    H EAT R EMOVAL /E NVIRONMENT AL C ONTROL Dr ycooler s - 60 Hz G ENERAL D AT A ...

  • Liebert 60 HZ - page 2

    ...

  • Liebert 60 HZ - page 3

    i T ABLE OF CONTENTS L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 F EATURES AND B ENEF IT S OF L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 S ELECTION P ROCEDU RE . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Liebert 60 HZ - page 4

    ii Figures Figure 1 Drycooler model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 3 Pressure drop correction ...

  • Liebert 60 HZ - page 5

    1 L IEBERT D RYCOOLERS Liebert drycoolers are designed to be used in conjunctio n with water cooled refrigerat ion and air conditioning machines as well as a variety of commercial and industri al applications requiring the rejection of heat from machinery or processes via a cooling fl uid. During periods of low ambient temperatures, drycoolers may ...

  • Liebert 60 HZ - page 6

    2 F EATURES AND B ENEFITS OF L I EBERT D RYCOOLERS Heat Rejection Module The low-profile direct-driv e propelle r-fan type drycoolers utilize optimum circuitry to balance the heat rejec- tion of the corresponding load. Constructed of al uminum with a copper-tube aluminum coil, the unit is quiet and corrosion resistant. Low Noise Level All Liebert d ...

  • Liebert 60 HZ - page 7

    3 S ELECTION P ROCEDURE Table 4 shows the performance specifications for Liebert drycoolers using a 40% by volume ethylene glycol solution at an av erage fluid temperature of 115°F with flow rates from 1.5 to 3 GPM/circuit and at standard air (.0 75 lbs/ft 3 ). Figure 2 and Figure 3 offer correction factors to Table 4 for average fluid temperature ...

  • Liebert 60 HZ - page 8

    4 P ERFORMANCE D AT A T able 4 Drycooler perform ance dat a Model Number GPM Range No. of Circuits MBH/°F Initial Temperature Difference 1.5 GPM/CIR 2.0 GPM/CIR 2.5 GPM/CIR 3.0 GPM/CIR MBH/ITD PD ft. water MBH/ITD PD ft. water MBH /ITD PD ft. water MBH/ITD PD ft. water Standard Models 033 6-12 4* 1 .3 4.2 1.5 6.2 1.6 9.2 1.7 12.8 069 6-12 4 1.8 7. ...

  • Liebert 60 HZ - page 9

    5 Figure 2 Cap acity correct ion factor Figure 3 Pressure drop correction fac tor Quiet-Line Models 040 6-12 4 1.4 7.4 1.5 11.4 1 .6 17.0 1.7 23.5 12-24 8 * 1.6 3.9 1.7 5.9 1.8 8.9 1.8 12.3 057 18-36 1 2* 2.1 3.6 2.2 6.1 2.3 8.6 2.3 11. 9 24-48 16 2.2 3.0 2.3 4.6 2 .3 6.2 2.4 8.6 060 12-24 8 2.2 7.1 2.3 11.3 2.4 16 .6 2.5 23.0 24-48 1 6* 2.4 3.8 2. ...

  • Liebert 60 HZ - page 10

    6 D IMENSIONAL D AT A Figure 4 Dimensional dat a—1-4 fan models Figure 5 Dimensional dat a—6 & 8 fan models Figure 6 T ypical footprint and unit anchor plan Eyebolt s for lif ting condenser pro vided on 4, 6 & 8 fan models only Height to top of fan guard 43-1/8" (1095mm) 37-7/8" (962mm) L C 18" (457mm) 43-3/16" (1097 ...

  • Liebert 60 HZ - page 11

    7 T able 5 Drycooler physic al data Drycooler Model Circuits A B C L #Fans & Motors** Conn FNPT In/Out Standard Models -033 any 42 - 44 51.5 1 3/4 -069 any 42 - 44 51.5 1 1-1/4 -092 any 42 - 44 51.5 1 1-1/2 -109 any 42 - 44 51.5 1 2 -112 any 42 - 44 51.5 1 2 -139 any 82 - 84 91.5 2 2 -174 any 82 - 84 91.5 2 2 -197 any 82 - 84 91.5 2 2 -225 any ...

