    FIELDPOINT ™ OPERATING INSTRUCTIONS AND SPECIFICATIONS FP-DO-403 and cFP-DO-403 16-Channel, 5 to 30 V Sinking Digit al Output Module These operating instructions descri be ho w to install and use the National Instruments FP-DO-403 a nd cFP-DO-40 3 digital output modules, referred to inclusi v ely as the [c]FP-DO-403. F or information about config ...

  • National Instruments cFP-DO-403 - page 2

    [c]FP-DO-403 2 ni.com 2. Align the FP-DO-403 alignment slots with the guide rails o n the terminal base. 3. Press firmly to seat the FP-DO-403 on the terminal base. When the module is firmly seated, the te rminal base latch locks it into place. Figure 1. Installing the FP-DO-403 Installing the cFP-DO-403 The cFP-DO-403 mounts on a Compact FieldPoin ...

  • National Instruments cFP-DO-403 - page 3

    © National Instruments Corp. 3 [c]FP-DO-403 Figure 2. Installing the cFP-DO-403 Wiring the [c]FP-DO-403 The FP-TB- x terminal base has conne ctions for each FP-DO-403 output channel and for an external supply to po wer field devices. The cFP-CB- x connector block provides the same connections for the cFP-DO-403. Each channel has one output termina ...

  • National Instruments cFP-DO-403 - page 4

    [c]FP-DO-403 4 ni.com loads on the output channels, up to 2 A per channel. 1 Connect the external po wer supply to multiple V and V SUP terminals and to multiple C and COM terminals as need ed to ensure that the maximum current through any terminal is 2 A or less. Install a 2 A maximum, fast-act ing fuse (F2A 250V) between the external po wer suppl ...

  • National Instruments cFP-DO-403 - page 5

    © National Instruments Corp. 5 [c]FP-DO-403 Figure 3. Wiring for Low-Current Applica tions Wiring for High-Current Applications If your application requires more than 2 A combined current through all channels of the [c]F P-DO-403, wire your application as shown in Figure 4. Install a 2 A maximum, f ast-acting fuse (F2A 250V) in series with each lo ...

  • National Instruments cFP-DO-403 - page 6

    [c]FP-DO-403 6 ni.com Digital Output Circuit The [c]FP-DO-403 digital output ch annels are optically isolated from the rest of the FieldPoint bank . In the ON state, a transistor is turned on between the V OUT terminal and the ex ternal supply (the C and COM terminals). In the OFF stat e, this transistor is turned of f, allowing only a smal l leaka ...

  • National Instruments cFP-DO-403 - page 7

    © National Instruments Corp. 7 [c]FP-DO-403 mount the flyback diode within 18 in. of the load. Figure 5 shows a flyback diode connected to an inductiv e load. Figure 5. Connection to Inductive Load with Flyback Diode Although the [c]FP-DO-403 contains flyback diodes to pre vent excessi vely high voltage from damaging the module, National Instrumen ...

  • National Instruments cFP-DO-403 - page 8

    [c]FP-DO-403 8 ni.com 250 V rms Measurement Cate gory II contin uous isolation, ve rified by 2,300 V rms , 5 s dielectric withst and test. The [c]FP-DO-403 provides double insulation (compliant with IEC 61010-1) for working v oltages of 250 V rms 1 . Safety standards (such as those published by UL and IEC) requir e the use of double insulation betw ...

  • National Instruments cFP-DO-403 - page 9

    © National Instruments Corp. 9 [c]FP-DO-403 •D o not use the [c]FP-DO-403 as the only isolating barrier between human cont act and working v o ltages higher than 250 V rms . • Operate the [c]FP-DO-403 only at or belo w Pollution Degree 2. Pollution De gree 2 means that only nonconductive pollution occurs in most case s. Occasionally , ho wever ...

  • National Instruments cFP-DO-403 - page 10

    [c]FP-DO-403 10 ni.com Caution For Zone 2 applications, install a protection device across the e xternal power supply and the COM terminal. The device must pre vent the external po wer supply voltage from e xceeding 42 V if there is a transient ov ervoltage conditi on. Special Conditions for Hazard ous Locations Use in Europe The [c]FP-DO-403 has b ...

  • National Instruments cFP-DO-403 - page 11

    © National Instruments Corp. 11 [c]FP-DO-403 Power Requirements Power from network module ............ 600 mW Safety Isolat ion Voltage Isolation voltage is v erified by a dielectric withstand te st. Channel to ground Continuous .............. ......... .......... 250 V rms , Measurement Category II Dielectric withstand... ......... ........ 2 ,30 ...

  • National Instruments cFP-DO-403 - page 12

    [c]FP-DO-403 12 ni.com Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for measurement, control, and laboratory use: • IEC 61010-1, EN-61010-1 • UL 61010-1, CSA 61010-1 Note For UL and other safety certif ications, refer to the product label or visit ni.com/certification , ...

  • National Instruments cFP-DO-403 - page 13

    © National Instruments Corp. 13 [c]FP-DO-403 contains the en vironmental regulat ions and directi v es with which NI complies, as well as othe r en vironmental information not included in this document. Waste Electrical and Electronic Equipment (WEEE) EU Customers At the end of their lif e cycle, all products must be sent to a WEEE re c ycling cen ...

  • National Instruments cFP-DO-403 - page 14

    [c]FP-DO-403 14 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint terminal base and connector block operating instructions Go to ni.com/support fo ...

  • National Instruments cFP-DO-403 - page 15

    © 2002–2007 Nati onal Instruments Corp. All rights reserved. 373354C-01 Aug07 National Instruments, NI, n i.com, and LabVIEW are trademarks of National I nstruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments tra demarks. Other product and company names ment ioned herein are trad ...

Fabricante National Instruments Categoría Network Router

Los documentos del dispositivo National Instruments cFP-DO-403 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos National Instruments
- manuales de instrucciones cFP-DO-403
- hojas de producto National Instruments
- folletos informativos
- o etiquetas energéticas National Instruments cFP-DO-403
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones National Instruments cFP-DO-403.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje National Instruments cFP-DO-403, instrucciones de servicio, instrucciones cortas o instrucciones de usuario National Instruments cFP-DO-403. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto National Instruments cFP-DO-403.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo National Instruments cFP-DO-403, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar National Instruments cFP-DO-403. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de National Instruments cFP-DO-403.

El manual de instrucciones completo de National Instruments debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual National Instruments cFP-DO-403 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice National Instruments cFP-DO-403, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de National Instruments cFP-DO-403 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo National Instruments cFP-DO-403 - que deben facilitarnos los primeros pasos durante el uso de National Instruments cFP-DO-403
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con National Instruments cFP-DO-403
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de National Instruments cFP-DO-403 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de National Instruments cFP-DO-403?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con National Instruments cFP-DO-403, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con National Instruments cFP-DO-403 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)