. Above 80 F db , add (co rr factor x cfm) t o SHC. ...

  • Bryant 502A - page 8

    8 PERFORMANCE D A T A (cont) BEL T DRIVE EV APORA T OR F AN PERFORMANCE (Spec ial Or der Only , Pricing an d or dering on related pri ce pages.) LEGEND NO TE: Pulley setting must be adjusted to limit cfm to 450 cfm/ton maximum. Unit operation bey ond that limit may result in blo w-off and condensate problems . CONDENSER F AN PERFORMANCE LEGEND kW ? ...

  • Bryant 502A - page 9

    9 CONTR OLS OPERA TING SEQUENCE Cooling 1. The r mosta t call s f or co oling . a. Indoor (e v aporator) f an rela y is energiz ed and starts e vap orato r f an. b . Compr essor contact or is energiz ed to star t compre ssor and conde nser fa n (up to a 5-min ute dela y on single- phase u nits). 2. When room the r mostat is satisfi ed, the e v apor ...

  • Bryant 502A - page 10

    10 ELECTRICAL D A T A (cont) ELECTRIC HEA TER ST A TIC PRESSURE DR O P (in. wg) NO TE: Abov e el ectric he aters are not UL or CSA listed f or use with optional hi gh-static ev apora tor-f an motor (048, 060 units only). TYPICAL WIRING SCHEMA TICS ELEC TRIC H EA TER UNIT 88EN UNIT 502A MIN CFM UNIT CFM 600 800 1000 1200 1400 1600 1800 2000 2200 005 ...

  • Bryant 502A - page 11

    11 TYPICAL WIRING SCHEMA TICS (cont) LEGEND AHA — Adjustab le Heat Anticipator C — Contactor Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Com pensator CDT — Compressor Discharge T hermostat COMP — Comp ressor M otor EQUIP — Equip ment FU — Fuse GND — Ground HPS — High-Pressure Switch HR — Heater Relay IFC — ...

  • Bryant 502A - page 12

    12 TYPICAL WIRING SCHEMA TICS (cont) LEGEND AHA — Adjustab le Heat Anticipator C — Contactor Compressor CAP — Capacitor CB — Circuit Breaker CC — Cooling Com pensator CDT — Compressor Discharge T hermostat CH — Crankcase Hea ter COMP — Comp ressor M otor EQUIP — Equip ment GND — Ground HPS — High-Pressure Switch HR — Heater ...

  • Bryant 502A - page 13

    13 TYPICAL WIRING SCHEMA TICS (cont) LEGEND AHA — Adjustab le Heat Anticipator BKR W/A T — Breaks wit h Amp T urns C — Contactor Compressor CC — Cooling Com pensator CLO — Comp ressor L ockou t COMP — Comp ressor M otor CT — Current T ransf ormer EQUIP — Equip ment GND — Ground HPS — High-Pressure Switch IFC — Indoor -Fan Cont ...

  • Bryant 502A - page 14

    14 TYPICAL PIPING AND WIRING APPLICA TION D A T A OUTDOOR-AIR TEMPERA T URE OPERA TING LIMIT S (F) Field Splitting Ins tructions — If c omp onen ts ar e s plit , ma xi- mum length of ref rigerant tubing to be us ed is 50 ft, as suming compon ents are ins talled in same hor iz ontal pl ane. Co ndenser ma y be moun ted up to 12-ft a bov e e va pora ...

  • Bryant 502A - page 15

    15 GUIDE S PECIFICA TIONS INDOOR P A CKA GED UNIT HV AC GUIDE SPECIFICA TIONS — SECTION 157 87 SIZE RANGE: 2 T O 5 T ONS, NOMINAL BR Y ANT MODEL NUMBER: 502A PA R T 1 — GENERAL 1.01 SYSTEM DESCRIPTION Indoor mo unted, electrically c ontrolled pac kaged horizon- tal coo ling unit uti lizing a her metic typ e scroll compre ssor . 1.02 QU ALITY AS ...

  • Bryant 502A - page 16

    Copyright 2001 Bryant Heating & Cooling Systems Printed in U.S . A. 1-01 Catalog No. 5250-200 SPECIFICATIONS SUBJE CT TO CHANGE WITHOUT NOTICE UNIT MUST BE INST ALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS GUIDE SPECIFICA TIONS (cont) 3. Co mpressor Cycle De lay: Pre ven ts compress or from restar ting f or a minimum of 5 min utes after s ...

メーカー Bryant カテゴリー Air Conditioner

Bryant 502Aのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 502Aの取扱説明書
- Bryantの製品カード
- パンフレット
- またはBryant 502Aの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bryant 502Aの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bryant 502Aの取り付け説明書、サービスマニュアル、簡易説明書、またはBryant 502Aのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bryant 502Aの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bryant 502Aデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBryant 502Aを使用するのを助ける技術的文書のことです。説明書は通常、全てのBryant 502Aユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bryantの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bryant 502Aの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBryant 502Aの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bryant 502Aに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bryant 502Aデバイスの基本機能を使うにあたってのヒント。 Bryant 502Aのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bryant 502Aに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBryant 502Aのメーカー/サービスへの連絡先に関する情報。

Bryant 502Aについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBryant 502Aの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBryant 502Aで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)