  • Liebert 60 HZ - page 12

    8 E LECTRICAL D AT A T able 6 Drycooler electrical dat a # of F a n s 123468 Model # 33,69,92,109,112 139,174,197,22 5 260,310,350 352,419,466,491 620,650,700 790,880,940 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/60 0.75 1 11.6 13.5 20.0 - - - - - - - - - - - - - - - - - - - - 0.75 3 ...

  • Liebert 60 HZ - page 13

    9 T able 7 Drycooler electrical dat a—Quietline models # of F a n s 123468 Model # 40,57,6 0 80,111,121 158,173,178 205,248 347,356 453,498 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/ 60 0.75 3 5.3 6.2 15.0 3 7 .1 8.0 15.0 3 8.9 9.8 15.0 3 1 0.7 11.6 15.0 3 1 4.3 15.2 15.0 3 1 7.9 1 ...

  • Liebert 60 HZ - page 14

    10 G UIDE S PECIFICATIONS St andard Features for Direct Drive Propeller Fan Drycoolers Furnish and install Liebert Model ________ Air-Cooled Drycoo lers, arranged for vertical air flow. Dry- coolers shall be draw-through design and shall perform in accor- dance with the schedule. General Each drycooler shall consist of cas- ing, drycooler coil, pro ...

  • Liebert 60 HZ - page 15

    11 C OMPONENT A SSEMBLY /I NST ALLATION Leg Assembly The legs are shipped loose and are to be field mounted as shown with the hardware provided. Rigging Holes in the drycooler legs permit lifting the unit. Spreader bars are required. Four, 6 and 8 fan models have additional lifting eyes. High V olt age Electrical Connections Line Voltage is connect ...

  • Liebert 60 HZ - page 16

    12 A PPLICATION /I NST ALLATION G UIDELINES Location Guidelines To ensure an adequa te air supply, locate drycoolers in a clean air area , away from loose dirt and for- eign matter that may clog the coil. In addition, drycoolers must not be placed near steam, hot air, or fume exhausts. Also, drycoolers should be no closer than 3 feet from a wall, o ...

  • Liebert 60 HZ - page 17

    13 P UMP P ACKAGES & E XP ANSION T ANK - O PTIONS Figure 8 Pump p ackage Figure 9 Pump mounting Notes 1. Sin gle pump packages are 17-1/4" (438 .2 mm) wide. Dual pump packages are 32-1/4" (819.2 mm) wide. 2. Mounting holes are 15-11/32" (389.7 mm) apart on single pump packages and 30-11/32" (770.7 m m) apart on dual pump pac ...

  • Liebert 60 HZ - page 18

    14 S UPPLEMENT ARY A PPLICATION D AT A T able 9 Room dew point temperature s Dry bulb °F (°C) Wet bulb °F (°C) Rel. hum. % Dew point* °F (°C) 70 57.2 45 41.1 70 58.5 50 50.5 72 58.9 45 50.0 72 60.0 50 52.4 75 61.2 45 52.4 75 62.5 50 55.0 * Minimum glycol temperature before condensation will occur T able 10 Glycol concentration at various ambi ...

  • Liebert 60 HZ - page 19

    ...

  • Liebert 60 HZ - page 20

    The Comp any Behind the Product s With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems fo r sensitive electronics: • Env ironmental systems—close-control air conditioning from 1 to 60 t ...

Fabricant Liebert Catégorie Fan

Les documents que nous recevons du fabricant de l'appareilLiebert 60 HZ peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Liebert
- manuels d’utilisations 60 HZ
- fiches produit Liebert
- dépliants
- ou étiquettes-énergie Liebert 60 HZ
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Liebert 60 HZ.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Liebert 60 HZ, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Liebert 60 HZ. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Liebert 60 HZ.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Liebert 60 HZ, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Liebert 60 HZ par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Liebert 60 HZ.

Le manuel d’utilisation complet Liebert, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Liebert 60 HZ - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Liebert 60 HZ, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLiebert 60 HZ qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Liebert 60 HZ - qui devraient nous aider dans les premières étapes lors de l'utilisation Liebert 60 HZ
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Liebert 60 HZ
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Liebert 60 HZ dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Liebert 60 HZ?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Liebert 60 HZ, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Liebert 60 HZ il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)